CB LCS-150E.1 LEVEL CONTROL SYSTEM-1

Model Intermediate Level Control Single Tank LCS-150e.1 CB LCS-150E.1 LEVEL CONTROL SYSTEM The Cleaver-Brooks LCS-150E.1 Level Control System utilizes a level transmitter and programmable controller to control water level and water level alarms. System includes modulating make-up valve with user-selectable manual or automatic control. FEATURES AND BENEFITS Standard Features: • Programmable controller with display, trending, data logging, and Modbus RTU communications • Set points, alarm points, transmitter span, and PI controls configurable using controller keypad • Manual or automatic control of up to two make-up valves • Easy-to-read level indication • No sight glass - water is contained in a pressure-tight housing PRODUCT OFFERING The following are included as standard in each LCS-150E.1 control system: • Programmable controller • Controller display with keypad • I/O module • Level sensor and transmitter • Modulating feed water valve and actuator • Alarm horn and silence button • High-High, High, Low, Low-Low and Low Water Cut-Off alarm lights ENGINEERING DATA • Supply voltage 120 VAC • Max load 3 amps • Ambient temperature range 32 - 122 deg F • Humidity, non condensing 5-95% • Degree of protection - Display/keypad: IP65, Type 3R, Type 12R - Panel Nema 4/12 - Lights and switches IP66 - Level indicator / transmitter Nema 4 - Siemens valve Nema 1; optional weather shield will change it to Nema 3R Section D06-1 Rev. 03-11

 Open the catalog to page 1
CB LCS-150E.1 LEVEL CONTROL SYSTEM-2

Model Intermediate Level Control Single Tank LCS-150e.1 Sample Specifications CB LCS-150E.1 Level Control System 1.1 GENERAL General A. Each LCS-150E.1 system shall be factory equipped with controller including display and I/O, NEMA 12 cabinet, primary and optional secondary make up valves and GEMS magnetic level sensor with transmitter. B. System shall provide the following functions: 1. Adjustable transmitter span 2. Individual adjustable water level set point for each MUV 3. Adjustable high-high water alarm point (with differential) 4. Adjustable high water alarm point (with differential)...

 Open the catalog to page 2
CB LCS-150E.1 LEVEL CONTROL SYSTEM-3

Model Intermediate Level Control Single Tank LCS-150e.1 D. Alarms 1. Panel mounted alarm horn 2. Alarm silence switch 3. LED alarm lights for High-High, High, Low, Low-Low and Low Water Cut- Off 4. Customer Relay contacts for High-High, High, Low, Low-Low and Low Water Cut-Off Section D06-3 Rev. 03-11

 Open the catalog to page 3

All Cleaver-Brooks catalogs and technical brochures

  1. LCS150e.1

    2  Pages

  2. LCS250e.1

    2  Pages

  3. LevelMaster

    4  Pages

  4. Model 4

    4  Pages

  5. Model 5

    4  Pages

  6. Oil Pump Set

    12  Pages

  7. PCS140e.1

    2  Pages

  8. ProFire-D

    8  Pages

  9. ProFire-NTH

    4  Pages

  10. ProFire-S1

    4  Pages

  11. Stack Damper

    2  Pages

  12. LC ClearFire

    8  Pages

  13. Heat Recovery

    8  Pages

  14. SCR

    4  Pages

  15. FLX Flextube

    8  Pages

  16. ADAC

    2  Pages

  17. 4WI - CBLE

    8  Pages

  18. CBR

    4  Pages

  19. ICB

    8  Pages

  20. CBL

    4  Pages

  21. Ohio Special

    4  Pages

  22. CB Accu-Draft

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.