TT3-A016-4040-0

TT3-A016-4040-0

TT3-A016-4040-0

Product catalog summary
Advantages
  • Provides safe galvanic isolation.
  • Features excellent corrosion protection and low noise due to BLOCK IMPEX vacuum impregnation.
  • Efficient thermal loss discharge through optimally arranged cooling channels within the coils.
  • Equipped with integrated crane eyes for easy handling.
  • Capable of handling voltages up to 1 KV if needed.
Applications

The isolating transformer is used for safe electrical isolation between input and output sides. It is suitable for establishing protective separation as a safety measure in compliance with VDE 0100.

Standards
  • Complies with VDE 0570 part 2-4, DIN EN 61558 part 1 with part 2-4.
Approvals
  • UL 1561, CSA 22.2 (E 327358).
Specifications
  • Type: TT3-A016-4040-0
  • Input: Rated input voltage of 3 x 400 Vac, frequency 50 - 60 Hz.
  • Output: Rated output voltage of 3 x 400 Vac, power 16,000 VA, output rated current 3 x 23.1 A, short circuit voltage 4.4%, vector group Dyn 5.
  • Environment: Maximum ambient temperature of 104.0 °F.
  • Safety and Protection: Insulation class F, protection index IP 00, open type, safety class I (prepared), non-short-circuit proof.
Order Information
  • Recommended sheet-metal enclosure: BGE-080.
  • Order Number: TT3-A016-4040-0.
Terminal and Mounting
  • Terminals: Screw-type terminal 10 mm², input and output screw clamp 10 mm², connection type screw-type terminal 4 mm².
  • Fixing method: Fixing rail.
Measures and Weights
  • Core type: 3UI 240/110.
  • Weight: 262.35 lbs.
See more

Catalog excerpts

TT3-A016-4040-0-1

Advantages Safe galvanic isolation Very good corrosion protection and low noise due to BLOCK IMPEX vacuum impregnation Very good discharging of thermal losses by means of optimally arranged cooling channels within the coils Integrated crane eyes If needed, voltages up to 1 KV are available Applications Isolating transformer for the safe electrical isolation of the input and output sides. The transformer may be used to set up protective separation as a protective measure in accordance with VDE 0100. Sample application Isolating transformer to: VDE 0570 part 2-4, DIN EN 61558 part 1 with part 2-4

 Open the catalog to page 1
TT3-A016-4040-0-2

Rated input voltage Rated frequency Output Rated output voltage Power Output rated current Short circuit voltage Vector group Terminal and mounting Terminals Fixing method Terminals Input Terminals Output Connection type Screw-type terminal 10 mm² Fixing rail Screw clamp, 10 mm² Screw clamp, 10 mm² Screw-type terminal, 4 mm² Measures and weights Core type Weight Environment Ambient temperature max. Safety and protection Insulation class Protection index Type Safety class (prepared) Short circuit strength F IP 00 Open type I non-short-circuit proof Order numbers Recommended sheet-metal enclosure...

 Open the catalog to page 2

All BLOCK Electronics (Kunshan) Co., Ltd catalogs and technical brochures

  1. BLOCK COMPACT

    80  Pages

  2. RTE 30/2x24

    2  Pages

  3. RTE 20/2x24

    2  Pages

  4. RKD 30/2x24

    2  Pages

  5. RKD 20/2x24

    2  Pages

  6. the big BLOCK

    719  Pages

  7. ALL ABOUT BLOCK

    17  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.