Overview: The document outlines the technical specifications and operational guidelines for the Digital Control Relay MCU-10, used in various applications such as temperature monitoring with RTDs, thermistors, and thermocouples. It also covers other models like MXC-10, MXC-20, MXC-30, and MXV-30, designed for monitoring single-phase and three-phase currents and voltages.
Mounting Options: The MCU-10 relay can be mounted using an 11-pole plug-in or directly on a DIN rail, allowing for flexible integration into different systems.
Output Relay: Features a Single Pole Double Throw (SPDT) relay with a maximum load of 8A/240V AC and a minimum of 10mA/24VDC, supporting up to 1000 operations per hour at maximum load.
Supply Voltage: Supports a wide range of supply voltages from 12-48V DC, 12-30V AC, to higher AC voltages up to 380/415V AC, making it versatile for various power systems.
Input Specifications: Capable of measuring DC and AC currents and temperatures using RTDs and thermocouples with a 1% full-scale accuracy.
Display and Controls: Equipped with a 3½-digit LCD display for real-time monitoring and setpoint adjustments, updating every 0.4 seconds. Adjustments are made using a front-mounted potentiometer.
Operational Modes: Configurable to energize the output relay above or below a setpoint, with a hysteresis of 1% of the full range to prevent frequent switching.
Protection and Compliance: Conforms to EMC standards EN 50081-2/EN 50082-1, providing isolation up to 4kV AC for AC versions. It is housed in a protective casing with IP40 or IP20 protection, depending on the mounting type.
Applications: Suitable for general process instrumentation and signal monitoring, with the ability to scale outputs to engineering units for precise control and monitoring.
Technical Specifications: Includes measuring ranges for DC signals, input impedance, temperature drift, display features, output relay specifications, supply voltage options, and protection ratings.
Configuration and Calibration: User-adjustable within scale limits of -1999 to 1999 with a maximum span of 2000 steps. Provides a guide for calibrating the control relay using a 4-20mA input signal.
Single Phase Voltage Relay (MXV-10): Designed for detecting AC/DC over-or under-voltage with adjustable setpoint and hysteresis, automatic locking function, and inversion of relay function.
Single Phase Current Relay (MXC-10): Monitors AC or DC current with adjustable setpoint and hysteresis, automatic locking function, and inversion of relay function.
General Specifications: Designed according to standards such as EN60204-1, VDE0110, IEC664, and EN61010 for electrical safety and EMC compliance. CE-marked with protection ratings and specific mounting and terminal configurations.
Mechanical Dimensions and Technical Data: Provides specifications for MXL-10 and MXT-10 thermostat relays, including size, weight, input sensitivity, probe voltage and current, temperature drift, hysteresis, reaction time, and probe cable specifications.
Operation and Features: MXT-10 thermostat relay is used for temperature monitoring and control within a range of -50 to 300°C, featuring a Pt100 probe input, adjustable setpoint and hysteresis, and LED indicators for status updates.
Wiring and General Data: Includes wiring diagrams for MXL-10 and MXT-10, detailing connections for AC and DC supply, input, and output terminals, along with general data on ambient and storage temperature ranges, mounting specifications, and protection ratings.
See more

Catalog excerpts

control & monitoring relays-1

BRODERSEN COMPONENTS CONTROL & MONITORING RELAYS

 Open the catalog to page 1
control & monitoring relays-2

^jP^^j^j^Mp^^^^p^j Export United Kingdom Germany E-mail: [email protected] E-mail: E-mail: [email protected]

 Open the catalog to page 2
control & monitoring relays-3

Control & Monitoring Relays Introduction & Selection Guide MCU-10 Digital control relay MCP-10 Phase monitoring relay The Brodersen monitoring relays are high quality products incorporating up-to-date circuit design together with modern, efficient components to ensure a long trouble free life in a wide range of operating conditions. Power consumption and, thus, heat dissipation are minimal and the entire range has been de-signed and tested to the latest requirements for EMC immunity and emission. MXC-10 AC/DC current relay A wide range of commonly used standards of voltage, current, temperature...

 Open the catalog to page 3
control & monitoring relays-4

Control & Monitoring Relays Phase Failure Relay PHASE MONITORING Control relay for monitoring of correct phase sequence, phase break and undervoltage. Connection to 3-phase mains supply with or without neutral. Fixed limits for energizing and de-energizing the single or double output relay. LED indication of supply voltage and phase failure. Versions available for DIN rail or 11-pole plug-in base mounting. Versions available for separate supply and measuring voltage. OPERATION The phase failure relay monitors phase sequence, phase break and undervoltage. The output relay is energized when all...

 Open the catalog to page 4
control & monitoring relays-5

Phase measuring: With neutral: Without neutral: Fault: ϕ > 25°, typically by ϕ > 20°. Fault: ϕ > 50°, typically by ϕ > 40°. Monitoring of the supply voltage to a 3-phase motor with signal lamp indication of phase failure and motor contactor on. Terminals: Max. conductor size 4mm2. Screw type terminals with self-lifting clamps shrouded in accordance with VDE0106 (finger and back of hand protection). S1/S2: 11-pole plug in. D1: Directly on 35 mm DIN rail (EN50022). Mains frequency: Other AC voltages on request. Frequency: Mechanical lifetime: Electrical lifetime: Time delay: MECHANICAL DIMENSIONS...

 Open the catalog to page 5
control & monitoring relays-6

Control & Monitoring Relays Digital Control Relay MCU-10...DV/AV Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of AC/DC The actual input signal type and measuring range must be specified when the control relay is ordered. 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail,surface and chassis...

 Open the catalog to page 6
control & monitoring relays-7

TECHNICAL DATA WIRING DIAGRAMS Measuring ranges: Control & Monitoring Relays Digital Control Relay MCU-10...DV/AV Measuring accuracy: 1% of full scale ± 1 digit. Temperature drift: Voltage, current and temperature: Max. 0.01% per °C. The scale is adjusted to the actual measuring range listed in the ordering key. Display: 3½-digit LCD-type (-1999 to 1999). Digit height: 6.5 mm. Display update time: Typically 0.4 sec. SPDT (single changeover contact). D1/S1: Max. 8A/240V AC Min. 10mA/24VDC Frequency: Max. 1000 operations per hour at max. load. Mechanical life time: Min. 10 x 106 operations. Electrical...

 Open the catalog to page 7
control & monitoring relays-8

Control & Monitoring Relays Digital Control Relay MCU-10...DC/AC Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of AC/DC The actual input signal type and measuring range must be specified when the control relay is ordered. 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail, surface and chassis...

 Open the catalog to page 8
control & monitoring relays-9

TECHNICAL DATA WIRING DIAGRAMS Measuring ranges: Control & Monitoring Relays Digital Control Relay MCU-10...DC/AC 0-10.00A with external shunt 0-100.0A (60mV voltage drop) Input impedance: AC 0-19.99mA 0-199.9mA 0-1.99A 0-199.9A with external current 0-500A transformer (1A sec.) 60mV with shunt. I max Measuring accuracy: 1% of full scale ± 1 digit. 1% of full range. Temperature drift: Voltage, current and temperature: Max. 0.01% per °C. The scale is adjusted to the actual measuring range listed in the ordering key. Output relay: Load (cosϕ=1): SPDT (single changeover contact). D1/S1: Max. 8A/240V...

 Open the catalog to page 9
control & monitoring relays-10

Control & Monitoring Relays Digital Control Relay MCU-10...P/N/T Digital control relay with 3½-digit LCD display. The control relay is used for control and measurement of Temperature with Pt-100, Ni-100, and thermistors The actual input signal type and measuring range must be specified when the control relay is ordered. 3½ digit LCD display with selectable read-out of actual input and setpoint. Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail...

 Open the catalog to page 10
control & monitoring relays-11

Temperature drift: Measuring accuracy: 1% of full scale ± 1 digit. Display: 3½-digit LCD-type (-1999 to 1999). Digit height: 6.5 mm. Display update time: Typically 0.4 sec. The MCU-10 temperature controller is supported by a wide range of temperature sensors, see the temperature sensor data sheet for detailed technical information and ordering codes. The scale is adjusted to the actual measur ing range listed in the ordering key, except U1 version with user adjustable scale (-1999 to 1999, max. 2000 steps). SPDT (single changeover contact). D1/S1: Max. 8A/240V AC Min. 10mA/24VDC Frequency: Max....

 Open the catalog to page 11
control & monitoring relays-12

Control & Monitoring Relays Digital Control Relay MCU-10...J/K/S/R Digital control relay with 31/2-digit LCD display. The control relay is used for control and measurement of tempera- ture with thermocouples. The actual input signal type must be specified when the control relay 31/2 digit LCD display with selectable read-out of actual input and Output relay with LED indication of energized output relay. Built-in power supply for direct mains supply. Galvanic isolation between input and supply. Standardized housing for 11-pole plug-in or DIN rail mounting. Bases for DIN rail,surface and chassis...

 Open the catalog to page 12

All Brodersen Controls catalogs and technical brochures

  1. UDC-32

    4  Pages

  2. UDC-35

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.