1. Catalogs
  2. COMADAN
  3. RC12/RV12, current and voltage relays

RC12/RV12, current and voltage relays
1 /2Pages

RC12/RV12, current and voltage relays

RC12/RV12, current and voltage relays
1 /2Pages

Catalog excerpts

RC12/RV12, current and voltage relays-1

RC12: Current monitoring RV12: Voltage monitoring 3 metering inputs in each module Adjustments for setpoint and hysteresis Selectable relay inversion and AC/DC mode DC supply or AC supplies up to 230 VAC Made in accordance with the and EMC regulations C-mac® current monitoring relay, type RC12, and voltage monitoring relay, type RV12, are universal metering relays, each supplied with 3 metering ranges, from 4 mA to 6 A or 400 mV to 600 V AC or DC, respectively. The input range is chosen by use of the appropriate input terminal, and the choice of AC/DC metering and relay inversionis made by connection/disconnection of terminal 5 and 8 to common (terminal 7). When the module is AC metering, the average value is metered, and the level adjustment is then calibrated to the r.m.s. value of a sinusoidal signal. Metering ranges, max. input signals and input impedances (Rin): Module Power consumption: Operation temp.: Humidity: Adjustments: Level: Hysteresis: Indications: Green LED: Red LED: Accuracy, scale: Temp. coefficient: Max. load, relay: Common technical data: Supply voltage, AC: Supply frequency: Variable supply: Isolation voltage: Supply voltage, DC: 24, 115 and 230 VAC +/- 10% 40-70 Hz 12-50 VDC or 48-250 VDC Supply - input - output: 3.75 kV 24 VDC +/- 10% Note: With this DC-supply there is no isolation between supply and internal electronics. 2,5 VA -20°C to +60°C 0 - 90% RH, non-condensing Connections RC12. DC metering: 7-8 closed AC metering: 7-8 open Potentiometer, scale 0.4 to 6 Potentiometer, scale 5 to 50% Supply voltage connected Relay active 5% typ 0,1 % / °C 1-pole: 8 A - 250 VAC ohmic load Connections RV12. DC metering: 7-8 closed AC metering: 7-8 open

 Open the catalog to page 1
RC12/RV12, current and voltage relays-2

EMC and safety regulations. Emmision: EN 50 081 - 1 Immunity: EN 50 082 - 2 Safety: EN 60 730 Approvals: The units are produced in accordance with the CE og low voltage regulations. Ordering guide, RV12: Supply 12-50 VDC 24 VDC 24 VAC 115 VAC 230 VAC Mechanical dimensions: 38 mm C-mac Functional diagram: setpoint hysteresis input relay, ex. 1 Supply Relay Materials and weight: Example 1, undercurrent/voltage monitoring pin 6-7 not connected Example 2, overcurrent/voltage monitoring pin 6-7 connected Housing: NORYL-SE-1, grey, self-extinguishing Housing bottom: NORYL SE-1, GFN-2, black, self-extinguishing...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.