Main Characteristics
GRANY medium voltage load break switches/disconnectors are designed for board manufacturers to facilitate the creation of Air Insulated Switchgear (AIS) modular distribution units up to 24 kV. These devices are compact and utilize SF6 gas within a moulded epoxy resin enclosure that is permanently sealed. The switches are motorized, allowing for diverse medium voltage device functions.
  • Nominal voltage range: 5.5 kV to 24 kV
  • Dielectric resistance voltage: 50 kV (insulation) / 60 kV (disconnection)
  • Shock resistance voltage: 125 kV (insulation) / 145 kV (disconnection)
  • Nominal heat current: 630 A
  • Nominal breaking capacity: 12.5/16/20 kA
  • Nominal admissible short-term current: 12.5/16/20 kA
  • Closing power: 31.5/40/50 kA
  • Operating temperature range: -25°C to +50°C
Advantages
The GRANY switches offer several advantages, including:
  • Compact design
  • Very short breaking time due to a patented magnetic blow-out system
  • Extended lifespan with a permanently sealed system
  • Maintenance-free active parts
  • Enhanced operating safety
  • Low breaking overvoltage levels
  • Improved mechanical and electrical endurance
Uses
These switches are suitable for:
  • High and medium voltage board manufacturers
  • Medium voltage electrical cabinet designers
  • Manufacturers of medium voltage machines and devices
  • The medium voltage electrical device market
See more

Catalog excerpts

GRANY-1

MEDIUM VOLTAGE LOAD BREAK SWITCH-DISCONNECTORS 12-24 KV - GRANY MV load break switches/disconnectors designed for board manufacturers. Easy making of Air Insulated Switchgear (AIS) modular distribution units, up to 24 kV. Main characteristics GRANY switches/disconnectors are used for the production of very compact medium voltage cut-off devices in SF6. They consist of a moulded enclosure of epoxy resin, permanently sealed and filled with SF6. Movable contacts are triggered by manoeuvred mechanisms or mechanical energy reserves for a control manoeuvre. These switches are motorised and can design a wide variety of MV device functions in order to meet various needs in your applications. q q q q q q q q Nominal voltage: 5.5 kV to 24 kV Dielectric resistance voltage: 50 kV (insulation)/60 kV (disconnection) Shock resistance voltage: 125 kV (insulation)/145 kV (disconnection) Nominal heat current: 630 A Nominal breaking capacity: 12.5/16/20 kA Nominal admissible short-term current: 12.5/16/20 kA Closing power: 31.5/40/50 kA Operating temperature: - 25°C + 50 °C Compact solution Very short breaking time (patented system: magnetic blow-out) Extended life, permanently sealed system Maintenance free active parts Operating safety Very low breaking overvoltage level Improved mechanical and electrical endurance

 Open the catalog to page 1
GRANY-2

Solutions for HTA and medium voltage board manufacturers Solutions for medium voltage electrical cabinet designers Solutions for manufacturers of medium voltage machines and devices MV electrical device market

 Open the catalog to page 2
GRANY-3

Powered by TCPDF (www.tcpdf.org)

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.