1. Catalogs
  2. CAT Electric Power
  3. XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)

XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)

XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)

XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)

Product catalog summary
Specifications:
The Cat® XQP150 Rental Generator Set is a switchable 50/60 Hz generator with a prime power rating of 120 kW (150 kVA). It features a Cat® C7.1 diesel engine with low fuel consumption, turbocharged-aftercooled aspiration, and a compression ratio of 18.2:1. The generator operates at engine speeds of 1500-1800 rpm and offers various voltage configurations for both 50 Hz and 60 Hz frequencies.
Benefits & Features:
The generator is designed for low environmental impact with a dual-wall base tank for spill containment and low fuel consumption. It includes a Cat EMCP 4.2B control panel for comprehensive power metering and control, and a Cat LC3100 generator designed to match the engine's performance. The enclosure is made of galvanized sheet steel with a sound-attenuating design and lockable access doors.
Standard Equipment:
Standard features include a two-stage air cleaner, a 12V charging alternator, a package-mounted radiator, and a robust distribution system with a main circuit breaker. The generator set is soft-mounted on a heavy-duty steel base frame with forklift pockets and a drag bar for easy transport.
Technical Data:
The generator set has a fuel tank capacity of 590 liters, providing a 24-hour runtime at 75% load. It has a noise rating of 93 dB(A) at 1 meter and 78 dB(A) at 7 meters at full load. The generator frame size is LC3114J with a 2/3 pitch and a single bearing design. It offers less than ±0.5% voltage regulation and less than 2% harmonic distortion.
Compliance and Ratings:
The generator set is designed to meet ISO 8528, EN 12601, EN 60204-1, ISO 3046, and IEC 60034 standards. It is rated for continuous power supply with no limitation on annual operation hours and can supply 10% overload power.
See more

Catalog excerpts

XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-1

Prime 120 kW, 150 kVA 50/60 Hz Switchable Low Fuel Consumption

 Open the catalog to page 1
XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-2

Benefits & Features Fuel/Emissions Strategy • Cat® C7.1 high performance diesel engine • Low Fuel Consumption Single-source Supplier • Factory designed and fully prototype tested with certified torsional vibration analysis available • ISO 9001:2000 compliant facility Cat C7.1 Diesel Engine • Four-stroke diesel engine combines consistent performance and excellent fuel economy with minimum weight • Electronic governed engine Cat EMCP 4.2B Control Panel • Fully featured power metering, protective relaying, and engine/generator control and monitoring • Simple user-friendly interface and navigation •...

 Open the catalog to page 2
XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-3

Standard Equipment Air Inlet • Air cleaner, two stage cyclonic/paper with dust cup and service indicator • Turbocharger and air-to-air aftercooler Alternator • LC3114J frame — 3-phase, random wound, 12 lead design, self excited, 2/3 pitch • Coastal Insulation protection Charging System • Charging alternator — 12V, heavy duty with integral regulator and belt guards Control Panel • EMCP 4.2B generator set mounted digital controller • 50/60 Hz frequency switch via terminal link • Panel mounted emergency stop switch • IVR with EM10 excitation module • Automatic set-point adjustment integrated with voltage...

 Open the catalog to page 3
XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-4

Standard Equipment (continued) Generator • LC3114J frame, three-phase, random wound, 12-lead design, self-excited, 2/3 pitch • Coastal insulation protection • 120 or 230 VAC anti-condensation heater available Lube System • On-engine primary and secondary oil filters, filler, and dipstick • Open crankcase breather with a fumes disposal container, drain located on side of base frame • Oil drain piped to edge of base frame with internally mounted ball valve. • 500-hour oil change intervals Mounting System • Generator set soft-mounted using captive vibration mounts • Heavy-duty steel base frame contains...

 Open the catalog to page 4
XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-5

Cat® XQP150 Rental Generator Set CAT Technical Data Cat Generator ‘Guaranteed sound power as per 2000/14/EC

 Open the catalog to page 5
XQP150 Rental Generator Set Spec sheet (Low Fuel Consumption)-6

Cat® XQP150 Rental Generator Set CAT Technical Data (continued) Dimensions Rating Definitions and Conditions Designed to Meet Specifications: ISO 8528, EN 12601, EN 60204-1, ISO 3046, IEC 60034. Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions. Prime — Applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation on the annual hours of operation and the generator can supply 10% overload power. Fuel rates are based on fuel oil of 35° API [16°C (60°F)] gravity having...