Designation and Series: The document describes the NCE D G 40 F - 120 / 250 series of energy-saving twin circulating pumps with flanges. These pumps are designed for heating, conditioning, and circulating systems in both civil and industrial applications.
Construction and Features: The pumps are equipped with a variable speed circulating pump driven by a permanent magnet synchronous motor, controlled by an onboard inverter. They feature DN ports with flanges and a maximum head of 120 dm. The pumps are designed for energy efficiency with an Energy Efficiency Index (EEI) ≤ 0.20.
Operating Conditions: The pumps operate within a liquid temperature range of -10 °C to +110 °C and an ambient temperature range of 0 °C to +40 °C. They can handle a maximum working pressure of 6/10 bar and are certified to meet CE requirements. The sound pressure level is ≤ 54 dB(A), and they can accommodate a maximum glycol quantity of 20%.
Motor Specifications: The pumps use a synchronous motor with permanent magnets, offering variable speed operation. They operate on a single-phase 230 V power supply with a frequency of 50-60 Hz. The motor is protected to IP 44 standards and has an insulation class of H.
Smart Pump Features: The NCED G.F pumps adapt their functions to the system by measuring pressure and flow, adjusting speed accordingly. They offer multiple operating modes, including automatic, proportional pressure, constant pressure, and fixed speed modes. A night mode is also available.
Operating Modes: The automatic mode is factory-set and adjusts operating pressure based on the hydraulic system. Proportional pressure mode adjusts pressure proportionally to flow, while constant pressure mode maintains pressure despite flow changes. Fixed speed mode allows operation at a constant curve.
Characteristic Curves: The document includes characteristic curves for various models, illustrating performance metrics such as flow rate (Q m³/h), head (H m), and power consumption (P W).
Dimensions and Materials: The document provides detailed dimensions and weights for different pump models. Key materials include cast iron for the pump casing, stainless steel for the impeller and shaft, carbon for bearings, and EPDM for gaskets.
See more

Catalog excerpts

NCED G F-1

Energy saving twin circulating pumps with flanges Construction Energy saving variable speed circulating pump driven by a permanent magnet synchronous motor (pm) controlled by on board inverter. Applications Heating, conditioning, circulating systems. For civil and industrial applications. Operating conditions - Liquid temperature from -10 °C to +110 °C - Ambient temperature from 0 °C to +40 °C - Maximum permissible working pressure: 6/10 bar - Storage: -20°C/+70°C max. relative humidity 95% at 40 °C - Certifications: in conformity with CE requirements - Sound pressure ≤ 54 dB (A). - Minimum suction pressure: - 0,5 bar at 50 °C. - 0,8 bar at 80 °C. - 1,4 bar at 110 °C. - Maximum glycol quantity: 20%. - EMC according to: EN 55014-1, EN 55014-2 EN 61000-3-2, EN 61000-3-2. - Connections: Flanges according to PN 6/10, EN 1092-2, DN 40, 50, 65, 80, 100. - The benchmark for most efficient circulators is EEI ≤ 0,20. Synchronous motor with permanent magnet. - Motor: variable speed - Standard voltage: single-phase 230 V (-10%;+6%) - Frequency: 50-60 Hz - Protection: IP 44 - Insulation class: H - Overload protection (integrated). - Cable: phases and neutral. - Constructed in accordance with: EN 60335-1, EN 60335-2-51. Twin pumps version Version DN ports in mm With flanges Max. head in dm connection size mm Features Operation Smart pump NCED G.F adapt its functions to the system: the circulator measures the pressure and the flow and adjusts the speed to the selected pressure. Easy use There are different operating modes selectable from the control panel. Single operation Operation of a single pump choosed by the customer, with the second pump on st

 Open the catalog to page 1
NCED G F-2

Energy saving twin circulating pumps with flanges Operating modes Automatic mode (factory setting): In this mode the pump automatically sets the operating pressure, depending on the hydraulic system. This mode is recommended in most systems. Proportional pressure mode: The circulator changes the pressure propotionally to the current flow. The pressure value can be adjusted with the + and - buttons. Constant pressure mode: The circulator mantains the pressure constant when the reference flow changes. The pressure value can be adjusted with the + and - buttons. Operating mode-control panel Fixed...

 Open the catalog to page 2
NCED G F-3

Energy saving twin circulating pumps with flanges

 Open the catalog to page 3
NCED G F-4

Energy saving twin circulating pumps with flanges

 Open the catalog to page 4
NCED G F-5

Energy saving twin circulating pumps with flanges Pump casing Cast iron Stainless steel Stainless steel Thrust bearing Stainless steel jacket Copper wire Electronic card

 Open the catalog to page 5

All Calpeda catalogs and technical brochures

  1. NM, NMS 60 Hz

    16  Pages

  2. NM, NMD

    12  Pages

  3. PMAT

    1  Page

  4. Catalot 50 hz

    624  Pages

  5. catalog 60 hz

    463  Pages

  6. MP 60Hz

    5  Pages

  7. MP 50Hz

    4  Pages

  8. GM 10

    2  Pages

  9. GQN

    4  Pages

  10. E-MXP

    8  Pages

  11. CS, CS-R. FK

    12  Pages

  12. NCE EI

    4  Pages

  13. NCE H

    5  Pages

  14. NCE H F

    5  Pages

  15. NCE G F

    5  Pages

  16. NCE EL

    4  Pages

  17. NCE GS F

    4  Pages

  18. NCE ES

    4  Pages

  19. NCE PS

    4  Pages

  20. NCS3

    3  Pages

  21. NC3

    4  Pages

  22. NCD3

    3  Pages

  23. NCD

    8  Pages

  24. IDROMAT

    2  Pages

  25. EASYMAT

    4  Pages

  26. VARIOMAT

    2  Pages

  27. BS

    90  Pages

  28. AUE, AUD, AUED

    20  Pages

  29. QM, QT

    25  Pages

  30. MXH

    12  Pages

  31. N, N4

    26  Pages

  32. NM, NMD

    12  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.