TNM 96 ETN-I

TNM 96 ETN-I

TNM 96 ETN-I

Product catalog summary
Overview: The TNM96 ETN-I is a compact, highly accurate three-phase multifunction meter with an accuracy of 0.2% (0.1% optional). It records energy consumption and supports BACnet and Modbus protocols. Configuration and operation can be done via a web browser using the Ethernet TCP/IP interface. It is designed to display and evaluate min/max values, active, apparent, and reactive power, and harmonics up to 64th order.
Technical Specifications:
  • Auxiliary Voltage: 90 - 250 VAC, 50/60 Hz; 110 - 280 VDC; 8 VA
  • Dimensions: 96 x 96 x 80 mm
  • Weight: 650 g
  • Accuracy: Active and Reactive power 0.2%
  • Environmental Conditions: Operating temperature -20 to 70 °C; Storage temperature -20 to 80 °C; Humidity 0 - 95% RH
  • Display: 85 x 64 color display, IP64 protection
  • Channels/Current Inputs: 1/3
  • Sampling Rate: 1600
  • Digital Input/Output: 2/1
  • Harmonic Distortion: Total and Partial Harmonic Distortion for current and voltage
  • Supported Current Transformers: 0.333V, 1A, 5A
Features:
  • Graphic display of harmonic distortion and waveform
  • Easy-to-use multilingual menus
  • Data logging and built-in rate meter
  • Alarms with memory for minimum/maximum measurements
Measurement Ranges:
  • Current: 0.001 - 6 A; Overload 50 A; Short term 100 A
  • Voltage L-L: 0 - 950 V; L-N: 0 - 550 V; Maximum 1000 V
  • Frequency: 45.001 - 65.001 Hz
  • Power Factor: -1 to +1
  • Power Measurements: Active, Reactive, Apparent power and work for total/phase
  • Total Harmonic Distortion: 0.000 - 100.0%
Communication: Supports BACnet MS/TP and TCP/IP, Modbus RS485 and TCP/IP, and is browser-enabled.
Standards: Complies with IEC 62052-23, IEC 62052-22, IEC 62052-11, EN 61000 series, and EN 55024/55022 standards.
See more

Catalog excerpts

TNM 96 ETN-I-1

Basic data The TNM96 is a compact, very accurate 0.2% (0.1 optional), three-phase multifunction meter. It includes energy consumption recording and supports BACnet and Modbus protocols. The meter can be operated and configured via a web browser using the Ethernet TCP/IP interface. An indispensable aid for displaying and evaluating via additional software the min/max values, active, apparent and reactive power, and harmonics up to 64en, as well as all important measured variables. Celsa Messgerate GmbH In den Rauhweiden 17 67354 Romerberg Germany

 Open the catalog to page 1
TNM 96 ETN-I-2

Technical data IEC 62052-23 IEC 62052-22 IEC 62052-11 EN 61000-4-11 EN 61000-4-6 EN 61000-4-5 EN 61000-4-4 EN 61000-4-3 EN 61000-4-2 EN 61000-3-2, Class A EN 61000-3-3, Amendments A1 EN 55024, Amendments A1; A2 EN 55022, Class A, Amendments A1; A2 Celsa Messgerate GmbH Fon: +49 6232 66291-0 Datum 8.i2.2023 Germany www.celsa-messgeraete.de

 Open the catalog to page 2

All Celsa Messgeräte GmbH catalogs and technical brochures

  1. WST 40

    3  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.