Overview: The QF19 Series Miniature Circuit Breakers are hydraulic-magnetic circuit breakers designed for low voltage applications. They are 100% rated and unaffected by ambient temperature, making them suitable for various environments.
Specifications: The circuit breakers are available in one, two, three, 1+N, and 3+N pole configurations. They operate at voltages of 240 Vac and 415 Vac, with current ratings ranging from 1 A to 63 A. The interrupting capacity is 5 kA or 6 kA depending on the model.
Approvals and Standards: The breakers comply with VC 8036 (SANS 556-1), IEC/EN 60947-2, VDE, EAC, CCC, and are CE certified. They are also UL 1077 recognized as supplementary protectors.
Features: Key features include precision tripping characteristics, trip indication with mid-trip position, and the ability to be switched immediately after tripping. Optional accessories include auxiliary switches and trip alarms.
Applications: These circuit breakers are suitable for AC branch circuit protection, telecom/datacom equipment, lighting control, UPS equipment, alternative energy equipment, mobile power generation, railway signaling, residential, and industrial equipment.
Technical Data: The breakers operate in temperatures from -40°C to +85°C and have a dielectric strength of 1000-2000 Vac. They are designed to withstand shocks of 16 G and vibrations of 2 G. The flammability rating is I3, and the toxicity rating is F1.
Ordering Information: The document provides a detailed coding system for ordering, specifying frame type, switch/neutral options, auxiliary options, number of poles, module width, mounting options, time delays, current ratings, and shunt trip options.
Time Delay Curves: The document includes graphs showing the tripping time versus the percentage of rated current for different time delay curves, indicating the operational characteristics of the breakers.
Contact Information: The document lists contact details for CBI-electric offices in Australia, South Africa, and the USA.
See more

Catalog excerpts

QF(19) - Series Miniature Circuit Breakers-1

QF(19) - Series Miniature Circuit Breakers Dual mount 1 pole Dual mount 2 pole Dual mount 3 pole AC circuit breaker Hydraulic-magnetic technology 100% rating capability, independent of ambient temperature One, two, three pole, 1+N and 3+N VC 8036 compliant (SANS 556-1) VDE, EAC and CCC approved, CE certified UL 1077 recognised (Supplementary protector) Ratings 1 A to 63 A Optional shunt trip (IEC / EN 60947-2) Available in various currents and time delays Precision tripping characteristics Trip indication with mid-trip position Can be switched immediately after tripping Dual mount product in black shells Suitable to use for electrical isolation AC branch circuit protection (IEC / EN 60947-2) Supplementary protection (UL 1077) Telecom / datacom equipment Lighting control UPS equipment Alternative energy equipment Mobile power generation equipment Railway signalling equipment Residential equipment Industrial equipment Auxiliary Switch, Trip Alarm & Combo: Features Optional Accessories Factory fitted Attached to right hand side of the circuit breaker Compact 6.5 mm width Auxiliary switch (Dual mount) Auxiliary switch + trip alarm (Dual mount) Trip alarm (Dual mount) UL 489 listed & IEC 60947-5-1 110 Vdc, 0.5 A; 240 Vac, 6A Handle lock Surface mounting clips Busbar Hydraulic-Magnetic Circuit Breakers 100% rated, unaffected by ambient temperature QF

 Open the catalog to page 1
QF(19) - Series Miniature Circuit Breakers-2

QF(19) - Series Miniature Circuit BreakersTechnical Data Product Type

 Open the catalog to page 2
QF(19) - Series Miniature Circuit Breakers-3

QF(19) - Series Miniature Circuit BreakersTechnical Data Product Type * Refer to standard for details.

 Open the catalog to page 3
QF(19) - Series Miniature Circuit Breakers-4

QF(19) - Series Miniature Circuit Breakers Long Code For options not listed, please contact CBI

 Open the catalog to page 4
QF(19) - Series Miniature Circuit Breakers-5

QF(19) - Series Miniature Circuit Breakers Time Delay Curves 1500 Tripping Time (Seconds) % Rated Current Tripping Time (Seconds) % Rated Current Data Sheet Page 5 of 8

 Open the catalog to page 5
QF(19) - Series Miniature Circuit Breakers-6

QF(19) - Series Miniature Circuit Breakers Time Delay Curves 1500 Tripping Time (Seconds) % Rated Current * The published time delay curves are generated at 30oC ambient temperature with the circuit breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which is available on request. Data Sheet Page 6 of 8

 Open the catalog to page 6
QF(19) - Series Miniature Circuit Breakers-7

QF(19) - Series Miniature Circuit Breakers Internal Impedance vs Current Rating Q-Range impedance values Data Sheet Page 7 of 8

 Open the catalog to page 7
QF(19) - Series Miniature Circuit Breakers-8

QF(19) - Series Miniature Circuit BreakersOutline Dimensions: Dual Mount 61.0 — [2.402] TOLERANCE ±0.4 UNLESS OTHERWISE SPECIFIED (DIMENSION IN BRACKETS ARE IN INCH) Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.za All rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use. Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise,...

 Open the catalog to page 8
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.