video corpo

LINETRAXX® RCMB330
4Pages

{{requestButtons}}

Catalog excerpts

LINETRAXX® RCMB330 - 1

LINETRAXX® RCMB330 AC/DC sensitive residual current monitoring module with integrated divisible measuring current transformer

Open the catalog to page 1
LINETRAXX® RCMB330 - 2

AC/DC sensitive residual current monitoring module with integrated divisible measuring current transformer Product description The RCMB330 residual current monitoring modules are intended for measuring AC and DC fault currents in earthed systems (TN and TT systems). The modules are able to measure residual currents IΔ = 10…500 mA in a frequency range of DC…100 kHz. Two separately adjustable response values allow a distinction to be made between prewarning and main alarm. The modules feature an RS-485 interface with Modbus RTU which can be used to transfer measured values and alarm values....

Open the catalog to page 2
LINETRAXX® RCMB330 - 3

AC/DC sensitive residual current monitoring module LINETRAXX® RCMB330 Installation instructions • Do not route any shielded cables through the measuring current transformer! • Device damage due to interference pulses! The connecting cable (supply, analogue interface…) must not be routed directly past the current transformer core/primary conductor. Protective conductors and live conductors Make sure that all current-carrying cables are routed through the measuring current transformer. Unlock current transformer core Press both elements together simultaneously and flip the RCMB330 open Never...

Open the catalog to page 3
LINETRAXX® RCMB330 - 4

Technical data (continued) Connection Refer to chapter “LED” in the manual. Interface Interface/protocol Baud rate Cable length Environment/EMC EMC IEC 62020-1 Operating temperature -25…70 °C Classification of climatic conditions acc. to IEC 60721 Stationary use (IEC 60721-3-3) 3K23 (except condensation and formation of ice) Transport (IEC 60721-3-2) 2K11 (except condensation and formation of ice) Long-term storage (IEC 60721-3-1) 1K22 (except condensation and formation of ice) Classification of mechanical conditions acc. to IEC 60721 Stationary use (IEC 60721-3-3) 3M11 Transport (IEC...

Open the catalog to page 4

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2