1. Catalogs
  2. bionomicind
  3. QSense Waste Heat Recovery Systems

QSense Waste Heat Recovery Systems

QSense Waste Heat Recovery Systems

Product catalog summary
Overview:
QSense™ Waste Heat Recovery Systems are designed to efficiently recover waste heat from hot gases to heat water or other liquids using a direct contact method. This system helps reduce energy consumption and fuel costs while cleaning flue gas contaminants and lowering exhaust temperatures. It is suitable for process heating applications and building space heating, utilizing waste flue gas from various sources such as boilers, kilns, ovens, dryers, thermal oxidizers, and incinerators. The system is available in a vertical configuration to save space and includes all necessary components for complete functionality. For gases with acid contaminants, neutralizing chemical reagents can be added, and for particulate-laden gas streams, a pre-scrubber and clog-resistant contactor are available.
How it Works:
The system operates by using a blower to supply air, which is heated by a heat source. The hot gas enters the direct contact exchanger and moves upward through a high-efficiency packed bed, which provides a large heat transfer surface area. Cool water is introduced at the top, flowing downward and coming into contact with the hot gas, resulting in rapid heating of the water. The heated water is collected in a sump section and pumped through a heat exchanger to reheat return heat transfer liquid in a closed-loop cycle. The cleaned, reduced-temperature gas, now saturated with water vapor, exits the top of the unit.
Materials of Construction:
The shell and internal components are typically made from 304L stainless steel, with an option for 316L stainless steel.
Capacity Size Range:
The system can handle heated liquid rates from 5 to 1500 gallons per minute, depending on gas volume and saturation temperature, with a 2-degree approach.
Typical Applications and Uses:
Applications include pre-heating boiler feed water, heating process liquids, pasteurization, space heating of buildings, and reduction of acid gases including CO2.
Contact Information:
Bionomic Industries, Inc., 777 Corporate Drive, Mahwah, New Jersey 07430. Tel: 800-311-6767, 201-529-1094. Fax: 201-529-0252. Email: [email protected]. Website: www.bionomicind.com
See more

Catalog excerpts

QSense Waste Heat Recovery Systems-1

QSense™ Waste Heat Recovery Systems Overview: Efficiently recover valuable waste heat BTU’s from hot gases to heat water or other liquids the direct contact way with a QSense™ Heat Exchanger. An optimal solution to reduce energy consumption and save on expensive fuel costs, while at the same time cleaning the flue gas contaminants and reducing the exhaust temperature. This highly efficient counter current flow exchanger can be used for process heating applications or to meet or supplement building space heating needs. Almost any hot waste flue gas source can be used originating from process or power sources including boilers, kilns, ovens, dryers, thermal oxidizers and incinerators. The QSense™ Heat Exchanger is offered in a vertical configuration for maximum space savings and with all necessary system components for complete one source responsibility. For flue gases containing acid contaminants the unit can be equipped with neutralizing chemical reagents. For particulate laden gas streams, a pre-scrubber and clog resistant contactor is available. How it Works: Air supplied by a blower (1) is raised in temperature by the heat source (2). The hot gas enters the direct contact exchanger inlet (3) and travels upward through a high efficiency packed bed (4) with over 30 sq. ft./cu. ft. of active heat transfer surface area. Cool water is introduced at the top of the unit through a liquid distributor (5) where it comes into intimate counter current contact with the hot gas in the packed bed as it travels downward. Sensible heat transfer between the colder water and hot gas occurs resulting in rapid heat up of the water. The heated water drains into the sump section (6) and is pumped (7) through a plate and frame or shell and tube heat exchanger (8) to reheat return heat transfer liquid in a complete closed loop cycle. Cleaned reduced temperature gas now saturated with water vapor exits out of the top of the unit (9). Available Materials of Construction: • Shell and internal components are offered standard in 304L stainless steel construction. • 316L stainless steel optional. Capacity Size Range: • Heated liquid rates from 5 through 1500 gpm depending on gas volume and saturation temperature within a 2 degree approach. Typical Applications and Uses: Pre-heat boiler feed water Heat up of process liquids Pasteurization Space heating of Buildings Reduction of acid gases including CO2 Bionomic Industries, Inc. • 777 Corporate Drive, Mahwah, New Jersey 07430 • Tel: 800-311-6767 • 201-529-1094 • Fax: 201-529-0252 e-mail: [email protected] • Visit us at our website: www.bionomicind.com

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.