FIRECEL SR 114H

FIRECEL SR 114H

Product catalog summary
Specifications:
The document provides detailed specifications for various types of FIRECEL SR 114H cables, including solid and stranded conductors with cross-sections ranging from 1 mm² to 4 mm². Key parameters include the number of conductors, cross-sectional area, outer diameter, and weight per kilometer. Notably, some configurations are not included in BS 7629-1:2015 and LPCB/BASEC approval.

Cable Construction:
Conductors are made of plain annealed copper wire, either solid class 1 or stranded class 2, compliant with EN 60228. The insulation is high-performance fire-resistant silicone rubber type EI2, according to BS EN 50363-1. Cables feature an aluminium/polyester tape overall screen and an uninsulated tinned copper conductor as a circuit protective conductor or drain wire. The outer sheath is made of LSZH thermoplastic material type LTS3, compliant with BS 7655-6.1, available in red or white.

Fire Resistance and Standards:
FIRECEL SR 114H cables are designed to be fire-resistant, meeting standards such as BS 5839-1:2017, BS EN 50200:2015, and BS 6387:2013. They are tested for fire and mechanical shocks at temperatures up to 950°C. The cables also comply with standards for flame retardancy, acid gas emission, and smoke density.

Applications:
These cables are intended for general applications, particularly in fire detection and alarm systems, voice alarm systems, emergency lighting, and fire-resistant control cable systems for life safety and fire-fighting applications.

Operating Conditions:
The cables operate within a temperature range of -40°C to +90°C and have a minimum bending radius of six times the outer diameter.

Approvals:
The document references LPCB and BASEC approvals, directing users to specific websites for detailed scope information.
See more

Catalog excerpts

FIRECEL SR 114H-1

Fire Resistant Cables Standard Cable 300/500 V BS 5839-1:2017 Clause 26.2d Silicone Insulation / Overall Screen Solid & Stranded conductor BS EN 50200:2015 (PH 30 - PH 60 - PH 120) 830°C fire and mechanical shocks BS EN 50200:2015 + Annex E 830°C - 30 min. (15 min. fire and mechanical shocks + 15 min. fire mechanical shocks and water spray) BS 6387:2013 Cat. C fire @ 950°C - 180 min Cat. W fire 15 min. + fire and water spray 15 min. Cat. Z fire and mechanical shocks @ 950°C - 15 min.fire APPLICATIONS FIRECEL SR 114H are primarily intended for general application. Typical applications are: LPCB ref. 217f (cables up to 4 cores) For the scope of the LPCB Approval see www.redbooklive.com BS 5839-1 for standard fire resistant cables in fire detection and fire alarm systems for building MINIMUM BENDING RADIUS 6 times the outer diameter. BS 5839-8 for voice alarm systems BS 5839-9 for emergency voice communication systems. BS 5266-1 for emergency lighting of premises (PH60) For the scope of the BASEC Approval see www.basec.org.uk CABLE CONSTRUCTION Conductors Plain annealed copper wire, solid class 1 or stranded class 2 according to EN 60228. High performance fire resistant silicone rubber type EI2 to BS EN 50363-1. Insulated cores are cabled together. Overall screen Aluminium/polyester tape. Circuit protective conductor or drain wire Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the 2-, 3- and 4-core cables. Drain wire of 0.5 mm2 tinned copper conductor is provided in cables with more than 4 conductors. Outer sheath LSZH thermoplastic material type LTS3 to BS 7655-6.1. Colour red or white (other colours on request). BS 8519 for fire-resistant control cable systems for life safety and fire-fighting application - Category 1 COLOUR CODE UP TO 4 CORES TO HD 308 2 cores: 3 cores: 4 cores: 7 cores: centre 1st layer 12 cores: centre 1st layer 19 cores: centre 1st layer 2nd layer N° of cond. x cross section (mm2) - 4 cores - 7 cores - 4 cores - 10 cores (on request the cores can be one colour only, identified by printed numbers) APPLICABLE STANDARDS Basic design BS 7629-1 Fire resistant BS 6387 (cat. C-W-Z) BS EN 50200 (PH30 - PH60 - PH120) BS EN 50200 annex E (fire, mechanical shock and water spray) IEC 60331 Flame retardant BS EN 60332-1-2 Fire retardant BS EN 60332-3-24 (cat. C) Acid gas emission BS EN 60754-1 Smoke density BS EN 61034-2 Weight (kg/km) not included in BS 7629-1:2015 and in LPCB/BASEC approva