Using the float spindle extension (bfs 070001), add. 13mm/ 0.5" Calculation of float size T = top of cell to top of separator T1 = top of cell to base of float T2 = top of cell to top of electrolyte level The filling level T2 on the list is an average with a tolerance of +/- 2,0mm (0.075"). For stationary batteries mainly T2 is deciding!