XT® / XT Plus® / XTH series
6Pages

{{requestButtons}}

Catalog excerpts

XT® / XT Plus® / XTH series - 1

TECHNOLOGIES, INC. Power Solutions • Low-maintenance lead-calcium alloy extends watering intervals • Design is optimized for high-rate, short duration discharges • Soft rubber post bushing minimizes stress on post seal, leak-free design using heli-arc process unique to C&D • Flame retardant covers standard to enhance battery plant safety • Electrical testing to 100% capacity assures performance of every battery • Warranty for cycle duty or float service is available • Hardened, lead-alloy terminals or copper-inserted posts provide better conductivity and tighter connections requiring less maintenance • 20 year life expectancy in float service at 77°F (25°C) ambient temperature LEAD CALCIUM BATTERIES FOR UPS AND SWITCHGEAR APPLICATIONS CAPACITIES FROM 0.370 TO 7.523 KILOWATTS PER CELL C&D Technologies’ flooded batteries are FEATURES & BENEFITS engineered to provide superior performance and reliability over the life of the product. These batteries are designed using proprietary techniques and quality components and materials for reduced maintenance and extended battery life. Sites that use XT Series batteries include: • Data Centers • Network Operations Centers • Industrial Process Control Facilities • Internet Hosting Sites • Semiconductor Manufacturing • Banks & Financial Markets • Power Generation Plants • Hospitals & Testing Laboratories • Emergency 911 Response Centers

Open the catalog to page 1
XT® / XT Plus® / XTH series - 2

t 8 Hour rate to 1.75 Vpc at 77°F (25°C), 1.215 Specific Gravity.

Open the catalog to page 2
XT® / XT Plus® / XTH series - 4

1.250 specific gravity @ 77°F (25°C) Ratings include connector voltage drop

Open the catalog to page 4
XT® / XT Plus® / XTH series - 5

• Proven quality • High performance • Fully tested • Wide range of KW ratings • Higher ratings and lower cost than XT-Plus XT Plus • All the benefits of the XT • More available discharge cycles XT Plus is ideal for sites with frequent blackouts and brownouts or locations that require the batteries to be cycled frequently to test other system components. Based on discharges at 15-minute rate to minimum voltage of 1.67 Vpc. XTH/XTH Plus • Newest Multi-Cell version • Less rack space required • Higher power density • Minimize maintenance • All the benefits of the Legacy XT Series batteries •...

Open the catalog to page 5
XT® / XT Plus® / XTH series - 6

C&D now offers a complete line of IBC 2009 certified stand-by battery racks, the RDC series, for the XT Series Batteries. Two Earthquake Protected battery storage rack categories (EP1 and EP2) are offered to suit a variety of seismic loading conditions. These designs have been qualified to the 2009 International Building Code (IBC), Chapter 16, “Structural Design”, Section 1613, “Earthquake Loads”. The qualification also covers the 2000, 2003, and 2006 versions of IBC as well as UBC 1994 and UBC 1997. See 12-560 flooded rack selection guide for more detail. TECHNOLOGIES, INC. 1400 Union...

Open the catalog to page 6

All C&D Technologies catalogs and technical brochures

  1. LCT-HP

    2 Pages

  2. LCZ

    2 Pages

  3. XDJ

    4 Pages

  4. L83_0117

    11 Pages

  5. Sageon® III

    4 Pages

  6. ARR Legacy

    4 Pages

  7. Lithium Ion

    4 Pages

  8. BBA-160RT

    2 Pages

  9. SGC Series

    4 Pages

  10. LCT II 1700

    2 Pages

Archived catalogs

  1. DC/DC Databook

    36 Pages