P9600 Shortform

P9600 Shortform

P9600 Shortform

Product catalog summary
Overview: The document provides technical specifications and features of Broyce Control's overcurrent and earth fault relays, designed for protection and control in electrical systems. These relays are equipped with programmable MODBUS options and various tripping characteristics such as IDMT, IDT, and DT.
Key Features:
  • True R.M.S. measurements for accurate detection.
  • Rear pluggable connectors for easy installation.
  • Low-set and High-set trip thresholds for both overcurrent and earth fault detection.
  • Six selectable IDMT characteristic curves or adjustable DT in compliance with IEC 60255-151.
  • Last trip memory capable of storing up to 10 events.
  • Three-phase overcurrent and earth fault detection with live display of individual phase and earth fault currents.
  • Pre-defined selectable CT ratios ranging from 5:5 to 6000:5.
  • Microprocessor-based design with self-checking and non-volatile memory.
  • Energy-efficient "Ecosmart" power supply design.
  • Supply voltage options include 18 - 55V AC/18 - 72V DC or 85 - 265V AC/85 - 370V DC.
Product Variants:
  • P9670: Overcurrent Relay.
  • P9690: Combined Overcurrent/Earth Fault with Voltage Monitoring.
  • P9680: Combined Overcurrent and Earth Fault.
  • P9620: Definite Time (DT) Earth Fault Relay.
  • P9660: Earth Fault Relay.
  • P9640: Inverse Definite Minimum Time (IDMT) Earth Fault Relay.
  • P9625: Definite Time (DT) Overcurrent Relay.
  • P9650: Inverse Definite Minimum Time (IDMT) Overcurrent Relay.
  • P9630: Inverse Definite Time (IDT) Overcurrent Relay.
Additional Features:
  • Adjustable Low-set and High-set tripping thresholds with options to disable High-set trip.
  • Adjustable Time Multiplier for defining curve tripping characteristics.
  • Instantaneous tripping on High-set triggering.
  • Test and Reset buttons for simulating and clearing fault conditions.
  • LED indicators for power supply presence and tripping conditions.
  • Terminals suitable for 2 x 2.5mm wires with protective cover.
Dimensions: The relays have a front dimension of 96 x 96mm, a main body dimension of 89.5 x 89.5mm, and a length of 107mm.
Compliance: The relays comply with ISO 9001:2015 standards, ensuring quality and reliability.
See more

Catalog excerpts

P9600 Shortform-1

BROYCEC O N T R O L Passionate about protection and control MODBUS OPTION IDMT, IDT, DT TRIPPING CHARACTERISTICS OVERCURRENT DETECTION EARTH FAULT DETECTION VOLTAGE, FREQUENCY POWER, POWER FACTOR, HOURS RUN

 Open the catalog to page 1
P9600 Shortform-2

OVERCURRENT & EARTH FAULT P9690 Combined Overcurrent/Earth Fault with Voltage Monitoring Key Features: Ÿ True R.M.S. measurements Ÿ Rear pluggable connectors provide quick and convenient method of installation Ÿ Low-set and High-set trip thresholds for both Overcurrent and Earth Fault detection Ÿ 6 selectable IDMT (Inverse Definite Minimum Time) characteristic curves or adjustable DT (Definite Time) in accordance with IEC 60255-151 Ÿ Last trip memory (up to 10 events) Ÿ Three phase Overcurrent and Earth Fault detection Ÿ Measurement and live display of individual phase and earth fault currents...

 Open the catalog to page 2
P9600 Shortform-3

OVERCURRENT & EARTH FAULT P9620 Definite Time (DT) Earth Fault Relay Key Features: Ÿ True R.M.S. measurements Ÿ Adjustable Low-set tripping threshold Ÿ Adjustable High-set tripping threshold with option to disable Ÿ Adjustable Definite Time setting (applicable to Low-set triggering only) Ÿ Instantaneous tripping on High-set triggering Ÿ Test and Reset buttons for simulating and clearing of fault condition Ÿ Red LED indication of Low-set or High-set triggering and tripping Ÿ Green LED indication for Auxiliary power supply presence Ÿ Microprocessor based (self checking) with non-volatile memory...

 Open the catalog to page 3
P9600 Shortform-4

OVERCURRENT & EARTH FAULT P9625 Definite Time (DT) Overcurrent Relay Key Features: Ÿ True R.M.S. measurements Ÿ Individual Trip Level adjustment for each phase Ÿ Adjustable Delay setting Ÿ Test and Reset buttons for simulating and clearing of fault condition Ÿ Red LED indication of which phase has been triggered Ÿ Red LED indication of actual tripped condition Ÿ Green LED indication for Auxiliary power supply presence Ÿ Microprocessor based (self checking) with non-volatile memory 2 Ÿ Terminals suitable for 2 x 2.5mm wires (complete with protective cover) Ÿ Supply voltage option: 115V AC or 230V...

 Open the catalog to page 4

All Broyce Control catalogs and technical brochures

  1. P50 shortform

    4  Pages

  2. TIMERS

    4  Pages

  3. BHRM

    1  Page

  4. LEIN

    1  Page

  5. LEDO

    1  Page

  6. LRTM/2

    1  Page

  7. LART

    1  Page

  8. LMMT

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.