Catalog excerpts
Your Heating Specialist since 1949 SLCAB Self-Regulating Heating Cable Product Highlights Ideal for freeze protection and low temperature process maintenance up to 150°F (66°C) CABLE / WIRE Automatically adjusts heat output based on surface temperature Safe to overlap and insulate Can be cut-to-length and terminated in the field No temperature controller is required* * If a specific process temperature is required, a temperature controller is necessary. • Continuous maintenance temperature: 150°F (66°C) maximum • Intermittent exposure temperature: 185°F (85°C) maximum; -20°F (-29°C) minimum • 3, 5, 8, or 10 watts/ft (10, 16, 26, or 33 watts/m) • Supply voltages: 110 - 120VAC or 208 - 277VAC • Moisture, chemical, and flame resistant • 16AWG bus wires • Braid resistance: - Tinned copper: 0.003 ohms/ft (0.009 ohms/m) - Stainless steel: 0.125 ohms/ft (0.410 ohms/m) • T-Rating** - T6: 3, 5, and 8 watts/ft (10, 16, and 26 watts/m) - T5: 10 watts/ft (33 watts/m) ** Electrical equipment T-rating codes define the maximum surface temperature that equipment will reach. It is used in hazardous (classified) area applications. Ordinary Locations Hazardous (Classified) Locations Class I, Division 2, Groups B, C, D Class II, Division 2, Groups F, G Class III, Division 2 Ordinary Locations 2E*, 3(A,B,C), 5(A,B) Hazardous (Classified) Locations Class I, Division 2, Groups B, C, D Class II, Division 2, Groups E, F, G Class III, Division 2 Approvals valid only when used with appropriate heating cable and installation accessories, and installed in accordance with all applicable instructions, codes, and regulations. *2E approved for 3 watts/ft and 5 watts/ft only Outer Layer Options Product Type Shipping Weight: Per 500-ft (152m) spool Tinned Copper Metal Braid Ordinary applications Tinned Copper Metal Braid with Thermoplastic Elastomer Overjacket For use in wet or weak chemical environments (i.e. weak acids) Tinned Copper Metal Braid with Fluoropolymer Overjacket For use in strong chemical environments (i.e. strong acids) Stainless Steel Metal Braid More resistant to rusting and corrosion than Tinned Copper Metal braid. Toll Free: 800-848-7673 Phone: 614-294-3376 w w w .BriskHeat. c o m Email: bhtsales1@briskheat.com Fax: 614-294-3807
Open the catalog to page 1Your Heating Specialist since 1949 SLCAB Self-Regulating Heating Cable Specification / Application Information: Maximum Circuit Length in Feet Vs. Circuit Breaker Size Circuit Breaker Size Heat Output (Watts per Foot) CABLE / WIRE Heat Cable Type Voltage Adjustment Power Adjustment Factor Product Type Note: Special consideration must be given for the circuit breaker due to the high initial in-rush currents. Ordering Information: Part Number Matrix SLCAB 3 120 BF Watts / ft: 3, 5, 8, 10 Voltage: 120- (110 - 120VAC), 240- (208 - 277VAC) Outer Layer: B- (Tinned Copper Metal Braid) BP- (Tinned...
Open the catalog to page 2Your Heating Specialist since 1949 FM Approved SLCAB Connection / Termination Kits USAGE CABLE / WIRE 3/4” (19mm) NPT pipe standoff Ring terminals Large, insulated crimp connectors Small, insulated crimp connectors Pipe straps (for up to a 6” [152mm] IPS pipe) Heat shrink end caps 6” (152mm) shrink sleeve 3 oz. (89ml) tube of RTV sealant Roll of fiberglass tape Caution label Ground screw Ordinary Locations Hazardous (Classified) Locations APPROVED Class I, Division 2, Groups B, C, D Class II, Division 2, Group F, G Class III, Division 2 Approvals valid only when used with appropriate...
Open the catalog to page 3Your Heating Specialist since 1949 CSA Approved SLCAB and SLMCAB Connection / Termination Kits USAGE KITS SLCABUC-CSA-M: SLCAB and SLMCAB Universal Connection Kit. CSA approved. Connector body Connector cap Connector gland washers Grommet Termination boot Strain relief grip Standoff bracket Locknut Termination block Roll of fiberglass tape Silicone sealant Pipe strap (for 2” to 6” [51 to 152mm] O.D. pipes) Ring tongue terminal End seal kit SLCABEND-CSA-2: SLCAB and SLMCAB End Seal Kit. CSA approved. 1 1 1 Approvals valid only when used with appropriate heating cable and installation...
Open the catalog to page 4Your Heating Specialist since 1949 SLCAB Roof and Gutter Kits and Accessories USAGE KITS ROOFPKIT: Roof and Gutter Power Connection Kit 1 1 1 CABLE / WIRE Ground screw Grommet Sealing fitting: connector body, cap, gland washer, and locknut Shrink sleeve, 0.5” (13mm) diameter, 1.5” (38mm) length Yellow / green shrink sleeve Shrink sleeve 0.125” (3mm) diameter, 5.5” (140mm) length Crimp connectors Shrink sleeve, 0.75” (19mm) diameter, 6” (152mm) length Ring terminal ROOFEND5: Roof and Gutter End Seal Kit 5 5 Black Shrink Tubes, 0.5” (13mm) diameter, 4” (102mm) length Black Shrink Tubes, 0.5”...
Open the catalog to page 5All BRISKHEAT CORPORATION catalogs and technical brochures
-
reusable cloth insulator
4 Pages
-
Etched foil heater
2 Pages
-
GCW/HWC
2 Pages
-
Blanket Heating
1 Pages
-
ECONO
1 Pages
-
DHCS/DHCH/DPCS/DPCH
1 Pages
-
INS
1 Pages
-
NEW APPROVAL
2 Pages
-
CLOTH HEATING JACKETS
3 Pages
-
etched foil heaters
1 Pages
-
general catalog
128 Pages