ATC-300+ Controller - 1

AUTOMATICTRANSFER SWITCH ATC-300+ CONTROLLER The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the cond ition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions. FEATURES • Auxiliary relay contacts: • Source 1 present 2NO and 2NC • Source 2 present 2NO and 2NC • Source 1 and source 2 sensing: • Undervoltage / underfrequency • Overvoltage / overfrequency • Three-phase rotation protection • Three-phase voltage unbalance/loss • Pre-transfer signal contacts 1NO and 1NC • Go to emergency (Source 2) • Seven field-programmable time delays • LCD-based display for programming, system diagnostic and help message display • Mimic diagram with source available and connected LED indication • Time-stamped history log • System test pushbutton • Programmable plant exercise (off, daily, 7,14 and 28 day) interval selectable run time 0-600 minutes no load/load with fail-safe • Integral overcurrent protection (optional) • In-phase transition • Stainless steel cover for controller (optional) • Communications via RS-232 or Modbus through an integrated RS-485 port (optional)

Open the catalog to page 1
ATC-300+ Controller - 2

ATC-300+ CONTROLLER SPECIFICATIONS Input control voltage 65 to 145 Vac 50/60 Hz Voltage measurements of Source 1 VAB Source 2 VAb Voltage measurement range 0 to 790 Vac rms (50/60 Hz) Voltage measurement accuracy ±2% of nominal inputvoltage Frequency measurement for Source 1 and Source 2 F requency measurement range 40 Hz to 70 Hz Frequency measurement accuracy ±0.1 Hz Undervoltage dropout range 50% to 90% of nominal voltage Undervoltage pickup range (Dropout +2%) to 99% of the nominal system voltage Overvoltage dropout range 105% to 120% of nominal voltage...

Open the catalog to page 2
ATC-300+ Controller - 3

ATC-300+ CONTROLLER SETPOINTS Setpoint Units Description New password Four digits Set new password TDES Minutes: seconds Time delay engine start TDNE Minutes: seconds Time delay normal to emergency TDEN Minutes: seconds Time delay emergency to normal TDEC Minutes: seconds Time delay engine cool off NOM FREQ Hertz Nominal frequency NOM VOLTS Volts Nominal voltage S1 UV DROP Volts Source 1 undervoltage dropout range S2 UV DROP Volts Source 2 undervoltage dropout range S1 UV PICK Volts Source 1 undervoltage pickup range S2...

Open the catalog to page 3
ATC-300+ Controller - 4

CHANGE TIME/DATE? Hours Minutes Weekday Month Day Year Description Set time and date Set hour Set minute Set weekday Set month Set day Set year Range 0 to 23 0 to 59 Sun, Mon, Tues, Wed, Thu, Fri or Sat Jan or 01 Current Year Factory Default Eastern Standard Time Eastern Standard Time Eastern Standard Time Eastern Standard Time Eastern Standard Time Eastern Standard Time RESET SYSTEM COUNTERS? RESET ALL? RESET ENGINE RUN? Hours RESET S1 CONN Hours RESET S2 CONN Hours RESET S1 AVAIL Hours RESET S2 AVAIL Hours RESET LOAD ENERG Hours RESET TRANSFERS Hours SAVE SETPOINTS...