LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 1

LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Multi-channel AC, pulsed DC and AC/DC sensitive residual current monitors for earthed AC, DC and AC/DC systems (TN and TT systems)

Open the catalog to page 1
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 2

Multi-channel AC, pulsed DC and AC/DC sensitive residual current monitors for earthed AC, DC and AC/DC systems (TN and TT systems) Product description RCMS460-D…/-L… and RCMS490-D…/-L… The RCMS system consists of one or more RCMS460-D/-L or RCMS490-D/-L residual current monitors, which are able to detect and evaluate fault, residual and operating currents in earthed power supplies via the related measuring current transformers. The maximum voltage of the system to be monitored depends on the nominal insulation voltage of the measuring current transformer used in the case of busbar systems,...

Open the catalog to page 2
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 3

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Digital input Each individual channel can be used for one of the following monitoring functions: – s digital input using a potential-free contact 1/0 A – r for current or residual current monitoring in combination O with measuring current transformers. History memory in RCMS460-D, RCMS490-D The device utilises a history memory for failsafe storing of up to 300 data records (date, time, channel, event code, measured value), so that all data about an outgoing circuit or an area can be traced back at any time (what happened...

Open the catalog to page 3
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 4

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Overview of device types Distinctive device features Parameter setting function Master/Slave Address range Measuring channels per device CTAC…, CTUB100, CTBS25, WR…S(P), WS…, W…F series measuring current transformers CT monitoring AC/DC sensitive 0…2000 Hz (Type B) Measuring circuit Rated residual operating current I∆n2 (Alarm) pulsed DC sensitive 42…2000 Hz (Type A) pulsed DC sensitive 42…2000 Hz (Type A) for the channels 9…12 (RCMS4x0-D4/-L4) Rated residual operating current I∆n1 (prewarning) Function selectable per channel...

Open the catalog to page 4
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 5

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Operating and display elements RCMS460-D 1 - ED ALARM “2” lights up when the measured value falls beL low or exceeds the response value in a measuring channel or an error is indicated by the digital input. 2 - ED “ALARM 1” lights up if the measured value exceeds or L falls below the “Prewarning” response value in a channel or in the event of device error. 3 - ower On LED “ON” lights up when the device is switched on P or flashes until the device is ready for operation during switching on. 4 - Illuminated graphic LCD 5 - “INFO”...

Open the catalog to page 5
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 6

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Connection of supply voltage Us (see ordering information): we recommend the use of 6 A fuses. C onnection of measuring current transformers CT1…CT12. Either Type A or Type B measuring current transformers can be selected for each measuring channel. Six CTUB100 series measuring current transformers require one STEP-PS power supply unit. The channels k9…k12 of the device versions RCMS460-D4/-L4 require the connection of Type A measuring current transformers. BMS bus (RS-485 interface with BMS protocol) External reset button...

Open the catalog to page 6
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 7

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Connection CTAC…, WR…, WS… series measuring current transformers (pulsed current sensitive) Connection CTUB100 series measuring current transformer (AC/DC current sensitive) S1(k) S2(l) Potentiometer CTXS-… Voltage supply (STEP-PS…) STEP-PS + surge protection device Connection WF… series measuring current transformers Anschluss Messstromwandler Serie CTBS25 (allstromsensitiv) L1 L2 L3 N The connections k and l at the residual current monitor must not be interchanged.

Open the catalog to page 7
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 8

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Example for a design of a – minimum system consisting of an RCMS460-D and 12 measuring points Measuring current transformers AC/DC sensitive (0…2000 Hz) Measuring current transformers pulsed DC sensitive (42…2000 Hz) Distribution board Series CTAC…, WR…, WS…, WF… Series CTUB100, CTBS25 Example for a system design of – standard system consisting of an RCMS460-D and RCMS460-L and a protocol converter COM465IP Note: 1 - hen usingAC/DC current sensitive measuring current transW formers of the CTUB100 and CTBS25 series , a DC 24 V...

Open the catalog to page 8
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 9

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 for the versions: a) RCMS4x0-D1 Supply voltage Us Supply voltage frequency Rated insulation voltage 100 V Rated impulse voltage/pollution degree 2.5 kV/3 Overvoltage category III Protective separation (reinforced insulation) between (A1, A2) - (k1, l…k12, R, T/R, T, A, B) Voltage test acc. to IEC 61010-1 1.344 kV Rated insulation voltage 250 V Rated impulse voltage/pollution degree 4 kV/3 Overvoltage category III Basic insulation between (A1, A2), (k1,...

Open the catalog to page 9
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 10

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Interface Interface/protocol RS-485/BMS Baud rate 9.6 kbit/s Cable length 0…1200 m Cable (shielded, shield connected to PE on one side) recommended: min. J-Y(St)Y min. 2x0.8 For UL application: Copper lines Terminating resistor Device address, BMS bus at least 60/70 °C 120 Ω (0.25 W) connectable via DIP switch 1…90 (2)* Cable lengths for CTAC…, WR…, WS…, WF… series measuring current transformers Single wire ≥ 0.75 mm² 0…1 m Single wire, twisted ≥ 0.75 mm² 0…10 m Shielded cable ≥ 0.5 mm² 0…40 m Cable (shielded, shield connected...

Open the catalog to page 10
LINETRAXX® RCMS460-D/-L – RCMS490-D/-L - 11

Residual current monitors LINETRAXX® RCMS460-D/-L – RCMS490-D/-L Ordering information RCMS460/490-D Differential measurement method pulsed DC sensitive AC/DC sensitive Common alarm relay Alarm relay per channel 4 channels for load current measurement – Ordering information RCMS460/490-L Current measurement pulsed DC sensitive 6 mA…20 A Common alarm relay for all channels Alarm relay per channel Accessories Description

Open the catalog to page 11

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages