BRODERSEN COMPONENTS CONTROL & MONITORING RELAYS
Open the catalog to page 1^jP^^j^j^Mp^^^^p^j Export United Kingdom Germany E-mail: [email protected] E-mail: E-mail: [email protected]
Open the catalog to page 2Control & Monitoring Relays Introduction & Selection Guide MCU-10 Digital control relay MCP-10 Phase monitoring relay The Brodersen monitoring relays are high quality products incorporating up-to-date circuit design together with modern, efficient components to ensure a long trouble free life in a wide range of operating conditions. Power consumption and, thus, heat dissipation are minimal and the entire range has been de-signed and tested to the latest requirements for EMC immunity and emission. MXC-10 AC/DC current relay A wide range of commonly used standards of voltage, current, temperature...
Open the catalog to page 3Control & Monitoring Relays Phase Failure Relay PHASE MONITORING Control relay for monitoring of correct phase sequence, phase break and undervoltage. Connection to 3-phase mains supply with or without neutral. Fixed limits for energizing and de-energizing the single or double output relay. LED indication of supply voltage and phase failure. Versions available for DIN rail or 11-pole plug-in base mounting. Versions available for separate supply and measuring voltage. OPERATION The phase failure relay monitors phase sequence, phase break and undervoltage. The output relay is energized when all...
Open the catalog to page 4Phase measuring: With neutral: Without neutral: Fault: ϕ > 25°, typically by ϕ > 20°. Fault: ϕ > 50°, typically by ϕ > 40°. Monitoring of the supply voltage to a 3-phase motor with signal lamp indication of phase failure and motor contactor on. Terminals: Max. conductor size 4mm2. Screw type terminals with self-lifting clamps shrouded in accordance with VDE0106 (finger and back of hand protection). S1/S2: 11-pole plug in. D1: Directly on 35 mm DIN rail (EN50022). Mains frequency: Other AC voltages on request. Frequency: Mechanical lifetime: Electrical lifetime: Time delay: MECHANICAL DIMENSIONS...
Open the catalog to page 5Control & Monitoring Relays Digital Control Relay MCU-10...DV/AV Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of AC/DC The actual input signal type and measuring range must be specified when the control relay is ordered. 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail,surface and chassis...
Open the catalog to page 6TECHNICAL DATA WIRING DIAGRAMS Measuring ranges: Control & Monitoring Relays Digital Control Relay MCU-10...DV/AV Measuring accuracy: 1% of full scale ± 1 digit. Temperature drift: Voltage, current and temperature: Max. 0.01% per °C. The scale is adjusted to the actual measuring range listed in the ordering key. Display: 3½-digit LCD-type (-1999 to 1999). Digit height: 6.5 mm. Display update time: Typically 0.4 sec. SPDT (single changeover contact). D1/S1: Max. 8A/240V AC Min. 10mA/24VDC Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical...
Open the catalog to page 7Control & Monitoring Relays Digital Control Relay MCU-10...DC/AC Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of AC/DC The actual input signal type and measuring range must be specified when the control relay is ordered. 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail, surface and chassis...
Open the catalog to page 8TECHNICAL DATA WIRING DIAGRAMS Measuring ranges: Control & Monitoring Relays Digital Control Relay MCU-10...DC/AC 0-10.00A with external shunt 0-100.0A (60mV voltage drop) Input impedance: AC 0-19.99mA 0-199.9mA 0-1.99A 0-199.9A with external current 0-500A transformer (1A sec.) 60mV with shunt. I max Measuring accuracy: 1% of full scale ± 1 digit. 1% of full range. Temperature drift: Voltage, current and temperature: Max. 0.01% per °C. The scale is adjusted to the actual measuring range listed in the ordering key. Output relay: Load (cosϕ=1): SPDT (single changeover contact). D1/S1: Max. 8A/240V...
Open the catalog to page 9Control & Monitoring Relays Digital Control Relay MCU-10...P/N/T Digital control relay with 3½-digit LCD display. The control relay is used for control and measurement of Temperature with Pt-100, Ni-100, and thermistors The actual input signal type and measuring range must be specified when the control relay is ordered. 3½ digit LCD display with selectable read-out of actual input and setpoint. Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail...
Open the catalog to page 10Temperature drift: Measuring accuracy: 1% of full scale ± 1 digit. Display: 3½-digit LCD-type (-1999 to 1999). Digit height: 6.5 mm. Display update time: Typically 0.4 sec. The MCU-10 temperature controller is supported by a wide range of temperature sensors, see the temperature sensor data sheet for detailed technical information and ordering codes. The scale is adjusted to the actual measur ing range listed in the ordering key, except U1 version with user adjustable scale (-1999 to 1999, max. 2000 steps). SPDT (single changeover contact). D1/S1: Max. 8A/240V AC Min. 10mA/24VDC Frequency: Max....
Open the catalog to page 11Control & Monitoring Relays Digital Control Relay MCU-10...J/K/S/R Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of tempera- ture with thermocouples. The actual input signal type must be specified when the control relay 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail,surface and chassis...