XAR6

XAR6

Product catalog summary
Product Overview: The XAR6 is a filtered, unregulated power supply designed for input voltages of 12-24Vac and output voltages of 12-24Vdc with a maximum current of 6A. It is part of a series with non-stabilized output.
Input Technical Data: The power supply operates with an input rated voltage of 12-24 Vac and can handle input voltages ranging from 6 to 20 Vac. It operates at a frequency of 47 to 63 Hz and has a current consumption of 7.2 A at 24 Vac. Internal protection is provided by a T 8 A fuse, while external protection on the AC line requires a C-10 A circuit breaker or a T 10 A fuse.
Output Technical Data: The output voltage range is calculated as (Uin x 1.41) – 2V. It supports a continuous current of 6 A at 20°C. An external fuse is necessary for overload protection. The ripple at nominal ratings is 2.5 Vpp, and the hold-up time is greater than 20 ms. A LED indicator shows "DC OK" status.
General Technical Data: The operating temperature range is from –20 to +45°C. The device is not insulated between input and output but has a 0.5 kVac isolation for 60 seconds between input/ground and output/ground. It does not support parallel connection and has a protection degree of IP 00. The overvoltage category is II with a pollution degree of 2. Connection terminals are 2.5 mm², and the housing is made of UL94V-0 plastic material. Dimensions are 70x80x93 mm, and it weighs approximately 140 g. It should be mounted vertically on a rail, 20 mm from adjacent components.
Accessories: Compatible mounting rails include IEC60715/TH35-7.5 models PR/3/AC, PR/3/AC/ZB, PR/3/AS, and PR/3/AS/ZB.
Approvals and Markings: The product is powered by a 12-24 Vac secondary transformer and is rail mountable. Note that the output is not protected against overcurrent and short circuit, necessitating an external fuse.
See more

Catalog excerpts

XAR6-1

XAR6 Fiteredunregulated power supply input 12-24Vac / output 12-24Vdc max.6A Series Code Type HS code with not stabilized output INPUT TECHNICAL DATA Input rated voltage Input voltage AC Frequency Current consumption Internal protection fuse External protection on AC line MT: C-10 A / Fuse: T 10 A OUTPUT TECHNICAL DATA Output voltage range Continuous current Overload limiting Ripple @ nominal ratings Hold up time Status indication External fuse must be installed 2.5 Vpp >20 ms LED "DC OK" GENERAL TECHNICAL DATA Operating temperature range Input / output isolation Input / ground isolation Alarm contact Output / ground isolation Parallel connection Protection degree Overvoltage category / pollution degree Connection terminal Housing material Dimensions (LxHxD) Approximate weight Mounting information vertical on a rail, 20 mm from adjacent components * Powered by a 12-24 Vac secondary transformer * Rail mountable 1 Please refer to the datasheet for more details 2 Output not protected against overcurrent and short circuit, an external fuse must be installed. PRODUCT DESCRIPTION AR6 Fitered unregulated power supply input 12-24Vac / output 12-24Vdc max.6A Copyright © Cabur srl Sede legale Localita isola Grande, 45 - 17041 Altare (SV) - Italia - Tel. 019-589991 - Fax 019-58999233 - E-mail: [email protected]

 Open the catalog to page 1

All Cabur catalogs and technical brochures

  1. XBPS01AHAA

    1  Page

  2. XCSA120BC

    1  Page

  3. XCSA120BC

    1  Page

  4. X766845

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry