SF6 6100 Pump Back Gas Analyser The Rapidox SF6 6100 Pump Back is a fully-automatic zero-emissions SF6 gas analyser, designed for controlling and monitoring the quality and purity of gas used in high voltage switchgear, circuit breakers and transformers. Exceptional accuracy and stability are provided when measuring the purity of SF6 gas, through specially selected sensors. The modular configuration allows for up to eight compatible gases to be analysed, simultaneously, using one analyser. The Rapidox is fully compatible with mixtures of SF6 CF4, N2 and air, together with toxic contamination gases such as SO2, HF, H2S and CO. The unit also measures the water content of the gas in dewpoint or ppm to ensure dryness is acceptable. The Rapidox SF6 6100 is housed neatly into a tough Peli transport case supplied with special tongue and groove self sealing couplings, which are compatible with famous brands. Once powered and connected, the Rapidox automatically removes a small quantity of gas from the electrical equipment, controlled with an auto gas pressure sensing function. A vacuum purge cycle and internal gas storage system ensures that no air can contaminate the gas sample and that no SF6 gas is able to escape during the testing period. All measured gases are analysed and data-logged simultaneously with only a few minutes required to achieve a stable reading. A powerful 10 bar compressor, with a separate lithium battery power supply, then returns the gas to the electrical equipment at high pressure. Results are displayed on screen and printed using the inbuilt thermal printer. The Rapidox has multiple safety features built in to ensure the cycle is completed correctly without gas loss or cross contamination. The analyser is pre-programmed with all current IEC and CIGRE test configurations, with the ability to create customised test parameters. Please contact Cambridge Sensotec for further information or to discuss Modular sensor choice Vacuum line purge Gas cylinder testing mode 6100 Pump Back has a number Walk away timer Multi language of standard features to enhance Auto abort function Vehicle charger Auto clean function Inbuilt CIGRE & IEC Tests
Open the catalog to page 1SF6 Gas SF6 is an extremely stable, non-flammable and highly electronegative gas with excellent dielectric properties. It is commonly used in medium and high-voltage electrical equipment as an electrical insulator, arc-quenching and cooling medium. However, SF6 is classified as a greenhouse gas and must be kept within a closed circuit to avoid any deliberate release into the atmosphere. The international Kyoto agreement protocol has mandated reductions to harmful emissions amongst its member states. For the power transmission and distribution network, SF6 technology remains essential. To protect...
Open the catalog to page 2Rapidox SF6 6100 Pump Back Sensor Specification The modular configuration allows for up to eight compatible gases to be analysed simultaneously with one analyser. SENSOR Sulphur Hexafluoride H2 O Dew Point -60oC to ±20oCdp (10 - 24,000ppmV) Reading is corrected to either RT or 20°C Sulphur Dioxide Hydrogen Fluoride LIFE SPAN Every 12 months by Sensor Exchange SENSOR TYPE Infrared (IR) Carbon Monoxide Electrochemical Electrochemical Electrochemical * For analysers containing a CF4 sensor, the measurement of Air is also a requirement. All sensor replacements to be carried out by Cambridge Sensotec...
Open the catalog to page 32 Pages