The ATC-100 is a microprocessor-based ATS controller designed to replace traditional relay and solid-state logic panels. It supports both fixed and jumper-selectable settings, operating across system voltages from 120 to 480 Vac, single-phase and three-phase at 50 or 60 Hz. It monitors three-phase line-to-line voltage and frequency for both utility and generator power sources, with options for single-phase operation.
Key FunctionsSpecifications are subject to change without notice. The ATC-100 controller is a UL-recognized component, compliant with various environmental and electrical standards, including UL 1008, UL 991, and IEC 61000 series.
ATC-100 Controller SpecificationsThe ATC-100 is compatible with NEMA 1, NEMA 3R, and NEMA 12 enclosures and features a UV-resistant faceplate. It meets FCC Part 15, Class B, and CSA 22.2-178 standards.
AUTOMATICTRANSFER SWITCH GfiT AUTOMATICTRANSFER SWITCH GfiT ATC-100 CONTROLLER The ATC-100 is a comprehensive and multifunctional micropro cessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC provides both fixed and jumper-selectable settings to allow for a range of applications. It operates from all system voltages between 120 and 480 Vac, single-phase and three phase at 50 or 60 Hz. The ATC-100 monitors the condition of the three-phase line to lin e voltage and the frequency of both the utility and generator power sources. It can also be set up for single-phase operation. The ATC-100 provides the necessary intelligence to ensure that the transfer switch operates properly through a series of selectable sensing and timing functions FEATURES • Source 1 sensing: • Undervoltage / underfrequency • Overfrequency • Source 2 sensing: • Undervoltage / overfrequency • Controller settings via jumpers located at the rear of the unit • Mimic diagram with source available and connected LED indication • System test pushbutton • Plant Exerciser - Selectable day, off, 7, 14 or 28 day intervals with fixed 15 minute run time • Monitor utility and generator power source voltages and generator power source frequency • Provides undervoltage protection of the utility and generator power sources • Provides underfrequency and overfrequency protection of the generator power source • Permits easy customer setup • Permits system testing • In-phase transition
Open the catalog to page 1PRODUCT SPECIFICATIONS ATC-100 CONTROLLER SPECIFICATIONS DescriptionSpecification Input control voltage95 to 145 Vac 50/60 Hz Voltage measurements of Utility Vab generator Vab Utility VBC generator VBC Utility VCA generator VCA Voltage measurement range0 to 575 Vac rms (50/60 Hz) Voltage measurement accuracy ± 1% of full scale Frequency measurements ofGenerator Frequency measurement range 40 Hz to 70 Hz Frequency measurement accuracy ±0.3 Hz over the measurement range Undervoltage dropout80% of the niminal system voltage Undervoltage pickup90% of the niminal system voltage Underfrequency dropout...
Open the catalog to page 23 Pages
6 Pages
5 Pages
8 Pages
5 Pages
4 Pages
2 Pages
2 Pages
20 Pages
12 Pages
2 Pages
2 Pages
2 Pages
1 Page
1 Page
2 Pages
20 Pages
15 Pages
6 Pages
4 Pages