1. Catalogs
  2. COMADAN
  3. RT18, Star-delta relay

RT18, Star-delta relay

RT18, Star-delta relay

Product catalog summary
Overview: The C-mac® Star/Delta Relay Type RT18 is a timing relay designed for controlling star-delta contactors. It features automatic start and offers four time ranges from 0.4 seconds to 10 minutes. The relay includes a built-in potentiometer for time adjustment and a 1-pole relay output with a neutral center position.
Specifications:
  • Supply Voltage: Options include 24 VAC/DC, 127 VAC/220 VAC, 230 VAC/400 VAC, and 240 VAC/415 VAC.
  • Power Consumption: Maximum of 2 W.
  • Operating Temperature: -20°C to +60°C.
  • Humidity: 0 - 90% RH, non-condensing.
  • Relay Output: 1-pole 8 A - 250 VAC, 2-pole 5 A - 250 VAC, ohmic load.
Functionality: Upon connection of the supply voltage, the relay activates in position 1-4, initiating the timing period. After the set delay, it switches to a neutral center position for approximately 100 milliseconds before moving to position 1-3, where it remains until the supply voltage is interrupted.
Time Ranges: The relay offers time ranges of 0.4 - 15 seconds, 0.8 - 30 seconds, 1.5 - 60 seconds, and 0.25 - 10 minutes. Time adjustment is possible from 2.5% to 100% of the range with an accuracy of 5% and repeatability of 0.1%.
Compliance and Safety: The relay complies with EMC and safety regulations, including EN 50 081-1 for emission, EN 50 082-2 for immunity, and EN 60 730 for safety. It is CE approved and adheres to low voltage regulations.
Indications: The relay features a green LED for position 1-4 and a red LED for position 1-3.
Ordering Information: The relay is available in different models based on supply voltage and time range. For example, RT18-2-1-230/400-60S is a model for 230/400 VAC with a specific time range.
See more

Catalog excerpts

RT18, Star-delta relay-1

Star/delta relay type RT18 Timing relay for star-delta switches Automatic start 4 time ranges from 0,4 sec. to 10 min. Time adjustment on built-in potentiometer 1-pole relay output with neutral centre position 100 msec. fixed neutral time Phase-neutral or phase-phase supply voltage Made in accordance with the and EMC regulations C-mac® time relay type RT18 is particularly made for the control of star-delta contactors. When the supply voltage is connected, the relay activates in position 1-4, and the time period starts. At the end of the set delay, the relay switches to neutral centre position for approx. 100 msec. Then it switches to position 1-3 and stays in this position, until the supply voltage is interrupted. Technical data: Supply voltage Power consumption: Operation temp.: Humidity: Indications: Green LED: Red LED: Time adjustment: Accuracy, scale: Repeatability: Reset of time and/or relay: Max. load, relay: 24 VAC/DC 127 VAC / 220 VAC 230 VAC / 400 VAC 240 VAC / 415 VAC max. 2 W -20°C til +60°C 0 - 90% RH, non-condensing Relay, position 1-4 Relay, position 1-3 2,5 - 100 % of the range 5 %. 0,1 % Supply voltage interruption for more than 0,2 sec. 1-pole 8 A - 250 VAC 2-pole: 5 A - 250 VAC, ohmic load EMC og safety regulations. Emmision: EN 50 081 - 1 Immunity: EN 50 082 - 2 Safety: EN 60 730 Approvals: The units are produced in accordance with the CE og low voltage regulations. Note: At 24 V AC/DC supply, pin 9 is not connected. (pin 2 is +) Functional diagram: supply relay, 1-4 Ordering guide: Supply Type number xxx = time ranges see table on previous page Ordering example: RT18-2-1-230/400-60S Mechanical dimensions.: see pagee 9-2

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.