1. Catalogs
  2. COMADAN
  3. Programmable converter PMR10

Programmable converter PMR10

Programmable converter PMR10

Programmable converter PMR10

Product catalog summary
Overview: The PMR10 is a programmable converter and isolation amplifier designed for various input types including temperature, resistance, pulse, and analogue inputs, with outputs in current, voltage, pulse, or relay forms. It supports both DC and AC supply voltages up to 400 VAC and complies with EMC regulations.
Specifications: The PMR10 supports temperature inputs from RTD and thermocouple sensors, potentiometer or variable resistor inputs, and provides sensor supply for NPN, PNP, NAMUR, and analogue inputs. It offers galvanic separation between supply, input, and output.
Input Functions: The unit can monitor temperature using 3-wire RTD sensors (Pt100, Pt500, Pt1000, Ni100, Ni500, Ni1000) and thermocouple sensors (types J, K, R, S, T, B, N, E). It compensates for sensor non-linearity and offers internal or external cold junction compensation for thermocouples. Potentiometer and resistor monitoring are also supported, with outputs reflecting actual values.
Output Configurations: Two types are available: Type A with analogue current (0-20 mA) and voltage (-10 to +10 V) outputs, and Type B with additional pulse output (up to 10 kHz). The unit includes trimming potentiometers for fine adjustments, which can be disabled if not needed.
Programming and Adjustments: The PMR10 can be programmed using C-mac software and a PC interface. It allows for fine adjustments via potentiometers P1 and P2, with procedures to reset to original settings if needed. Programming can be done with or without supply voltage connected.
Technical Data: The unit features various input impedances and supports a wide range of sensor types and configurations. It operates within a temperature range of -20°C to +60°C and humidity up to 90% RH. The PMR10 is designed for panel mounting with specific spacing requirements.
Ordering Information: The PMR10 is available in basic units without range programming or with specified ranges. It can be ordered with different supply voltages and output configurations.
Performance and Compliance: The PMR10 offers high accuracy and speed, with conversion delays programmable up to 4 seconds. It complies with CE and high voltage regulations, ensuring safety and reliability in industrial applications.
See more

Catalog excerpts

Programmable converter PMR10-1

Temperature inputs from RTD or thermocouple sensors Potentiometer or variable resistor inputs Sensor supply for NPN, PNP, NAMUR and analogue inputs Analogue or pulse outputs Galvanic separation, supply - input - output DC supply or AC supply voltages up to 400 VAC Made in accordance with the and EMC regulations PMR10 is a multirange converter / isolation amplifier with temperature, resistance, pulse and analogue inputs and current, voltage, pulse or relay outputs. The unit has a number of programmable input functions: Temperature monitoring with 3-wire RTD sensors Pt100, Pt500; Pt1000, Ni100, Ni500 and Ni1000, including sensor cable monitoring. Temperature monitoring with thermocouple sensors type J (Fe-CuNi), type K (NiCr-Ni), type R (Pt13%RhPt), type S (Pt10%Rh-Pt), type T (Cu-CuNi), type B (Pt30%Rh-Pt6% Rh), type N (Nicrosil-Nisil) or type E (NiCr-CuNi). When the unit is programmed for thermocouple sensor, you can select between internal Cold Junction Compensation and external CJC-box, which gives a higher accuracy.No matter which type of temperature sensor is used, the unit will compensate for the unlinearity of the sensor. Potentiometer monitoring. If this function is selected, the output signal will indicate the actual position of the potentiometer, independent of the total value of the potentiometer. Resistor monitoring. With resistor monitoring the output signal is an expression of the actual value of the resistor, compared with the programmed metering range. Speed monitoring with programmable inputs from NPN, PNP or NAMUR sensors, including supply voltage for the sensor. Input signals from analogue transducers, including supply voltage for the transducer. You can select between 2 different output configurations: • Type A is supplied with analogue current output, programmable between 0 and 20 mA and analogue voltage output, programmable between -10 and +10 V. If you want, you can order the unit with specified metering ranges, or you can program it yourself, by means of the Cmac programming software for PC and a small interface to connect between the PC and the module. All parameters in the converter are programmable within the specified limitations (min. and max. input and output levels), giving the following possibilities: • Basic converter, (0 to defined input range and standard output range, 0-20 mA, 4-20 mA or 0-10 V). • Converter with input and/or output offset, e.g. 10 to 50 °C input and 8 to 15 mA output. • Bidirectional output range (only voltage output), e.g. -10 to +10 V. • Type B has the same outputs as type A, but in addition it is also supplied with pulse output, programmable to a maximum frequency of 10 kHz. The unit is supplied with 2 trimming potentiometers, which can be used to fine-adjust the metering range, if the unit is used with analogue outputs. In either case the potentiometers can be disabled, if the adjustment possibility is not wanted. • Inverted function with or without offset, e.g. 150 to 20 S input and 4 to 20 mA output.

 Open the catalog to page 1
Programmable converter PMR10-2

Supply voltage. sensor cable monitor current input voltage input NPN/PNP input NAMUR supply input common 12: pulse output (type PCV10-B only) Programmable converter Connection drawings: Supply voltage: Sensor inputs: NAMUR sensor Analogue transducer Analogue voltage output: Programmable ranges Pulse outputs (type PMR10-B only): Eksternal load: Eksternal load: Pulse output.

 Open the catalog to page 2
Programmable converter PMR10-3

Mechanical dimensions: Materials: CYCOLOY C2100, grey Frontplate: CYCOLOY C2100, grey Terminal cover: CYCOLOY C2100, black Terminals: nickel plated brass Screws: nickel plated iron Housing base: C-mac Supply Programmable converter Programming connections and adjustments: Potentiometers P1 and P2. Programming connector CON. Connects to the PC via C-mac interface cable. PMR10-A and PMR10-B: The interface unit is internally battery powered, which means it is not necessary to connect any P1 = Offset fine adjust +/- 5% external supply voltage to the PMR unit during P2 = Span fine adjust +/- 5% programming....

 Open the catalog to page 3
Programmable converter PMR10-4

Technical data: Supply voltage AC: Supply frequency: Supply voltage DC: Isolation voltages: Power consumption: Operation temp.: Humidity: Temp. coefficient: 24, 115, 230 and 400 VAC +/- 10% 40-70 Hz 12-50 VDC Supply - internal electronics: 3,75 kV Input - output: 2.5 kV 6 VA -20°C to +60°C 0-90% RH, non condensing < 0.003% /°C EMC data. Emission: Immunity: Safety: Approvals. EN 50 081 - 1 EN 50 082 - 2 EN 60 730 - 1 The module is produced in accordance with CE and high voltage regulations. Speed and accuracy. Conversion speed: Accuracy: RTD sensors: Thermocouple: remaining ranges: Linearity:...

 Open the catalog to page 4