Water cooled condensers with liquid receiver

Product catalog summary
Functional Features and Applications
Water cooled condensers with liquid receivers, such as the CONDOR-V (vertical), are designed for cooling, condensation, and refrigerant storage in refrigeration and air conditioning systems. They accommodate refrigerant volume variations due to expansion valve operations. The heat exchange is facilitated by high-performance finned copper tubing coils. These products are compatible with various refrigerants including HFCs, HCFCs, and CFCs, and are designed for non-hazardous refrigerants from group 2 of PED 97/23/EC.

Specifications
The condensers are constructed with a steel shell and copper heat exchanger, equipped with fastening means suitable for their volume and weight. The CONDOR-V 2500 model includes a 3/8” NPT boss for safety elements. They offer connection options for refrigerants and are supplied clean and dried. The products are GOST certified and feature low water consumption and high-performance heat exchangers.

Selection and Recommendations
Installation should occur after the compressor discharge, respecting refrigerant and water flow directions. Receivers should be 20% larger than the total refrigerant load to maintain a gas reserve above the liquid level. Water circulation must be ensured before handling the refrigerating circuit to prevent icing. Sea water usage is prohibited, and water circuits should be kept clean with suitable filters.

Technical Features
The document provides a detailed selection table for various CONDOR-V models, specifying condensation capacity, water flow, storage volume, and water pressure drop. It includes correction factors for different refrigerants and water types to adjust condensation capacity. The technical features section also outlines the maximal working pressures and temperatures for each model.

Example of Selection
An example is provided for selecting a CONDOR water cooled condenser with a liquid receiver, operating with R404A under specific conditions. The selection process involves correcting the condensation capacity based on fouling and refrigerant factors, and matching the capacity to the quick selection table.

Spares Parts and Options
The document lists spare parts and options available for the CONDOR-V models, including gaskets, Rotalock connections, and support feet, with specific part numbers and descriptions.
See more

Catalog excerpts

Water cooled condensers with liquid receiver-1

34.1 n Functional features n CARLY advantages Water cooled condensers with liquid receiver CONDOR-V(vertical) n Applications • Water cooled condensers with liquid receiver ensure cooling, condensation and storage of refrigerant in refrigerating and air conditioning installations. • They also allow storage of the refrigerant, in order to compensate volume variations due to the opening and closing sequences of the expansion valve. • Heat exchange is carried out by a water circulation inside a very high performance finned copper tubing coil. C o Products are compatible with HFCs, HCFCs, CFCs, as well as with their associated oils and additives. Products are designed for use of non-hazardous refrigerants from group 2 of PED 97/23/EC. o Product classification in CE categories is performed using the PED 97/23/EC table, corresponding to a volume-based selection. oWater cooled condensers with liquid receiver are made of steel for the shell and copper for the heat exchanger. o They are fitted with fastening means suited to their volume and to their weight (see page 34.10). o The CONDOR-V 2500 model comes with a 3/8” NPT boss for mounting of safety elements such as safety valves. o Water cooled condensers with receiver are supplied perfectly clean and dried. o They offer both following connection possibilities for the refrigerant: Outside of the connections to screw. Inside of the connections to braze. o Very high performance heat exchangers. o Low water consumptions. o A wide range of accessories is available: Rotalock stop valves, with connections to screw or to braze. Rotalock connections with possibility of diameter reductions and with connections to screw or to braze. o Reduction of the quantity of the refrigerant in the circuit compared to installations with air cooled condensers. o GOST certified products. At the heart of refrigeration technology 03/08 Non-binding documents

 Open the catalog to page 1
Water cooled condensers with liquid receiver-2

34.2 n Selection table * Water cooled condensers with liquid receiver are to be installed after the compressor discharge. * For optimal operation, refrigerant and water flow directions should be respected (“IN” tag at the inlet). * If sizing of the receivers is performed on the basis of the total refrigerant load, it is imperative to select receivers with an internal volume 20 % bigger, so that the gas reserve is always above the liquid level. * It is essential to ensure a water circulation before any handling on the refrigerating circuit (risk of icing). * Take care to keep the water circuit...

 Open the catalog to page 2
Water cooled condensers with liquid receiver-4

34.4 Non-binding documents At the heart of refrigeration technology Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 (1) Classification by volume, according to PED 97/23/EC (refer to chapter 0.7). The sizing of a product implies for the buyer to take into account the conditions under which the product will be used (temperature - pressure refrigerant oil external environment). The values of the selection tables proposed in the CARLY catalogue match accurate test conditions. 1°: Make corrections according to the water and the refrigerant: - 1-1 Correction...

 Open the catalog to page 4
Water cooled condensers with liquid receiver-5

At the heart of refrigeration technology 34.5 Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 Non-binding documents * According to the type of refrigerant used, the condensation capacity (Qk x ) of the installation should be corrected in accordance to the following Fr factor by the formula: Qk = Qk x x Fr Quick Selection Table * According to the type of water available, the condensation capacity (Qk x ) of the installation should be corrected in accordance to the fouling factor by the formula: Qk = Qk x x Fe Fouling factor (m2.K / W) Correction factor...

 Open the catalog to page 5
Water cooled condensers with liquid receiver-6

34.6 At the heart of refrigeration technology Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 Non-binding documents Capacity (kW) Water pressure drop (bar) Capacity (kW) Water flow (l/h) Water pressure drop (bar) Water flow (l/h) Ät water = 5K Ät water = 3K Ät water = 1K Ät 1 = 25K Ät 1 = 20K Ät 1 = 15K Ät 1 = 10K Ät 1 = 5K Äp water Ät 1 = 5K Ät water = 1K Ät 1 = 10K Ät 1 = 15K Äp water Ät 1 = 20K Ät 1 = 25K Ät water = 10K Ät water = 5K Ät water = 3K

 Open the catalog to page 6
Water cooled condensers with liquid receiver-7

Ät water = 1K Ät water = 3K Äp water Ät water = 15K Ät water = 10K Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 Non-binding documents Water pressure drop (bar) Capacity (kW) Capacity (kW) Water pressure drop (bar) Water flow (l/h) Water flow (l/h) At the heart of refrigeration technology 34.7 Äp water Ät water = 5K Ät1 = 5K Ät1 = 10K Ät1 = 15K Ät1 = 20K Ät1 = 25K Ät1 = 10K Ät1 = 5K Ät1 = 15K Ät1 = 20K Ät water = 15K Ät1 = 25K Ät water = 10K Ät water = 5K

 Open the catalog to page 7
Water cooled condensers with liquid receiver-8

Non-binding documents 34.8 At the heart of refrigeration technology Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 Water flow (l/h) Water flow (l/h) Water pressure drop (bar) Water pressure drop (bar) Capacity (kW) Capacity (kW) Ät water = 5K Ät water = 10K Ät water = 15K Ät water = 20K Äp water Ät1 = 10K Ät1 = 15K Ät1 = 20K Ät1 = 25K Ät water = 5K Ät water = 10K Ät water = 15K Ät water = 20K Ät1 = 5K Ät1 = 10K Ät1 = 15K Ät1 = 20K Ät1 = 25K Äp water

 Open the catalog to page 8
Water cooled condensers with liquid receiver-9

Water cooled condensers with liquid receiver CONDOR-V(vertical) n Technical features C 03/08 La technique au coeur du froid Non-binding documents 34.9 At the heart of refrigeration technology Water pressure drop (bar) Capacity (kW) Water flow (l/h) Ät water = 5K Ät water = 10K Ät water = 20K Ät water = 15K Ät1 = 5K Ät1 = 10K Ät1 = 15K Ät1 = 20K Ät1 = 25K Äp water

 Open the catalog to page 9
Water cooled condensers with liquid receiver-10

Water cooled condensers with liquid receiver CONDOR-V(vertical) n Spares parts and options C 03/08 34.10 At the heartLL oaaf ttreeeccfrhhignneiiqqrauuteeio aan uut ecccoeoeoehnuuorrl oddguuy ffrrooiidd (1) (E) Inlet, (S) outlet CARLY references Description CONDOR Types (1) Part N° Quantity CY 15580100 1 Gasket for 1/4” and 3/8” Rotalock connections and valves V 100 - V 150 - V 240 - V 500(S) 1 CY 15580120 1 Gasket for 5/8”, 7/8” and 1” 1/8 Rotalock connections and valves V 1000(E) - V 1400(E) - V 2500(S) 1 CY 15580140 1 Gasket for 1/2” Rotalock connections and valves V 500(E) - V 1000(S) - V...

 Open the catalog to page 10