FCR05/07

FCR05/07

FCR05/07

Product catalog summary
Overview: The document provides technical specifications and features of the new generation FCR05 and FCR07 power factor controllers by BMR Trading. These controllers are designed to enhance performance with improved sensitivity and measurement precision.
Specifications:
  • Supply Voltage: 400 V AC or 230 V AC (+10%, -15%)
  • Frequency: 50 / 60 Hz
  • Current Range: 10 mA to 6 A
  • Measurement Accuracy: ± 2%
  • Number of Step Outputs: 6 (FCR05) or 8 (FCR07)
  • Power Consumption: 10 VA
  • Last Output as Alarm Output: 250 VAC / 5 A
  • Switching Power of Relay Output Contacts: 250 VAC / 5 A
  • Requested Power Factor Range: 0.8 ind. to 0.8 cap.
  • Reconnection Delay: 5 to 900 seconds
  • Working Temperature: -40°C to +80°C
  • Site Depth: 55 mm
  • Front Panel Dimensions: 97 x 97 mm
  • Panel Cutout: 91 x 91 mm
  • Weight: 0.65 kg
  • Switching Off Delay: 5 to 900 seconds
  • Communication Interface: RS485 with Modbus RTU protocol
  • Protection Degree: IP20 rear cover / IP54 front panel
  • Communication Speed: Up to 38400 Bd
  • Measuring Voltage: L-L 400 VAC or L-N 230 VAC
  • Adjustable Step Reactive Power Range: 999 kVAr ind. to 999 kVAr cap.
  • Standards: EN 61010-1, EN50081-1, EN50082-1
Features:
  • 4 Quadrant Measurement and Compensation
  • Four Digits Display with Dichromatic Indication LED
  • Current Measurement Sensitivity from 10 mA
  • Symbolic Menu for Easy Setting and Operation
  • Automatic Detection of System Connection and Capacitor Battery Composition
  • Reactive Power Offset Feature
  • Menu Parameter Lock for Panel Builders
  • Ready for Compensation in LV and HV Systems
  • Independent Setting of Every Step Output
  • APFR or Instantaneous Power Factor Regulation
  • Ready for De-compensation Reactors Usage
  • Programmable Alarm Last Output with Adjustable Response
  • Temperature Measurement with Adjustable Alarm Level and Forced Ventilation Start
  • Memory for Maximum and Minimum Values Recording
  • Operation Number Counter and Working Hour Counter for Each Step
  • Measurement of U, I, f, cosφ, THDI, THDU, U harm, I harm, P, Q, S, temp.
See more

Catalog excerpts

FCR05/07-1

FCR05/FCR07 power factor controllers new generation of FCR05/FCR07 power factor controller range New generation of FCR05 / FCR07 controllers brings new features and performance of existing range. Faster processor and better AD converters increse the sensitivity for measurement of current, add the fast measurement of voltage and current for more precise computing and many other interesing improvements. • 4 quadrant measurement and compensation • Four digits display and dichromatic indication LED • Measurement of current with sensitivity from 10 mA Power supply voltage Measuring voltage Last output alarm • Symbolic menu for easy setting and operation • Independent setting of every step output • APFR (average power factor regulation) or instantaneous power factor regulation • Automatic detection of system connection and capacitor battery composition in all 4 quandrants • For FCR07 controller enlarge number of outputs to 8 • Reactive power Offset feature • Menu parameter lock for panel builders • Ready for compensation in LV and HV systems • Ready for de­compensation reactors usage with possibility to use one reactor tuned by capacitor steps • Programmable response • Temperature measurement with adjustable level for alarm and forced ventilation start • Memory for maximum and minimum values recording • Operation number counter adn working hour counter for each step • Communication interface RS485 (Modbus RTU) • Measurement of U, I, f, cosφ, THDI, THDU, U harm, I harm, P, Q, S, temp. BMR trading, Horní lán 17, 779 00 Olomouc, Czech Republic, tel.: +420 778 066 566, export@bmr­trading.com, www.bmr­trading.com

 Open the catalog to page 1
FCR05/07-2

FCR05/FCR07 power factor controllers new generation of FCR05/FCR07 power factor controller range Supply voltage Measuring voltage Current range Measurement accuracy Power consumption Number of step outputs Last output as and alarm output Switching power of relay output contacts Range of adjustable step reactive power Range of requested power factor Reconnection delay Communication interface Communication protocol Communication speed Compensation stages value setting manually / automatically Working temperature Front panel Panel cutout Site depth Protection degree IP20 rear cover / IP54 front...

 Open the catalog to page 2

All BMR trading catalogs and technical brochures

  1. FCR06/12

    2  Pages

  2. PLA33

    3  Pages

  3. PLA34

    3  Pages

  4. PLA34RGP

    3  Pages

  5. PLA44

    3  Pages

  6. PLA44RGP

    3  Pages

  7. Catalogue

    44  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.