Special Cable KW6

Special Cable KW6

Special Cable KW6

Product catalog summary
Product Overview: The Special Cable KW6 is designed to connect the Compact Flame Controller with burner management systems. It features a unique shield combination of copper braiding and metal foil for protection against electrical, electrostatic, and electromagnetic fields.
Material and Resistance: Made from thermoplastic polyether-polyurethane, the cable is resistant to hydrolysis, low temperatures, microorganisms, oils, fats, oxygen, and ozone. It also boasts high wear, abrasion resistance, tensile strength, and tear resistance.
Technical Specifications:
  • Nominal Voltage: 300/500 V
  • Test Voltage: 3 kV/1 min
  • Isolation Resistor: Minimum 20 MΩxkm at +20 °C
  • Conductor Resistor: Maximum 39 Ω/km at +20 °C
  • Capacity: Wire/Wire < 70 pF/m, Wire/Shield < 140 pF/m
  • Inductance: Wire/Wire < 0.6 µH/m, Wire/Shield < 0.4 µH/m
  • Temperature Range: Flexible use -30 °C to +90 °C, Fixed installation -40 °C to +90 °C
  • Bending Radius: Flexible use 14 × D, Fixed installation 9 × D, One-time ring winding 5 × D
Construction Details:
  • Conductors: CU-ETP1, 16 × 0.2 mm blank
  • Wire Isolation: PP, halogen-free
  • Wire Colors: White, brown, pink, green, yellow, grey, blue, red
  • Wire Cross-section: 0.5 mm²
  • Single Shielding: 7 × 0.25 mm tinned
  • Overall Shielding: Cu-braid tinned, approx. 85% tightness
  • Outer Jacket: PUR, Color: Yellow
  • Outer Diameter: 10.7 mm ± 0.3 mm
  • Weight: Approx. 0.15 kg/m
Standards Compliance:
  • Flame Retardancy: IEC 60332-1-2
  • Oil Resistance: EN 60811-2-1
See more

Catalog excerpts

Special Cable KW6-1

PRODUCT INFORMATION PART-NO. 6060-0680-00 Special Cable KW6 The Special Cable KW6 connects the Compact Flame Controller with the burner management. The special shield combination made of copper braiding and metal foil offers highly efficient protection against electrical, electrostatic and electromagnetic fields. The Special Cable made of thermoplastic polyetherpolyurethane has excellent resistance to hydrolysis, flexibility at low temperatures and resistance to microorganisms as well as high resistance to oils, fats, oxygen and ozone. It also has high wear and abrasion resistance as well as high tensile strength and excellent tear resistance. Nominal voltage Test voltage Isolation resistor Conductor resistor wire/wire wire/shield wire/wire wire/shield Continuous temperature range flexible use fixed installation Smallest bending radius flexible use fixed installation one time ring winding BFI Automation Mindermann GmbH | Ruegenstr. 7 . 42579 Heiligenhaus . Germany T +49 2056 98946-0 . [email protected] . www.flamonitec.com Technical changes reserved. | © BFI Automation Mindermann GmbH 2024/21

 Open the catalog to page 1
Special Cable KW6-2

CU-ETP1 in accordance with DIN EN 13602 16 × 0.2 mm blank Wire isolation PP in accordance VDE 0207 halogen free Wire colors white, brown, pink, green, yellow, grey, blue, red Wire cross-section Overall shielding Cu-braid tinned, opt. tightness approx. 85 % Outer jacket Outer diameter 3 | Standards Flame retardancy in accordance with IEC 60332-1-2 Oil resistance in accordance with EN 60811-2-1 BFI Automation Mindermann GmbH | Ruegenstr. 7 . 42579 Heiligenhaus . Germany T +49 2056 98946-0 . [email protected] . www.flamonitec.co

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.