1. Catalogs
  2. CBI-electric: low voltage
  3. QF(18) - Series Miniature Circuit Breakers

QF(18) - Series Miniature Circuit Breakers

QF(18) - Series Miniature Circuit Breakers

QF(18) - Series Miniature Circuit Breakers

Product catalog summary
Overview: The document is a technical data sheet for the QF18-Series Miniature Circuit Breakers, which are hydraulic-magnetic circuit breakers designed for low voltage applications. These breakers are 100% rated and unaffected by ambient temperature changes.
Specifications:
  • Approvals: VC 8036 (IEC / EN 60947-2), UL 1077, AS/NZS 3111, VDE, EAC, CCC, CE certified.
  • Poles: Available in 1, 2 (1+N), 3, 4 (3+N) configurations.
  • Operating Voltages: 240 Vac and 415 Vac.
  • Current Ratings: 1 A to 63 A.
  • Interrupting Capacity: 5 kA to 6 kA depending on the model.
  • Ambient Operating Temperature: -40 °C to +85 °C.
  • Mounting Options: DIN rail and surface mount.
Features:
  • Hydraulic-magnetic technology ensures precision tripping characteristics.
  • Trip indication with mid-trip position and immediate reset capability.
  • Optional shunt trip and auxiliary switch available.
  • Suitable for electrical isolation and a wide range of applications including telecom, lighting control, UPS, and more.
Technical Data:
  • Endurance: 10,000 operations (1,500 with current, 8,500 without current).
  • Dielectric Strength: 1000 - 2000 Vac for one minute.
  • Rated Impulse Withstand Voltage: 4 kV.
  • Weight: 120 g per pole, 180 g with auxiliary.
  • Shock and Vibration: 16 G and 2 G respectively.
  • Flammability and Toxicity: I3 and F1 ratings.
Ordering Information: The document provides a detailed coding system for ordering, specifying frame type, switch/neutral options, auxiliary options, number of poles, module width, mounting type, time delays, current ratings, and shunt trip options.
Time Delay Curves: The document includes graphs showing the tripping time versus percentage of rated current for different time delay curves (1, 2, and 9), indicating the operational characteristics of the breakers.
Contact Information: The document lists contact details for CBI-electric offices in Australia, South Africa, and the USA.
See more

Catalog excerpts

QF(18) - Series Miniature Circuit Breakers-1

QF(18) - Series Miniature Circuit Breakers AC circuit breaker Hydraulic-magnetic technology 100% rating capability, independent of ambient temperature One, two, three pole, 1+N and 3+N VC 8036 compliant (SANS 556-1) VDE, EAC and CCC approved, CE certified UL 1077 recognised (supplementary protector) Ratings 1 A to 63 A Optional shunt trip (IEC / EN 60947-2) Wide range of time delays & operating currents Precision tripping characteristics Trip indication with mid-trip position Can be switched on immediately after tripping DIN mount product in grey shells Suitable to use for electrical isolation AC branch circuit protection (IEC / EN 60947-2) Supplementary protection (UL 1077) Telecom / datacom equipment Lighting control UPS equipment Alternative energy equipment Mobile power generation equipment Railway signalling equipment Residential equipment Industrial equipment Auxiliary Switch: Features Optional Accessories Factory fitted Attached to right hand side of the circuit breaker Compact 6.5 mm width UL 489 listed & IEC 60947-5-1 110 Vdc, 0.5 A; 240 Vac, 6A Handle lock Surface mounting clips Busbar Hydraulic-Magnetic Circuit Breakers 100% rated, unaffected by ambient temperature QF18-SE

 Open the catalog to page 1
QF(18) - Series Miniature Circuit Breakers-2

QF(18) - Series Miniature Circuit BreakersTechnical Data Product Type Auxiliary Module

 Open the catalog to page 2
QF(18) - Series Miniature Circuit Breakers-3

QF(18) - Series Miniature Circuit BreakersTechnical Data Product Type * Refer to standard for details.

 Open the catalog to page 3
QF(18) - Series Miniature Circuit Breakers-4

QF(18) - Series Miniature Circuit Breakers Long Code Switch / neutral Auxiliary switch Triple pole Medium delay curve 2 Shunt trip Long Code Ordering Information For options not listed, please contact CBI

 Open the catalog to page 4
QF(18) - Series Miniature Circuit Breakers-5

QF(18) - Series Miniature Circuit Breakers Time Delay Curves Tripping Time (Seconds) % Rated Current Data Sheet Page 5 of 8

 Open the catalog to page 5
QF(18) - Series Miniature Circuit Breakers-6

QF(18) - Series Miniature Circuit Breakers Time Delay Curves Tripping Time (Seconds) % Rated Current Data Sheet Page 6 of 8

 Open the catalog to page 6
QF(18) - Series Miniature Circuit Breakers-7

QF(18) - Series Miniature Circuit Breakers Time Delay Curves 1500 Tripping Time (Seconds) % Rated Current * The published time delay curves are generated at 25oC ambient temperature with the circuit breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which is available on request. Internal Impedance vs Current Rating Q-Range impedance values Data Sheet

 Open the catalog to page 7
QF(18) - Series Miniature Circuit Breakers-8

QF(18) - Series Miniature Circuit BreakersOutline Dimensions: DIN Mount TOLERANCES ±0.4 UNLESS OTHERWISE STATED (DIMENSIONS IN BRAKETS ARE IN INCHES) Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.za All rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use. Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise, for reasons...

 Open the catalog to page 8