Product catalog summary
Technical Specifications
  • Type: Control Transformer Class 1 Isolation Transformer with Earth Screen between Primary and Secondary
  • Standards: IEC / BS-EN 61558
  • Frequency: 50/60Hz
  • Insulation Class: B, F, or H
  • Insulation Resistance: Greater than 5 Meg Ω
  • Dielectric Strength: Greater than 2.5kV for Primary to Secondary, Primary to Earth, and Secondary to Earth
  • Ambient Temperature: 40°C
Transformer Circuit Protection
  • Transformers must be protected against short circuit and overload.
  • Primary Circuit: Protection against short circuit is necessary, considering high inrush current during energizing. Suggested protection values are provided to avoid nuisance tripping.
  • Secondary Circuit: Protection should be equal to or less than the rated output current.
Protection Values Table
Rating (VA)Primary VoltsAmps FuseType C MCBType D MCB
300023013.042040
400023017.392563
500023021.73263
750023032.605063
1000023043.4763100
1500023065.2111063
2000023086.95150
30000230130.43200
40000230173.91300
Transformer Dimensions and Performance
Part No.VAABCDEWeight (Kg)% Reg.Watts LossInrush VA for 10% Volt DropInrush VA for 5% Volt Drop
CL300020011527516085203.4160118007400
CL4000200135275160105253.4170157009800
CL5000240140390200100403.11802500015000
CL7500240160390200120503.02104300025700
CL10000280230440240130702.92545000035000
CL150002802604402401701001.9350
CL200003203204902802001301.9560
CL300004003506903001701901.8950
CL400004003506903001802251.81100
See more

Catalog excerpts

Single Phase Transformers CL Range-1

Single Phase Transformers CL Range Data Sheet Technical data_________________________________________________ Control Transformer Class 1 Isolation Transformer with Earth Screen between Primary and Secondary IEC / BS-EN 61558 TBA TBA 50/60Hz B, F or H ˃ 5 Meg Ω Primary to Secondary. ˃ 2.5kV Primary to Earth ˃ 2.5kV Secondary to Earth ˃ 2.5kV 40° C Standard Primary Voltages Secondary Voltages Frequency Insulation Class Insulation Resistance Dielectric Strength Ambient Temperature Transformer circuit protection Transformers must be protected against short circuit and overload Primary circuit. The primary side of the Transformer should be protected against short circuit thereby cutting the supply voltage in the event of a short circuit fault. The rating of the primary protection device has to take into account the high inrush current during energizing of the Transformer. The table below gives suggested protection values to avoid nuisance tripping on inrush Secondary circuit. The secondary circuit should be protected against short circuit and overload. The value of the protection should be the same or less than the rated output curr

 Open the catalog to page 1
Single Phase Transformers CL Range-2

Watts Loss Inrush VA For 10% Volt drop

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.