XDRCU-ALT Single-core Cable for 500/290 (550) kV

XDRCU-ALT Single-core Cable for 500/290 (550) kV

Product catalog summary
Technical Specifications
  • Conductor Cross-section: Ranges from 800 mm² to 2500 mm².
  • Outer Diameter: Approximately 124 mm to 144 mm.
  • Cable Weight: Approximately 19.9 kg/m to 37.1 kg/m.
  • AC Resistance: Varies from 31.6 mΩ/km to 11.3 mΩ/km.
  • Reactance: Ranges from 139 mΩ/km to 110 mΩ/km.
  • Capacitance: Between 0.130 µF/km and 0.225 µF/km.
  • Minimum Bending Radius: 2500 mm to 2900 mm.
  • Maximum Pulling Force: 48 kN to 150 kN.
Capacity and Installation
  • Ambient Temperature: 20°C and 35°C.
  • Soil Resistivity: 1.0 Km/W in air.
  • Load Factor: 1.0 and 0.7.
  • Current Capacity: Varies with cross-section and ambient conditions, e.g., 800 mm² supports 946 A to 1326 A.
Construction Details
  • Conductor: Copper, round stranded or segmented, with optional longitudinal water barrier.
  • Insulation: XLPE main insulation with inner and outer semi-conductive layers.
  • Screen: Copper wire with semi-conductive swelling tapes.
  • Sheath: Aluminium foil as radial diffusion barrier, thermoplastic oversheath for mechanical protection.
Features and Standards
  • Features: Low weight, low losses, low cost, internationally proven design, suitable for most applications.
  • Standards: Complies with IEC 62067.
Remarks

The inner semi-conductive layer, XLPE main insulation, and outer semi-conductive layer are extruded in a single operation using dry curing and water or nitrogen cooling methods.

See more

Catalog excerpts

XDRCU-ALT Single-core Cable for 500/290 (550) kV-1

XDRCU-ALT Single-core Cable for 500/290 (550) kV with Copper wire screen and Aluminium laminated sheath Construction * Copper conductor, round stranded or segmented, optionally with longitudinal water barrier * Inner semi-conductive layer firmly bonded to the XLPE insulation * XLPE main insulation, cross-linked * Outer semi-conductive layer firmly bonded to the XLPE insulation * Copper wire screen with semi-conductive swelling tapes above and below as longitudinal water barrier * Aluminium foil, overlapped and glued as radial diffusion barrier bonded to the oversheath * Thermoplastic oversheath as mechanical protection, optionally with semi-conductive and/or flame-retardant layer Remarks The inner semi-conductive layer, the XLPE main insulation and the outer semi-conductive layer are extruded in a single operation applying a dry curing and a water or nitrogen cooling method. Features * Low weight * Low losses * Low cost * Internationally proven design * Suitable for most applications Standards IEC 62067 Technical data 20170415-1 Subject to change without notice Calculation basis: Conductor temperature: 90°C, Frequency: 50 Hz, Laying depth: 1200 mm, Phase distance at flat formation: 30 cm, Earthing method: Single-Point Bonding or Cross-bonding