Application
The UFO-3AW emergency battery pack is designed to work with fluorescent fixtures' normal AC ballasts to provide emergency lighting, eliminating the need for additional emergency units. It supports 32W to 40W T8, T10, or T12 fluorescent lamps without integral starters and is compatible with various AC ballasts. For emergency-only fixtures, no AC ballast is needed.

Construction
The unit features a compact 22-gauge sheet metal case with a black enamel finish. It includes a solid-state charger, automatic transfer circuit, test switch, LED charge indicator, high-frequency inverter, and a high-temperature Nickel-Cadmium battery.

Installation
The UFO-3AW does not affect normal fixture operation and can be used with switched or unswitched fixtures. It must be connected to the same branch circuit as the AC ballast and can be installed inside, on top of, or remote from the fixture, up to 50 feet away. It is not suitable for heated air outlet fixtures or wet/hazardous locations and should not be used where temperatures fall below 0°C (32°F).

Illumination
The unit provides 350-450 lumens of initial emergency light output, illuminating one lamp during emergencies.

Compliances
UL 924 Damp Location Listed, NFPA 101, NFPA 70.

Warranty
5 Years Full Warranty.

Operation
The UFO-3AW provides a minimum of 90 minutes of emergency lighting for one lamp in 2-4 foot fixtures. It operates automatically, switching to emergency mode upon power interruption and recharging within 24 hours. It supports dual input (120 or 277VAC, 60Hz) and includes a test switch and LED indicator.

Standard Features
Compatible with various AC ballasts, provides 90 minutes of lighting, features a heavy steel battery case, dual input operation, maintenance-free battery, and versatile mounting options.

Operating Temperature Range
0˚C to 50˚C (32˚F to 122˚F).

Weight
2.1 lbs (0.94kg).

Specifications
Dimensions: 9.4”L x 2.4”W x 1.5”H. Input wattage: 3.5W, Output wattage: 9.6W, Lamp types: T8, T10, T12, Circline 4-pin, Lumens: 350-450.
See more

Catalog excerpts

Lampak UFO-3AW specification sheet-1

Emergency Lighting Fluorescent Battery Pack Catalog Number The UFO-3AW emergency battery pack works in conjunction with a fluorescent fixture’s normal AC ballast to convert new or existing fluorescent fixtures for emergency lighting operation, eliminating the need to install additional emergency lighting units. The UFO-3AW can be used with one 32W through 40W (2’ - 4’) T8, T10, or T12 fluorescent lamp without integral starters, including U-shaped, HO, VHO and circline. It is also compatible with most 1, 2, 3, and 4-lamp electronic, standard magnetic, end-of-lamp-life and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. For information about specific lamps and ballast compatibility, please contact the factory. All unit housings consist of a compact case constructed of 22 gauge sheet metal finished in black enamel. The unit contains a solid-state charger with automatic transfer circuit, test switch, LED charge indicator light, a dependable, high-frequency inverter and a high-temperature, Nickel-Cadmium battery. Model UFO-3AW emergency battery pack does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency battery pack. The emergency battery pack must be fed from the same branch circuit as the AC ballast. The UFO-3AW may be installed inside, on top of, or remote from the fixture. The emergency battery pack may be remotely installed up to half the distance from the lamp the AC ballast manufacturer recommends, or up to 50 feet, whichever is less. UFO-3AW emergency battery packs are not suitable for installation in heated air outlet fixtures and wet or hazardous location fixtures. Installation is not recommended with fixtures where the ambient temperature may fall below 0°C (32°F). The UFO-3AW produces 350-450 lumens initial emergency light output. During emergency illumination, one lamp is illuminated, even if installed with a multi-lamp fluorescent fixture. UL 924 Damp Location Listed NFPA 101 (Life Safety Code) NFPA 70 (National Electrical Code) 5 Years Full Warranty ORDERING GUIDE ACCESSORIES (ORDER SEPARATELY) F-WC Remote test switch/charge indicator module(2) (1) Encloses exposed wiring harness when power pack is externally mounted on the lighting fixture. One required per fixture. (2) Fits single-gang box.

 Open the catalog to page 1
Lampak UFO-3AW specification sheet-2

Emergency Lighting Fluorescent Battery Pack SPECIFICATIONS Operation UFO-3AW emergency fluorescent battery packs are designed to provide a minimum of 90 minutes of emergency lighting to one lamp in 2-4 foot commercial or industrial fixtures. Operation is fully automatic. A solid-state charger maintains the battery at full charge as long as utility power is present. Upon interruption of normal power, the unit will activate and the automatic transfer circuit will switch to the emergency mode, keeping one lamp illuminated at a reduced lumen output for a minimum of 90 minutes. Upon restoration of...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.