FIRECEL SR 114 - 109/15
10Pages

{{requestButtons}}

Catalog excerpts

FIRECEL SR 114 - 109/15 - 1

Conducting Value UKAS PRODUCT CERTIFICATION 109/15 PRODUCT MARKING LICENCE NO: 211/001

Open the catalog to page 1
FIRECEL SR 114 - 109/15 - 2

Atlantis The Palm, Dubai FIRECEL cables are installed all over the world. New projects are coming. Cavicel has been committed since 1970 to the study, design and manufacture of highly reliable fire resistant cables. Designed and manufactured in Italy. Cleveland Clinic, Abu Dhabi Approvals • Civil Defence - Abu Dhabi • Civil Defence - Dubai • Civil Defence - Bahrain • Civil Defence - Qatar • Saso - Saudi Arabia • Royal Oman Police - Sultanate OfOman • Fire Service Directorate - Kuwait • Fire Service Dept. (Fire Protection Bureau) - Hong Kong Opera House, Dubai Mochovce Nuclear Power Plant,...

Open the catalog to page 2
FIRECEL SR 114 - 109/15 - 3

EknSsd] Conducting Value STANDARDS According to BS 5839-1:2017 “Fire detection and fire alarm systems for buildings - Parti: Code of practice for system design, installation, commissioning and maintenance", two different levels of cable fire resistance are specified. For most application "standard" fire resistant cables can be used. However, for other applications, such as unsprinklered premises or buildings, in which the designer or specifier require an improved fire resistance, "enhanced" cables must be used. Enhanced cables meet the most severe fire tests as they survive fire at the...

Open the catalog to page 3
FIRECEL SR 114 - 109/15 - 4

FIRECEL SR 114H Standard Cable 300/500 V nvR-iJ] Conducting Value Silicone Insulation / Overall Screen Solid & Stranded conductor Applicable Standards BS 5839-1:2017 Clause 26.2d BS EN 50200:2015 (PH 30 - PH 60 - PH 120) 830°C fire and mechanical shocks BS EN 50200:2015 + Annex E 830°C - 30 min. (15 min. fire and mechanical shocks + 15 min. fire mechanical shocks and water spray) BS 6387:2013 Cat. C fire @ 950°C - 180 min Cat. W fire and water @ 650°C - 15 + 15 min. Cat. Z fire and mechanical shocks @ 950°C - 15 min.fire APPLICATIONS OPERATING TEMPERATURE (cables up to 4 cores) For the...

Open the catalog to page 4
FIRECEL SR 114 - 109/15 - 5

FIRECEL SR 114E Enhanced Cable 300/500V Conducting Value Mica/Silicone Insulation / Overall Screen Applicable Standards BS 5839-1:2017 Clause 26.2e BS EN 50200:2015 (PH 120) 830°C fire and mechanical shocks BS 8434-2:2003 +A2:2009 930°C - 120 min. (60 min. fire and mechanical shocks + 60 min. fire mechanical shocks and water spray) BS 6387:2013 Cat. C fire @ 950°C - 180 min Cat. W fire and water @ 650°C - 15 + 15 min. Cat. Z fire and mechanical shocks @ 950°C - 15 min.fire APPLICATIONS OPERATING TEMPERATURE For the scope of the BASEC Approval see www.basec.org.uk FIRECEL SR 114E are...

Open the catalog to page 5
FIRECEL SR 114 - 109/15 - 6

FIRE TESTS Conducting Value FIRECEL CABLES ARE TESTED AND CERTIFIED BY THIRD-PARTY INSPECTION COMPANIES: LPCB-BRE AND BASEC. ANYWAY IN CAVICEL ALL TESTS RELATED TO FIRE ARE INHOUSE PERFORMED ON A REGULAR BASE, TO GET A VERY HIGH TRUST TO ASSURE CUSTOMERS THE COMPLETE SAFETY. Flame and mechanical shock BS 50200 Ongoing fire test Flame retardant test on bunched cables IEC 60332-3 Smoke density test BS EN 61034-2 Flame retardant test on single wire IEC 60332-1, BS 4066 pt. 1 Flame, mechanical shock and water spray BS 8434-2

Open the catalog to page 6
FIRECEL SR 114 - 109/15 - 7

Following tests are carried out to verify if a cable is capable of maintaining circuit integrity under fire condition, fire with water, and fire with mechanical shocks. During the tests the cables are maintained at their rated voltage. 6 Total duration of test: 30' 0; si This test is carried out to verify circuit integrity during a fire. The cable is exposed to a flame at 830°C and mechanical shocks for 15 minutes and additional 15 minutes to flame, mechanical shocks and water spray. During the tests the cables are maintained at their rated voltage. Total duration of test: 30'

Open the catalog to page 7
FIRECEL SR 114 - 109/15 - 8

Conducting Value 830 °C 83 83 83 This test is carried out to verify circuit integrity during a fire. The cable is exposed to a flame at 930°C and mechanical shocks for 60 minutes and additional 60 minutes to flame, mechanical shocks and water spray. During the tests the cables are maintained at their rated voltage. 1 A + + eo'A + Total duration of test: 120'

Open the catalog to page 8
FIRECEL SR 114 - 109/15 - 9

Voltage rating Current Ratings and Voltage Drop1 1 Conductor operating temperature: 90 °C; Ambient temperature: 30 °C. Electrical Characteristics Cable Installation Ambient Temperature FIRECEL cables are easy to install also at temperature as low as -10 °C. Storage temperature: -40 °C to +80 °C. Minimum 6 times the nominal diameter of the cable. Cable is easy to handle and easy to install without special tools. Cable can be fixed directly to a surface using LSZH coated copper P clips or Saddle clips, available together with cables. Plastic clips must not be used. Cable can also be installed...

Open the catalog to page 9
FIRECEL SR 114 - 109/15 - 10

Conducting Value CAVICEL SpA Via Caduti del Lavoro, 18/A 20096 Pioltello (Milano) Italy ph. +39 - 02 - 921.605.21 fax +39 - 02 - 921.607 .53 e-mail: cavicel@cavicel.com DUBAI BRANCH OFFICE Fortune Executive Tower Office 406 - Plot No. T1 Jumeirah Lakes Towers Dubai - UAE - PO Box 634377 ph. +971 4.4581199 fax +971 4.4581144 e-mail: middleeast@cavicel.com HONG KONG OFFICE 2/F AXA Southside Building , 38 Wong Chuk Hang Road Hong Kong Ph: +852 3963 9365 e-mail:apac@cavicel.com CORPORATE VIDEO Cavicel firmly believes in the importance of the quality of its products and it undertakes itself to...

Open the catalog to page 10