SINEAX DM5S/F-1

^CAMILLE BAUER Rely on us. System state monitoring: class 0.2 • All-purpose: V/I, P/Q/S, f, PF etc. • Remote communication via Modbus • DM5S: Energy metering class 0.5S • DM5F: Response time 15...25ms • Configuration even without power supply SINEAX DM5S/DM5F Programmable premium class heavy current transducers

 Open the catalog to page 1
SINEAX DM5S/F-2

DM5S/DM5F - The next transducer generation SINEAX DM5S and SINEAX DM5F are free-programmable universal measurement devices for heavy-current systems: Classical high-accuracy transducer, suited for monitoring tasks and retrofit applications in energy distribution and industry. The devices can be adapted fast and easily to the measurement task by means of the CB-Manager software - even if there is no power supply available. Depending on the device version measured quantities can be mapped proportionally to analog DC current outputs or to Modbus. The measurement is done uninterrupted in all four...

 Open the catalog to page 2
SINEAX DM5S/F-3

DM5S: Energy consumption monitoring in class 0.5S The DM5S supports up to 32 energy meters. To each of these meters a base measurement quantity and a tariff can be assigned. The present tariff is set via Modbus. For application with short measurement times, e.g. energy consumption for a single working day or production lot, the resolution can be adapted. Thanks to uninterrupted measurement and automatic range detection a high accuracy is achieved. • Up to 32 meters • Up to 16 tariffs (Control via Modbus) • Free selectable base quantity (P, Q, S, I) • High accuracy 0.5S • Uninterrupted measurement...

 Open the catalog to page 3
SINEAX DM5S/F-4

Technical data Inputs Nominal current: Maximum: Consumption: Overload capability: Nominal voltage: Maximum: Consumption: Impedance: Overload capability: Nominal frequency: Measurement TRMS: via screw terminals 6mm2 adjustable 1...5 A 7.5 A (sinusoidal) < I2 x 0.01 Q per phase 10 A continuous 100 A, 10 x 1 s, interval 100 s 57.7...400 VLN, 100...693 VLL 480 VLN, 832 VLL (sinusoidal) < U2 / 1.54 MQ per phase 1.54 MQ per phase 480 VLN, 832 VLL continuous 600 VLN, 1040 VLL, 10 x 10 s, interval 10 s 800 VLN, 1386 VLL, 10 x 1 s, interval 10 s 45. 50 / 60 .65 Hz up to 31st harmonic Ambient conditions,...