video corpo

BSR

BSR

BSR

Product catalog summary
Introduction
BRUSH Switchgear introduces the BSR circuit breaker as a retrofit solution for existing switchgear, utilizing advanced magnetic actuator technology. This solution extends the life of switchgear with minimal maintenance and no need for panel modifications.
Key Benefits
  • Utilizes proven technology with minimal maintenance requirements.
  • Eliminates the need for high capacity auxiliary supplies.
  • No civil works required; existing HV cabling remains undisturbed.
  • Improves health and safety by removing oil.
  • Extends the life of existing switchgear significantly.
  • Reduces owner costs due to low maintenance and increased lifespan.
  • Uses existing primary and automatic secondary contacts design.
  • Improves panel interlocking to meet latest ENA requirements.
  • Offers enhanced control and automation for distribution networks.
Technical Specifications
  • Rated Voltage: 12 kV
  • Normal Rated Currents: 630, 1250, 2000 A
  • Lightning Impulse Withstand Voltage: 75/95 kVP
  • Short Duration Power Frequency Withstand Voltage: 28 kV
  • Rated Frequency: 50 Hz
  • Rated Short-Time Withstand Current: 25 kA
  • Rated Peak Withstand Current: 62.5 kA
  • Rated Auxiliary Voltages: 30, 48/50, 110/125 V dc
  • Minimum Opening/Closing Time: 33ms/76ms
  • Normal Operations: 10,000
  • Weight: 211 Kg
  • Operating Mechanism: Magnetic actuator for closing, springs charged during closing stroke for opening
Standards and Compliance
  • ENA Technical Specification 41-36 Issue 3
  • ENA Technical Specification 50-18: 2008
  • ENA Technical Specification 50-19: 2003
  • ISO 9001: 2008
  • IEC 62271-100: 2003
  • IEC 60529: 2001
  • IEC 62271-1: 2007
Legacy Circuit Breakers
The VSI and VTD oil circuit breakers, manufactured between 1963 and 1990, and the VMV vacuum circuit breaker introduced in 1990, are predecessors to the BSR. The VMV circuit breaker was a direct replacement for the VSI/VTD, utilizing vacuum interrupter technology for improved safety and durability.
See more

Catalog excerpts

BSR-1

The BSR is an OEM designed retrofit circuit breaker for both the BRUSH Switchgear VSI range of Oil Circuit Breakers and the VMV vacuum Circuit Breaker, to IEC 62271-100. BRUSH Switchgear is proud of its heritage in the VSI, VTD & VMV range of switchgear, which continue to work at the highest standards today. Technological advances have allowed us to improve further and offer our customers a circuit breaker that boasts the award-winning magnetic actuator technology. The BSR circuit breaker, offers a new lease of life for existing switchgear, with this effective retrofit solution. Employing award-winning magnetic actuator technology with vacuum interrupters, the BSR is designed for 10,000 operations and a life expectancy of 30 years. It is designed for retrofitting into existing switchboards without the need for panel modification. Key Benefits to Retrofit • Superior, proven technology with minimal maintenance • Remove the need for high capacity auxiliary supplies • No civil works required and existing HV cabling remains undisturbed • Improvement of Health & Safety by removal of oil • Considerable life extension of the existing switchgear • Lower owner costs through virtually no maintenance requirements and increased switchboard life expectancy • Uses existing design of primary and automatic secondary contacts • Improved panel interlocking to latest ENA requirements • In addition to the retrofit of the circuit breaker BRUSH Switchgear can offer a more complete system solution to enhance the control and automation of the distribution network

 Open the catalog to page 1
BSR-2

VSI/VTD Circuit Breaker The BRUSH range of VSI and VTD oil circuit breakers was manufactured between 1963 and 1990 by BRUSH Switchgear boasting a global install base. The BRUSH range of oil circuit breakers have provided excellent service in both the 11kV primary and 6.6kV and 3.3kV secondary substation application. However, both time and development have offered us improved technology and mechanical endurance, which are present in the BSR retrofit circuit breaker, offering 10,000 operations and 30 year life expectancy. VMV Circuit Breaker In 1990, the VMV circuit breaker was introduced as a...

 Open the catalog to page 2