Manual Motor-Starters
6Pages

{{requestButtons}}

Catalog excerpts

Manual Motor-Starters - 3

DescriptionSpecification Type PackWeightpcs.kg/pc. > BusbarFor 2 units 3-pole, 99mm long MU25A-D99 100,036BusbarFor 3 units 3-pole, 154mm long MU25A-D154 100,060BusbarFor 4 units 3-pole, 208mm long MU25A-D208 100,084BusbarFor 5 units 3-pole, 262mm long MU25A-D262 100,107Supply Block3-pole for use with busbar connector MU25A-DB 100,034Protection Coverfor unused busbar terminations MU25A-BS 100,003Spacing piece TEfor ambient temperature >40ݰC P730 100,013 Current LimiterFor increasing the fault breaking MU25A-ID50 10,172capacity of single unit or group back-up to 50kA at 3~415V, above setting...

Open the catalog to page 3
Manual Motor-Starters - 4

Type MU25A Main ContactsRated insulation voltage U > 1) i V~ 690Rated operational current I > e (=I > th ) open, at 50CA25 Mechanical life S x 10 > 6 0,1 Contact life at I > 6 e /AC3S x 10 0,1 Tripping class according to IEC 60947-4-110A Rated ultimate short-circuit breaking capacity I > cu 220-240V AC380-415V AC500V AC660-690V ACValues for open unit, when incoming supply on upper terminals Setting rangeto 1AkA1001001001001 - 1,6AkA1001001001001,6 - 2,5AkA10010032,52,5 - 4AkA10010032,54 - 6,3AkA10010032,56,3 - 10AkA1006/50 > 2) 32,510 - 16AkA10/100 > 2) 6/50 > 2) 2,5216 - 20AkA10/100 > 2)...

Open the catalog to page 4

All BENEDIKT & JÄGER catalogs and technical brochures

  1. Switches

    97 Pages

  2. Push Buttons

    30 Pages

  3. Main Switches

    21 Pages