LRTM/2

LRTM/2

Product catalog summary
Installation and Setting Instructions:
Before installation, ensure the power supply is isolated. Connect the unit as required. For the Delayed Pulse function, link terminals A1 and B1. Set the 'tOFF' and 'tON' range selectors to the desired time unit (seconds, minutes, hours). Adjust the 'Set %' for 'tOFF' and 'tON' to determine the percentage of the selected range. Apply power to start the timing process, indicated by a flashing green LED. The red LED indicates the relay's energized state during the 'tON' delay.
Technical Specifications:
Supply voltage ranges from 12 to 230V AC/DC with a frequency range of 48-63Hz. The unit supports a supply variation of +15/-10% for AC and +/-15% for DC. It features an overvoltage category III and a rated impulse withstand voltage of 4kV. Power consumption varies with voltage, with maximum values of 6.8VA for 230V AC and 1.9W for 230V DC. The timing function includes asymmetrical recycling 'Off/On' or Delayed Pulse. Timing ranges are selectable from 0.1 seconds to 100 hours. The unit has a reset time of less than 100ms and an accuracy of ±1% of the full scale.
Environmental and Output Specifications:
The unit operates within an ambient temperature range of -20 to +60°C and can handle relative humidity up to 95%. It features a DPDT relay output with ratings of 250V 8A for AC1 and 25V 8A for DC1. The electrical life is rated at over 150,000 operations at the rated load. The housing is made of orange flame-retardant material, and the unit weighs approximately 80g. It can be mounted on a 35mm DIN rail or directly on a surface.
Compliance and Approvals:
The unit conforms to IEC 61812 standards and is CE, C-tick, and RoHS compliant. It meets EMC immunity standards EN 61000-6-2 and emissions standards EN 61000-6-4.
Function Diagrams and Dimensions:
The document includes diagrams for Asymmetrical Recycling Off/On and Delayed Pulse functions. The unit dimensions are provided, with instructions for surface mounting using clips.
See more

Catalog excerpts

LRTM/2-1

Type: LRTM/2 Asymmetrical Recycling / Delayed Pulse Timer *NEW* 17.5mm DIN rail housing Microprocessor based Dual Function - Asymmetrical recycling “Off/On” AF or Delayed Pulse DP Separate adjustments for “on” and “off” ranges 7 Selectable time ranges (0.1 seconds – 100 hours) Fine adjustment of selected time range Multi-voltage input (12 – 230V AC/DC) DPDT relay output 8A Green LED indication for supply / timing status Red LED indication for relay status Conforms to IEC 61812 FUNCTION DIAGRAMS TECHNICAL SPECIFICATION Supply voltage U (A1, A2): Frequency range: Supply variation: Overvoltage category: Rated impulse withstand voltage: Power consumption (max.): AC: DC: Timing function: Asymmetrical Recycling “Off / On” or Delayed Pulse (A1 > B1 linked) Seconds: Minutes: 0.1 – 1 0.1 – 1 1 – 10 1 – 10 Timing ranges (7): (applies to “tON” and “tOFF”) Delayed Pulse (DP) (terminals A1 and B1 linked) Reset time2: Accuracy: Adjustment accuracy: Repeat accuracy: Drift with temperature: Power on indication / Timing1: Relay status: Ambient temp: Relative humidity: <100mS ± 1% of maximum full scale < 5% of maximum full scale ± 0.5% at constant conditions (IEC 61812) ± 0.05% / °C DPDT relay AC1 AC15 DC1 ≥ 150,000 ops at rated load 2kV AC (rms) IEC 60947-1 4kV (1.2/50µS) IEC 60664 BEFORE INSTALLATION, ISOLATE THE SUPPLY. out by qualified personnel. Connect the unit as required. If the Delayed Pulse function is required, place a link between terminals A1 and B1. Installation work must be carried Setting the unit. • Set the “tOFF” and “tON” “Range” selectors to the required position (depending on whether seconds, minutes or hours are required). • Set the “Set %” adjustment for the “tOFF” and “tON” as required. The “Set %” is a % of the selected range, so 60% of the 1 – 10 hour range will give 6 hours. Electrical life: Dielectric voltage: Rated impulse withstand voltage: Housing: Weight: Mounting option: Terminal conductor size Orange flame retardant UL94 ≈ 80g On to 35mm symmetric DIN rail to BS EN 60715 or direct surface mounting via 2 x M3.5 or 4BA screws using the black clips provided on the rear of the unit. ≤ 2 x 2.5mm2 solid or stranded Conforms to IEC 61812. CE, C-tick and RoHS Compliant. EMC: Immunity: EN 61000-6-2 (EN 61000-4-3 10V/m 80MHz - 2.7GHz) Emissions: EN 61000-6-4 Applying power. • Apply power and the green LED will start flashing to indicate timing is in progress. • The red relay LED will illuminate to indicate the relay is the energised state when the “tON” delay is running. • When the “tOFF” delay is running and relay is de-energised, the red LED will remain extinguished. • If the Delayed Pulse function is selected, the green LED will stop flashing and remain illuminated when the relay de-energises after the “tON” period. Note: 1 In accordance with IEC 61812, the green LED is permitted to extinguish during a voltage dip or momentary interruption of the power supply providing the state of the output relay does not change. The dip / interruption (reset) duration and levels are defined in the product standard however, the standard allows for these to be different from the levels actually specified. 2 Link terminals A1 and B1 for Delayed Pulse SETTING DETAILS 1. Power supply status / Timing (Green) LED 2. Relay output status (Red) LED 3. “tOFF” delay “Set %” adjustment 4. “tOFF” delay “Range” selector 5. “tON” delay “Set %” adjustment 6. “tON” delay “Range” selector Insert screwdriver to release clips CONNECTION DIAGRAM Withdraw clips fully when surface mounting Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: [email protected] Web: www.broycecontrol.com The Information provided in this literature is believed to be

 Open the catalog to page 1

All Broyce Control catalogs and technical brochures

  1. P50 shortform

    4  Pages

  2. TIMERS

    4  Pages

  3. BHRM

    1  Page

  4. LEIN

    1  Page

  5. LEDO

    1  Page

  6. LART

    1  Page

  7. LMMT

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.