FLEXICOPPER

FLEXICOPPER

FLEXICOPPER

Product catalog summary
Definition: The FLEXICOBRE range consists of flexible copper busbars made from Cu-ETP copper strips, insulated with a black PVC sheath. These busbars are designed to maintain dielectric insulation under various conditions.
Fields of Application: FLEXICOBRE is suitable for electrical connections in low voltage switchgear, panel boards, and appliances. It is also used for connecting generators, transformers, inverters, and control panels.
Product Range: The standard lengths are 2000 mm to 3000 mm, with strip widths ranging from 9 mm to 120 mm. The strips can be bare or tinned copper, with thicknesses of 0.5 mm, 0.8 mm, or 1 mm, depending on the width.
Raw Material: The copper conductor is made from annealed Cu-ETP with a copper content of 99.9%. Tinned copper strips have a tin coating thickness of 2 to 4 µm.
Insulation: The PVC insulation is black, with options for orange or blue upon request. It has a density of 1.36 and a hardness of 86 Shore A. The operating temperature ranges from -40°C to +105°C.
General Features: The maximum operating voltage is 1000 V AC or 1500 V DC, with a maximum temperature of 90°C or 105°C. The nominal insulation thickness is 2 mm, with a dielectric strength of 15 kV/mm between conductor and earth, and 30 kV/mm between conductors. The product complies with RoHS, CE marking, and UL 94 standards.
Permissible Current Rating: The current should not exceed 90°C for red copper and 105°C for tinned copper. The rated current and power losses are detailed in tables, with examples provided for specific configurations.
Tables: The document includes detailed tables of rated current and power losses for various configurations, as well as a table of tolerances for dimensions.
See more

Catalog excerpts

FLEXICOPPER-1

ÉLÉMENT SOUPLES - Gamme PVC 105°C FLEXIBLE ELEMENTS - Range PVC 105 °C DÉFINITION / DEFINITION Les barres souples isolées «Éléments Flexibles» sont composées d’un empilage de lames conductrices en couvre nu ou étamé, revêtues d’un isolant PVC noir The flexible copper busbars in the FLEXICOBRE range consist of an assembly of (Cu-ETP) copper strips, protected by an extruded PVC sheath (from 9mm to 50mm)* which ensures the products are dielectrically insulated irrespective of how the bars are distorted or their conditions of use. DOMAINE D’APPLICATION / FIELDS OF APPLICATIONS : FLEXICOBRE® ont été développés: - Pour toutes les connexions électriques dans les tableaux de distribution et les installations Basse Tension. - Pour le raccordement aux alternateurs, transformateurs, onduleurs, convertisseur et armoires secondaires. FLEXICOBRE® has been designed: - For all electrical connections in switchgear, panel board and electrical appliances in the Low Voltage area. - With the intent of connecting generator, transformer, inverter and panel control. GAMME PRODUIT / PRODUCT RANGE Longueur des barres / Standard length : Lame / Strip : Cuivre nu ou cuivre étamé. Bare copper or Tinned copper. Largeur lames / Width of the strip : Epaisseur lames Thickness of strip : 0,5 mm (pour largeur / for width of 13 mm) 0,8 mm (pour largeur / for width of 9 & 15.5 mm) 1 mm (pour les autres largeurs / for other width) Quantité de bande / Quantity of strip : Isolation / Insulation : Désignation Designation Epaisseur lame Strip thickness Largeur Width Nombre de lames Strip quantity MATIÈRE / RAW MATERIAL : Conducteur / Conductor : Isolant / Insulated part : Feuillard Cuivre selon EN 13599 / Bare Copper strip according to EN 13599 Désignation / Désignation : Recuit / Annealed Couleur / Colour : Noir / Black (Sur demande: Orange / Bleu) (Under request: Orange/Blue) Dureté shore A / Hardness, shore A (ISO R 868) : Résistance mécanique / Tensile strength (EN 60811-1-1) : Allongement à la rupture / Ultimate Elongation (EN 60811-1-1) : Température de service / Operating temperature : Etat métallurgique / Material Condition : Thermoplastique / compound : Teneur cuivre / Copper rate : Résistivité électrique à 20°C / Resistivity at 20°C : Résistance mécanique / Tensile strength : Allongement à la rupture / Elongation at breaking : Feuillard cuivre étamé selon EN 14436 Tinned copper strip according to EN 14436 : Revêtement d’étain / Tin coating : Épaisseur d’étain / Tin thickness : Caractéristiques générales / General features : Tension maximale de service Maximum Operating Voltage : Temperature maximale d’utilisation Maximum Operating Temperature : Épaisseur nominal isolant Nominal Insulation thickness : Rigidité diélectrique / Dielectric Strength : Entre conducteur et masse Beetween conductor and earth : Entre conducteurs / Beetween conductors : Autoextinguibilité / Self Extinguishing (NFC 32070 / IEC 60332-1) : Réglementations / Regulation : - Produits conformes à la directive RoHS / Product in compliance with RoHS directive. - arquage CE (UE Directive Basse tension) / M EC mark (Low Voltage directive). - Homologation UL 94 / UL 94 approval. Coefficient de calcul pour barres parallèles Calculation coefficient for parallel bars Pour 2 bars / for 2 bars: Pour 3 bars / for 3 bars: Les informations techniques ci-dessus sont indicatives et peuvent variées selon les conditions d’utilisations. Nous nous réservons le droit de procéder à des changements sans préavis. The technical information in this catalogue was determined with care but it could change in regards of use. We explicitly reserve the right to change it without prior notice.

 Open the catalog to page 1
FLEXICOPPER-2

INTENSITÉ MAXIMUM ADMISSIBLE / PERMISSIBLE CURRENT RATING : L’ Intensité maximale en régime permanent pour une température ambiante donnée doit être déterminée pour que la température du conducteur ne dépasse pas 90°C ou 105°C ci-dessous (tableau des valeurs ci-après). The steady operating current shall be such that the temperature reached by the conductor shall not be greater than 90°C or 105°C (See values on table below after). Exemple / Example : Élément Souple ES 24X1X8 CRN Température ambiante Ta = 40 °C Conducteur en cuivre rouge ΔT = 50 °C Donc Ta + ΔT = 90 °C Regarder dans la colonne...

 Open the catalog to page 2
FLEXICOPPER-3

TABLEAU DES INTENSITÉS ET PUISSANCES DISSIPÉES / TABLE OF RATED CURRENT & POWER LOSSES DESIGNATION SIZE Epaisseur Feuillard Thickness of individual copper sheet Nombre de feuillard No. Of laminates Largeur Width Les informations techniques ci-dessus sont indicatives et peuvent variées selon les conditions d’utilisations. Nous nous réservons le droit de procéder à des changements sans préavis. The technical information in this catalogue was determined with care but it could change in regards of use. We explicitly reserve the right to change it without prior notice. FLEXICOBRE. ELEMENT SOUPLES...

 Open the catalog to page 3
FLEXICOPPER-4

FLEXICOBRE. ELEMENT SOUPLES - Gamme PVC 105°C / FLEXIBLE ELEMENTS - Range PVC 105ºC Les informations techniques ci-dessus sont indicatives et peuvent variées selon les conditions d’utilisations. Nous nous réservons le droit de procéder à des changements sans préavis. The technical information in this catalogue was determined with care but it could change in regards of use. We explicitly reserve the right to change it without prior notice. Main office Complementary Facilities TELLURIUM COOPER RODS

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.