video corpo

SINEAX CAM
12Pages

{{requestButtons}}

Catalog excerpts

SINEAX CAM - 1

^CAMILLE BAUER UNIVERSAL MEASURING UNIT FOR HEAVY CURRENT VARIABLES CONTROLLING ANALYZING METERING

Open the catalog to page 1
SINEAX CAM - 2

POWER SYSTEM MONITORING THE UNCOMPROMISING MEASUREMENT SOLUTION The universal measurement system of the CAM is designed for a high-precision and disturbance insensitive measurement in multi-phase heavy current systems. The consistent (uninterrupted) measurement records reliably each change in the monitored mains. With its unique combination of hardware and software modules this measuring device provides a solution for each measurement task. The adaption to this task is performed quick and easy by means of the CB-Manager software. Single phase, 2-, 3- and 4-wire systems Strongly distorted...

Open the catalog to page 2
SINEAX CAM - 3

FREE COMPOSITION OF THE REQUIRED FUNCTIONS CAM BASIC DEVICE AS INITIAL POSITION • Measurement system: 3 voltages and 4 currents • Modbus/RTU- and USB interface for service, configuration and measurement acquisition • 2 relay outputs • Logic module for monitoring/control • Security system for granting access rights for up to 3 users • Synchronizable real-time clock as time base • Operating hours counter CUSTOMER SPECIFIC ADAPTION WITH OPTIONS • I/O interface: analog and digital I/Os • Data logger for measurement recordings for longer time periods • Lists: Recording of alarms, events and...

Open the catalog to page 3
SINEAX CAM - 4

POWER SYSTEM MONITORING PARAMETRIZATION, SERVICE AND MONITORING Analog output HM.niitti qn.«My votage U1N The CB-Manager software provides to the user the following functions: • Complete parametrization of the CAM (also offline) • Acquisition and recording of measured quantities • Archiving of configuration and measurement files • Setting or resetting of meter contents • Selective reset of extreme values • Setting of interface parameters • Adjustment of analog inputs • Simulation of all I/O module functions • Comprehensive help system A security system can be activated to restrict the...

Open the catalog to page 4
SINEAX CAM - 5

POWER SYSTEM MONITORING I/O INTERFACE POSSIBILITIES AND APPLICATIONS I/O modules can be assembled according to individual needs. Up to 4 modules with selectable functionality may be used. Five different hardware modules are available. ANALOGUE OUTPUTS ±20 mA 2 outputs per module 0/4...20 mA 2 outputs per module • On-site display via analog display units • Heavy-current measurements for PLC DIGITAL OUTPUTS 12/24 VDC 3 outputs per module (switchable to inputs) • Alarming output of the logic module • State reporting • Pulse output (S0) to external counter • Remote controllable ANALOGUE INPUTS...

Open the catalog to page 5
SINEAX CAM - 6

POWER SYSTEM MONITORING LONG-TERM RECORDINGS AND LOGGING The data logger allows to perform long-term recordings of measurement progressions or load profiles, e.g. to monitor the variable load of transformers, feeders or transmission lines. In addition to the recording of mean-values, fluctuations of instantaneous values may be registered to recognize load peaks at the earliest possible moment. By means of the automatical meter reading a time synchronous reading of the meter contents of all devices may be performed, e.g. on a weekly, monthly or three months base. These values can be stored...

Open the catalog to page 6
SINEAX CAM - 7

POWER SYSTEM MONITORING VISUALIZATION, ALARM HANDLING AND DATA ANALYSIS MEASUREMENT DISPLAY The display is intended for the visualization of measured data and entries of the alarm, event or operator list. Also state information or measurement information of the I/O interface may be displayed. The user can customize the display almost freely to his individual needs. If necessary a preference display or an automatical sequence of different pages can be defined as well. The navigation is done using the easy to operate keypad. ALARM HANDLING ON-SITE Alarms can be configured to be displayed...

Open the catalog to page 7
SINEAX CAM - 8

POWER SYSTEM MONITORING CONTROL SYSTEM CONNECTION VIA IEC 61850 (ED. 1) The communication standard IEC 61850 (..Communication networks and systems in substations") is the new standard for substation automation. Each possible device or system function is standardized and mapped in so called logical nodes (LN's). Also the complete communication and the engineering process are stated. So a high grade of independence from manufacturers is achieved. The field of application is situated in switchgears and transformer substations in the medium and high voltage area. The group Metering and...

Open the catalog to page 8
SINEAX CAM - 9

TECHNICAL DATA Rated voltage: Overriding max.: Consumption: Input impedance: Thermal ratings: Voltage, current: Power: Power factor: Frequency: Voltage unbalance U: Harmonics: THD Voltage: TDD Current: Active energy: Active energy: Reactive energy: Measurement TRMS: Up to the 63rd harmonic Measurement category: 300 V CATIII, 600 V CATII CURRENT MEASUREMENT Rated current: 1A (+ 20 %), 1A (+ 100 %), Consumption: s I2 x 0.01 Q per phase Thermal ratings: 12 A continuous Instead of current inputs the version for Rogowski coils provides voltage inputs of nominal 5 V (max. 10 V)....

Open the catalog to page 9
SINEAX CAM - 10

POWER SYSTEM MONITORING ANALOG OUTPUTS Linearization: Range: Burden: Burden influence: Residual ripple: Galvanic isolation: ANALOG INPUTS Range: Accuracy: Input resistance: Galvanic isolation: 12/24 V DC (30 V max.) < 7.0 mA s 50 Hz - 3 till + 5 V 8 till 30 V approx. 6.5 V / 2.6 mA I/O-INTERFACE RELAYS Contacts: Changeover contact active Linear, quadratic, kinked 0/4...20 mA (24 mA max.), unipolar or ± 20 A (24 mA max.), bipolar Accuracy: ± 0.1 % of 20 mA s 500 0 (max. 10 V / 20 mA) s 0.1 % s 0.2 % From all other connections (connected within group of terminals) 0/4.20 mA (24 mA max.)...

Open the catalog to page 10
SINEAX CAM - 11

VIBRATION WITHSTAND (acc. EN 60 068-2-6) Acceleration: ± 5 g Frequency range: 10 ... 150 ... 10 Hz, rate of frequency sweep: 1 Octave/Minute Number of cycles: 10 in each of the three axes Result: No faults occurred, no loss of accuracy and no problems with the snap fastener SECURITY The current inputs are galvanically isolated from each other. Protection class: II (protective insulation, voltage inputs via protective impedance) Pollution degree: 2 Protection: IP40, housing (test wire, IEC/EN 60 529) IP20, Terminals (test finger, IEC/EN 60 529) Measurement category: CAT...

Open the catalog to page 11

All Camille Bauer Metrawatt AG catalogs and technical brochures

  1. Camille Bauer

    12 Pages

  2. A2000

    10 Pages

  3. APLUS-LED

    89 Pages

  4. SINEAX F534

    4 Pages

  5. SIRAX BT5100

    32 Pages

  6. SINEAX V604s

    12 Pages

  7. SMARTCOLLECT

    8 Pages

  8. KINAX WT720

    4 Pages

  9. KINAX N702

    6 Pages

  10. KINAX HW730

    4 Pages

  11. SINEAX TV829

    2 Pages

  12. SINEAX DM5

    4 Pages

  13. SINEAX VS30

    4 Pages