SFA 400

SFA 400

SFA 400

Product catalog summary
Overview: The document provides technical specifications and details for Sine Filters, specifically the SFB and SFA 400 series. These filters are designed for use with inverters and motors to improve performance and reduce interference.
Specifications:
  • SFB Series: Includes models like SFB 400/4 to SFB 400/480, with varying terminal sizes, fixing methods, and weights. They are designed for vertical mounting and have specific dimensions and weights ranging from 4.0 kg to 220.0 kg.
  • SFA Series: Models range from SFA 400/1.3 to SFA 400/60, with rated voltages of 3 x 400 Vac and current ratings from 1.3 A to 60 A. They support motor outputs from 0.55 kW to 30 kW and have a maximum ambient temperature of 45°C.
General Data:
  • Rated voltage for SFA 400 is 3 x 400 Vac, and for SFA 500 is 3 x 500 Vac.
  • Switching frequencies are up to 8 kHz for SFA 400 and 4 kHz for SFA 500.
  • Insulation class is H, with a protection index of IP 20.
Advantages:
  • Prevents motor overvoltages and allows for long cable lengths.
  • Reduces motor noise, bearing currents, and leakage currents.
  • Minimizes line-borne and field-borne interference, reducing the need for shielded cables.
  • Improves drive system efficiency and extends motor service life.
Applications: These filters are used for suppressing differential and common mode interference in inverter systems, enhancing performance and reliability.
Standards and Approvals: Complies with IEC 61558-2-20, UL 508, CSA 22.2 No. 14-10, UL 5085-1/-2, and CSA 22.2 No.66.
Safety and Protection:
  • Metal enclosures with insulation class F.
  • Test voltage of 2500 Vac, 50 Hz.
  • Safety class I prepared.
See more

Catalog excerpts

SFA 400-1

Reactors / EMI filters All-pole sine filters All-pole sine filter SFA 400 BLOCK Website General Data Rated voltage 3 x 400 Vac Rated current 1.3 - 60 A Designed for inverter with DC link connector (+Vdc), positive or negative or mid point and and works with continuous PWM (please contact our technical support staff) For motor rated output 1.5 - 30 kW For switching frequencies ð 8 kHz Rated frequency from 0 to 60 Hz Insulation class H Maximum ambient temperature 45 °C Advantages Prevention of overvoltages on the motor Long cable lengths possible Reduction in motor noise Minimisation of bearing currents Minimisation of leakage currents (is beneficial in the event of incorrect RCD tripping) Reduction in line-borne and field-borne emitted interference: can be omitted from shielded cables, where necessary Reduction of motor losses Applications Sine filter for the suppression of differential mode interference and common mode interference. Designed for inverter with DC link connector (+Vg/+Ug), positive or negative or mid point and and works with continuous PWM (please contact our technical support staff). Output filter with capacitor for frequency inverters complying with IEC 61558-2-20, UL 508, CSA 22.2 No. 14-10

 Open the catalog to page 1
SFA 400-2

Reactors / EMI filters All-pole sine filters All-pole sine filter SFA 400 O BLOCK Website Typ Operating data Rated voltage Voltage range Voltage drop Rated current for motor rated output approx. Rated frequency Switching frequency Approvals Approvals Environment Ambient temperature max. Safety and protection Type Insulation class Protection index Safety class (prepared) Test voltage Order numbers Order Number cURus cURus cURus cURus cURus cURus Metal enclosure Metal enclosure Metal enclosure Metal enclosure Metal enclosure Metal enclosure

 Open the catalog to page 2
SFA 400-3

Reactors / EMI filters All-pole sine filters BLDCKE5 All-pole sine filter SFA 400 O BLOCK Website 1.1 Typ Operating data Rated voltage Voltage range Voltage drop Rated current for motor rated output approx. Rated frequency Switching frequency cURus cURus cURus cURus cURus Safety and protection Type Insulation class Protection index Safety class (prepared) Test voltage Order numbers Metal enclosure Metal enclosure Metal enclosure Metal enclosure Metal enclosure

 Open the catalog to page 3
SFA 400-4

Reactors / EMI filters All-pole sine filters All-pole sine filter Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Screw clamp, Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Mounting lugs Dimension pictures Dimension pictures

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.