ATC Service Entrance Rated MCCB & Power Breaker Based ATS
6Pages

{{requestButtons}}

Catalog excerpts

ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 1

AUTOMATIC TRANSFER SWITCH • CAT® •ATC SERVICE • ENTRANCE RATED MCCB & • POWER BREAKER BASED • AUTOMATIC TRANSFER • • SWITCHES • Cat® Service Entrance Rated (SER) automatic transfer • switches (ATS) are designed to provide standby power • emergency power to entire installation loads to protect • against utility power interruption; yet allow the ATS to be • as close as possible to the point of service entrance. By safely and • code compliance, integrating the necessary in overcurrent protection and service disconnecting means into the automatic transfer switch, a single installation can be made at the service entrance. This design eliminates the need for a separate upstream fault protection and respective interconnections, which in turn reduces installation space, time, and cost. Breaker-based Service Entrance Rated transfer switches are available from 30A to 5000A. ATC-100 on Residential & Light Commercial MCCB based, ATC-300+ or ATC-800 on MCCB & Power Breaker ATS products UL 1008 service entrance listed (up to 3200A) Service disconnect (both off) capability Integral over current protection Lockout when in disconnected position (only) Service entrance labeled Integrated Design Disconnecting neutral assembly Ground fault protection capability (all ratings) (Required by code on rating 480V, and 1000A or higher) Keyed service entrance switch Draw-out type breakers (available on Power Breaker ratings) UL 891 for 4000-5000A Loads protected against extended power loss Quick restoration of the circuit after a trip (versus a fused circuit that requires fuse availability) Trip on a fault prohibits transfer to the emergency source Fused circuit allows switch testing by simulating an actual power failure. Locka

Open the catalog to page 1
ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 2

OPTIONS • Open, closed or delayed transition • Integral overcurrent protection • 4-position test switch • Multi-meter options available • Selectable Automatic or Non-Automatic operation • Space heaters • Load sequencing contacts • Surge suppression • Remote communications • Seismic Zone 4 Qualified (BOCA, CBC, IBC, UBC and OSHPD) • Field selectable, multi ratio, control voltage transformer 50/60 Hz • Communications for the ATC-300+ controller via RS-232 or Modbus through an integrated RS-485 port OPTIONAL DELAYED TRANSITION INCLUDES: • Time Delay Neutral • Pre-Transfer Signal with 1 N.O....

Open the catalog to page 2
ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 3

AUTOMATIC TRANSFER SWITCHTESTING STANDARDS UL 991 UL standards for safety tests for safety-related controls employing solid-state devices UL 1008 Dielectric test (endurance, w ithstand, etc.) IEEE® 472 (ANSI C37.90A) Ringing w ave immunity/voltage surge test EN55022 (CISPR11): Conducted and radiated emissions EN61000-4-2 Class B Level 4 ESD immunity test EN61000-4-3 (ENV50140) radiated RF, electromagnetic field immunity test EN61000-4-4 Electrical fast transient/burst immunity test EN61000-4-5 IEEE C62.41: Surge immunity test EN61000-4-6 (ENV50141) Conducted immunity test EN61000-4-11...

Open the catalog to page 3
ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 4

WITHSTAND AND CLOSE RATINGS FOR POWER BREAKER TYPE TRANSFER SWITCHES UP TO 600V When Protected by Any Breaker T est Voltage When Coordinated with Upstream Breaker with a Short When Protected by Fuses Test Voltage Maximum Fuse Type Fuse Amperes

Open the catalog to page 4
ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 5

SERVICE ENTRANCE RATED POWER BREAKER DIMENSIONS AND WEIGHTS 200-4000A Rating Ampere 200-2000 200-2000 2500-3200 2500-3200 200-2000 200-2000 2500-3200 2500-3200 200-2000 200-2000 2500-3200 2500-3200 SER Switch Type Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Breaker Fixed Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power Brea Power...

Open the catalog to page 5
ATC Service Entrance Rated MCCB & Power Breaker Based ATS - 6

MCCB DIMENSIONS AND WEIGHTS FOR SERVICE ENTRANCE RATED SWITCHES Rating Breaker Switch Height Width Depth Weight Ampere Type Poles Type Inches (mm) Inches (mm) Inches (mm) Lbs (kg) Distribution Panels (240/120V Single Phase, ATC-300 only) Nema 1, 3R & 12 Automatic Transfer Switches (AG: 240/120 Single Phase, 280/120, ATC-100 & ATC-300) Nema 1, 3R & 12 Service Service Service Service Service Service Service Service Service Service Service Entrance Entrance Entrance Entrance Entrance Entrance Entrance Entrance Entrance Entrance Entrance Automatic Switches & Non-Automatic Transfer...

Open the catalog to page 6

All CAT catalogs and technical brochures

  1. Cat® C1C2

    6 Pages

  2. C1.1

    5 Pages

  3. RP3600

    2 Pages

  4. RP6500 E

    2 Pages

  5. RP5500

    2 Pages

Archived catalogs