Overview
The document outlines the specifications and operational principles of UVC water treatment systems, emphasizing their chemical-free, effective, and economical nature. It highlights the advantages of UVC radiation in treating various water sources, including saltwater, and its applications in different fields.

Principle of Treatment
UVC radiation, particularly at a wavelength of 253.7 nm, is effective in destroying microorganisms and certain molecules like chloramine and ozone. The treatment's effectiveness depends on the microorganism's sensitivity to UVC, which varies based on its biochemical composition.

Fields of Application
The UVC treatment is applicable in fish farms, aquariums, oyster farms, swimming pools, sea water, thermal spas, and wastewater released into the environment.

Generator Operating Principle
The system consists of a hydraulic reactor where water is exposed to UVC radiation without direct contact. The generator control involves electrical power supply, lamp condition checks, and monitoring the lamp life cycle.

Maintenance
Regular cleaning of the quartz sheath and timely replacement of lamps (every 18,000 hours) are crucial for proper functioning. If an upstream filter is used, its cartridge should be changed annually. Direct exposure to UVC lamp radiation should be avoided.

Sizing of the Generator
Proper sizing requires information on treatment rate, permeability to UVC radiation, system pressure, water temperature, application, and bacteriological requirements. This ensures safe and effective operation.

Guarantee
The system comes with a one-year parts and labor guarantee, excluding consumables and transport.

Technical Characteristics
The system requires 230 V, 50 Hz electrical power, operates at a service pressure of 3 bars, and has a maximum water temperature of 30°C. It features a waterproof HDPE case and can be installed horizontally or vertically.

Standard Installation
Installation requires unobstructed space for lamp replacement, an upstream filter for cleanliness, an air purge at the high point, a support cradle for the chamber, and anti-vibration expansion sleeves.

Model Specifications
The document provides detailed specifications for different models, including part numbers, number of lamps, total power, inlet/outlet diameter, and dimensions.

Spare Parts
Information on spare parts such as UVC lamps, quartz seals, and removal keys is provided.
See more

Catalog excerpts

RANGE V (HDPE)-1

UVc GENERATOR Range V (HDPE) SynthEtiC (Rating 0 to 50 m3/h) PRINCIPLE OF TREATMENT UVc electromagnetic radiation wavelengths are expressed in nanometres (nm). Exposure to UVc radiation can have various consequences, depending on the radiation wavelength. Each micro-organism has a specific sensitivity to UVc, depending on its bio-chemical composition. Any living cell can be destroyed by UVc radiation at 253,7 nm. UVc radiation also acts on certain molecules, such as chloramine or ozone. Depending on the problems posed by your water supply, COMAP specialists will provide the necessary expertise to ensure that your solution is properly sized. Fields of Application The V HDPE range treats salt water. Possible applications are: - sh farms, fi - quariums, a - yster farms, o - wimming pools (public and private), s - ea water, s - thermal spas/thalassotherapy/balneotherapy. Waste water released into the natural environment. Major advantages of UVc - No chemicals used. - Guaranteed effective (properly sized). - Simple, reliable and economical water treatment. Generator operating principleR 1. Hydraulic reactor: The generator inlet and outlet are both connected to your water system. When the water enters the chamber, it is subjected to UVc radiation, with no direct contact. The lamps are protected by waterproof quartz tubes. When leaving the reactor, the water is treated. 2. Generator control: - electrical power supply, - check lamp condition, - monitor lamp life cycle.

 Open the catalog to page 1
RANGE V (HDPE)-2

UVc GENERATOR Range V (HDPE) SynthETIC (Rating 0 to 50 m3/h) Technical Characteristics - Electrical power required: 230 V, 50 Hz + earth. - Service pressure: 3 bars. - Test pressure: 6 bars. - HDPE case. - lean the UVc generator quartz sheath regularly - see the C servicing/maintenance document. - amps must be changed every 18000 hours. If this is not done, L the generator cannot function properly. - f an upstream filter is installed, the cartridge should be changed I annually. - Never expose yourself to UVc lamp radiation. Standard Installation - he generators can be installed horizontally or...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.