Technical documentation - Fire-fighting flexible tank
10Pages

{{requestButtons}}

Catalog excerpts

Technical documentation - Fire-fighting flexible tank - 1

Designer and manufacturer of flexible tanks FLEXIBLE TANK • FIRE-FIGHTING FIRE FIGHTING Citerneo specialise in the design and manufacture of high quality flexible tanks for the storage of liquids. The CITERNEO group offer a 100 % r ecyclable range that meets the technical needs of the global market. PRODUCT PRESENTATION MADE TECHNICAL FEATURES FLEXIBLE TANK ADVANTAGES EQUIPMENT INSTALLATION GUIDE ISO 9001 CERTIFICATE GUARANTEE GENERAL TERMS AND CONDITIONS www.citerneo.eu Date de création : 15/03/2017

Open the catalog to page 1
Technical documentation - Fire-fighting flexible tank - 2

This equipment is a watertight enclosed flexible and foldable tank, which structure is formed by an exclusive technical fabric coated with PVC. The tanks offer total protection of their contents. Thanks to the design, the stored products are in permanent contact with the internal walls of the tank, which means they are not in contact with any exterior elements. This aspect prevents any evaporation, colouring or lteration a of the water. Storage of water for fire-fighting is frequently used for the protection of buildings that are not covered by the c lassic fire-fighting network (industrial...

Open the catalog to page 2
Technical documentation - Fire-fighting flexible tank - 3

TECHNICAL FEATURES Range Coating type Completion Fire resistance Frame breaking strength Resistance to tears Weld tensile resistance Resistance to puncturing Temperature resistance range Material Thread Armour PVC Biface varnish Flammability speed ISO 3795 Q ADVANTAGES Economical solution No evaporation Total protection Net volume storage High capacity up to 2000 m3 Minimal earthwork Simple and fast to install ii Compact and foldable No needs of building permit A transportable solution Easily integrable in the environment

Open the catalog to page 3
Technical documentation - Fire-fighting flexible tank - 4

SOILLESS VERSION: DN 100 Knife gate valve with revolving connection and ecurtex 3 antivortex S Multilayer thermal valve protection FREEZE-FREE VERSION: BLUE DRY HYDRANT VERSION 1 Sleeve to glue DN110 elbow and 2x2 pipe to glue DN 100 reversible suction outlet in S Automatic purge system Block valve, operating stem with 30x30 manipulation square DN 100 revolving connection with cork BLUE FIRE HYDRANT VERSION 1 DN 100 bridle Securtex 3 antivortex Sleeve to glue DN110 elbow and 2x2 pipe to glue 9 Cast iron bridle Freezeless reversible fire hydrant with revolving connection and cork. THE TANK...

Open the catalog to page 4
Technical documentation - Fire-fighting flexible tank - 5

SURFACE PREPARATION: Slope to the center of the platform (1 %) A 15 to 20 cm bedding of compacted gravel is r ecommended to ensure the stability of the platform. A 10 cm (+/- 2 cm) layer of sand (0/2 cm) is then necessary to avoid puncturing. The dimensions of the platform area must match those of the empty tank plus an area of 0,50 meter minimum on each side of the tank. The platform must support the weight of the full tank w ithout sagging or eroding. The earthwork shall be carried out in accordance with the opposite diagram. Clean and leveled ground + layer of sand (0/2 cm) 10 cm (+/- 2...

Open the catalog to page 5
Technical documentation - Fire-fighting flexible tank - 6

Follow filling instructions The filling can be carried out by gravity or by pumping through the inspection hatch or by the suction and / or filling devices. Any soilless connection to the tank must be flexible to bsorb level a variations. Do not obstruct in any case the overflow and never put a flexible tank under pressure. The selection and positionning of the equipment depend on the use. If the filling is not done immediately, it is recommended to ballast the tank with a minimum of 5 cm of liquid. Please observe and follow the instructions on the tank label. TECHNICAL OBLIGATION: The...

Open the catalog to page 6
Technical documentation - Fire-fighting flexible tank - 7

Certificate of Approval This is to certify that the Management System of: CITERNEO ZI La Boitardiere, 124 rue de la Girardière, 37402 AMBOISE, France has been approved by LRQA to the following standards: ISO 9001:2015 Gilles Bessiere - Area Technical Manager Issued by: LRQA France SAS for and on behalf of: Lloyd's Register Quality Assurance Limited Current issue date: 8 January 2019 Expiry date: 5 January 2022 Certificate identity number: 10163742 Original approval(s): ISO 9001 – 6 January 2013 Approval number(s): ISO 9001 – 0032752 The scope of this approval is applicable to: Design and...

Open the catalog to page 7
Technical documentation - Fire-fighting flexible tank - 8

GUARANTEE* 69/01-322 GENERAL INFORMATION TO THE ATTENTION OF THE BUYER-USER OF FREESTANDING FLEXIBLE TANK The guarantee period is indicated in the contractual documentation. The guarantee period is one year for the equipment of the tank and electromechanical equipment provided that the installation and the utilisation of the tank comply with the recommended procedures. No depreciation coefficient is applied to this warranty. CITERNEO flexible tanks for water storage are designed to resist a storage temperature from -30 °C to +70 °C. Any storage of liquid which do not comply with the...

Open the catalog to page 8
Technical documentation - Fire-fighting flexible tank - 9

GENERAL TERMS AND CONDITIONS 69/01-322 1- OBJECT The purpose of the present General Terms and Conditions is to define the conditions under which the C ITERNEO Company is committed to its Customer to selling the products concerned by the Quotation-order form.All correspondence must be written in French. 2- SCOPE 2.1 The present General Terms and Conditions, the Quotation-order form as well as any related documents (such as those relating to warnings and recommendations) constitute the entire Contract between the p arties. They shall supersede any principle agreement or exchange of...

Open the catalog to page 9
Technical documentation - Fire-fighting flexible tank - 10

ZI de la Boitardière 124 rue de la Girardière BP226 37402 AMBOISE Cedex FRANCE