Model SF125, 125 BHP Steam Generator
2Pages

{{requestButtons}}

Catalog excerpts

Model SF125, 125 BHP Steam Generator - 1

Technical Specifications The Next Generation of Clayton Steam Generators Available in the following configurations: •Standard configuration for most installations. •Super Economizer (SE) for increased efficiency. •Low NOx Fiber Metal Burner (FMB) for NOx levels below 12 ppmv. •Step-fired and fully modulating burners. •Fuel Options: Natural Gas, Propane, #2 Fuel Oil, Biogas and Hydrogen The SigmaFire: • SAVES FUEL The unique counter flow design provides higher fuel-to- steam efficiency than traditional boilers. • IS SAFE FOR PERSONNEL AND EQUIPMENT Inherently safe, the Clayton design eliminates hazardous steam explosions. • PROVIDES RAPID RESPONSE The Clayton design responds rapidly to sudden or fluctuating load demands. • STARTS FAST The Clayton design will provide full output from a cold start within five minutes, without thermal stress. • IS COMPACT AND LIGHTWEIGHT The Clayton design typically occupies one-third of the floor space and weighs 75% less than a traditional boiler. • ENSURES HIGH QUALITY STEAM Clayton offers a 99.5% quality separator to minimize moisture in the steam. • OFFERS ADVANCED CONTROLS Digital controllers, PLC’s and a linkage-less servo con- trolled burner management system is available. • INCLUDES OUTSTANDING SUPPORT Every Steam Generator is backed by Clayton factory direct sales and service plus full service feedwater treatement. SigmaFire 125 BHP Steam Generator

Open the catalog to page 1
Model SF125, 125 BHP Steam Generator - 2

MODEL SF125 BOILER HORSEPOWER HEAT INPUT, BTU/hr MODEL SF125-SE-FMB MODEL SF125-SE MODEL SF125-FMB with Low NOx FMB Burner with Super Economizer with Low NOx FMB Burner and Super Economizer 125 125 125 4,865,552 NA NA 4,922,794 5,165,895 4,922,794 4,184,375 4,184,375 4,184,375 NET HEAT OUTPUT, BTU/hr EQUIVALENT OUTPUT (from and at 212°F 4,313 lbs/hr 4,313 lbs/hr 4,313 lbs/hr 4,313 lbs/hr feedwater and 0 PSIG steam) 15 - 500 psig 15 - 500 psig 15 - 500 psig 15 - 500 psig DESIGN PRESSURE (see note 1) 13 - 450 psig 13 - 450 psig 13 - 450 psig 13 - 450 psig STEAM OPERATING PRESSURE (determined...

Open the catalog to page 2

All CLAYTON INDUSTRIES catalogs and technical brochures

  1. PLC Control

    2 Pages

  2. Hotwell

    2 Pages

Archived catalogs