REVO S-1PH from 30A to 40A
4Pages

{{requestButtons}}

Catalog excerpts

REVO S-1PH from 30A to 40A - 1

GENERAL DESCRIPTION Revo S has been specifically designed to save space and labour These simple units can be connected with REVO PC to manage multizone system this minimize your energy cost by controlling synchronization and power limit on each zone Integrated fuse + fuse holder is necessary to have a complete power control zone including current transformer and optional circuit board Flat Cable Wiring System (option) to connect in plug in mode many Revo S when HB alarm or analog input are used Input signal: SSR, Analog as an option Zero Crossing, Burst Firing available at 4, 8 or 16 Cycles at 50% of Power demand Electronic fully isolated from power with constant current drain on input. Heater Break alarm option to diagnose partial or total load failure and Thyristor Short circuit Total Load Faillure Alarm at low cost it’s also available Fuse and Fuse holder available as an option Current transformer integrated (with Heather Break option) Special design for Heat sink with very high dissipation value Comply with EMC, cUL DIN RAIL side by side mounting IP20 Protection TECHNICAL SPECIFICATION Voltage power supply Voltage Frequency 50 or 60 Hz no setting needed from 47 to 70 Hz Nominal Current Input Signal SSR for REVO S, Fuse + Fuse Holder SSR for REVO S, Fuse + Fuse Holder,+ HB Voltage input Current input Zero Crossing, Burst Firing with analog input signal only Auxiliary Voltage Supply 12:24V dc/ac (max 70 mA) required only with HB Alarm or Analog Input Option Heater Break Alarm Partial Load Failure Alarm Microprocessor based with automatic setting via Digital Input; Relay Output 0,5A at 110V Total Load Failure Alarm at low cost it’s an alternative at standard HB DIN RAIL or panel mounting Operating Temperature 40 °C without derating. Over this temperature see below derating curve Storage temperature Over 1000 m of altitude reduce the nominal current of 2% for each 100m From 5 to 95% without condense and ice Derating curve USER’S MANUAL

Open the catalog to page 1
REVO S-1PH from 30A to 40A - 2

OPTION’S FEATURES AND SPECIAL DETAILS OPTION’S FEATURES AND SPECIAL DETAILS (HB) HEATER BREAK ALARM (HB) Microprocessor based circuit Capacity to diagnose the failure of one Resistance over five in parallel Load failure alarm with LED indication on front unit Thyristor short circuit alarm with LED indication on front unit Alarm output with free voltage relay contact Alarm reset function and possibility to auto reset if the alarm disappear Built in Current transformer when heater Break option has been selected Self Setting via external command or push button on front unit Commom setting...

Open the catalog to page 2
REVO S-1PH from 30A to 40A - 3

WIRING CONNECTION REVO S 1PH from 30 to 40A NOTE (1) • A suitable device must ensure that the unit can be electrically isolated from the supply, this allows the qualified people to work in safety. • The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator. The semiconductor fuses are classified for UL as supplementar protection for semiconductor. (2) • The heat-sink must be connected to the earth. (3) • Only for the HB option (4) • Only for the Analog Input option. 2 (5) • Use the extrarapid fuse with low I t. DIMENSION AND FIXING HOLES SR6 W 36mm. - H...

Open the catalog to page 3
REVO S-1PH from 30A to 40A - 4

OUTPUT FEATURES (POWER DEVICE) Nominal current in continuos service: 30A, 35A, 40A 400A for unit type 030 600A for unit type 035 800A for unit type 040 Max peak current (10ms) Voltage range: Repetitive peak reverse voltage: Latching current: Leakage current: 15mA eff 780A2/S for unit type 030 1750A2/S for unit type 035 3110A2/S for unit type 040 I2t value tp=10msec: Frequency range: 47÷70Hz 38W for unit type 030 44W for unit type 035 50W for unit type 040 Power loss (I=Inom): Isolation Voltage: ORDERING CODES Numeric code Description code No Aux. Voltage, without HB and/or without Analog...

Open the catalog to page 4