ISOSCAN® EDS440/441 Insulation fault locators for localisation of insulation faults in unearthed DC, AC and three-phase power supply systems (IT systems) From serial number: 2000…

Open the catalog to page 1
ISOSCAN® EDS440/441 - 2

Insulation fault locators for localisation of insulation faults in unearthed DC, AC and three-phase power supply systems (IT systems) Product description The insulation fault locators ISOSCAN® EDS44x are used in connection with the ISOMETER® iso685-D-P or the locating current injector PGH to locate insulation faults in unearthed power supply systems (IT systems). They detect locating current signals generated by the insulation monitoring device iso685-D-P or the locating current injector PGH and evaluate them correspondingly. Up to 12 measuring current transformers can be connected to an...

Open the catalog to page 2
ISOSCAN® EDS440/441 - 3

Insulation fault locators ISOSCAN® EDS440/441 Device variants EDS44…-L Alarm messages are directly indicated on the device display Observe the applicable national and international standards. The EDS44x series meets the device standards: EDS44…-S Alarm messages are displayed on the respective ISOMETER® Option “W” Devices with the suffix “W” feature increased shock and vibration resistance. The electronics is covered with a special varnish to provide increased protection against mechanical stress and moisture. Operating and display elements EDS44x EDS440-S EDS440-L 1 - he “ON” LED flashes...

Open the catalog to page 3
ISOSCAN® EDS440/441 - 4

Insulation fault locators ISOSCAN® EDS440/441 Connection to the voltage supply M+ Dig. current output Ground A RS-485 A (output) B RS-485 B (output) Input 1 Input 2 RS-485 A (input) RS-485 B (input) Back-up fuse voltage supply If the device is supplied via an external power supply unit, the back-up fuse F at connection “A1/+ A2/-” must be selected in such a way that the feeding power supply unit is able to trip the DC-compatible back-up fuse. Example: A back-up fuse of 650 mA/T is recommended when using a 24-V power supply unit (min. 1 A). Connection of relays First and last device in a bus...

Open the catalog to page 4
ISOSCAN® EDS440/441 - 5

Insulation fault locators ISOSCAN® EDS440/441 Connection measuring current transformer CTAC…, WR…, WS… series Connection of CTAF…SET series measuring current transformers to EDS440-LAF-4 For insulation fault location, the measuring current transformers of the CTAC… (closed), WR… (rectangular) and WS… (split-core) series are used. For insulation fault location, the measuring current transformers of the CTAF…SET series are used. CTAF 1 Connecting measuring current transformers of the CTBC… series to EDS441-LAB-4

Open the catalog to page 5
ISOSCAN® EDS440/441 - 6

Insulation fault locators ISOSCAN® EDS440/441 Wiring diagram to 3(N)AC system with iso685-D-P Un For systems > 690 V and with overvoltage category III a fuse for the connection to the system to be monitored must be provided. Recommendation: 2A fuses. * Communication between iso685-x-P and EDS44x-L only via BS bus (RS-485). Wiring diagram to DC system with iso685-D-P Un * Communication between iso685-x-P and EDS44x-L only via BS bus (RS-485). 6 EDS44xx_D00201_10_D_XXEN/10.2021

Open the catalog to page 6
ISOSCAN® EDS440/441 - 7

Insulation fault locators ISOSCAN® EDS440/441 Wiring diagram to AC system with ISOMETER® iso685-D-P Un * Communication between iso685-x-P and EDS44x-L only via BS bus (RS-485). Connection example: ISOMETER® iso685-D-P, EDS440-S, IOM441-S and EDS440-L Un External signal * Communication between iso685-x-P and EDS44x-L only via BS bus (RS-485).

Open the catalog to page 7
ISOSCAN® EDS440/441 - 8

Insulation fault locators ISOSCAN® EDS440/441 Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Definitions Supply circuit (IC1) A1, A2 Output circuit 1 (IC2) 13, 14 Output circuit 2 (IC3) 23, 24 Control circuit (IC4) (A1, A2), (13,14)-(23,24)-(X1, X3) Rated voltage 1000 V Overvoltage category III Range of use ≤ 2000 m AMSL Rated impulse voltage IC1/(IC2-4) 4 kV IC2/(IC3-4) 4 kV IC3/(IC4) 4 kV Rated insulation voltage IC1/(IC2-4) AC 250 V IC2/(IC3-4) 250 V IC3/IC4 250 V 3 Pollution degree outside (Un < 690 V) 2 Pollution degree outside (Un > 690 < 1000 V) Protective...

Open the catalog to page 8
ISOSCAN® EDS440/441 - 9

Insulation fault locators ISOSCAN® EDS440/441 Technical data (continuation) Rated insulation voltage 4 kV Kontaktdaten nach IEC 60947-5-1 GebrauchskategorieAC-13/AC-14/DC-12/DC-12/DC-12/DC-12 Bem.betriebsspannung 230 V/230 V/24 V/48 V/110 V/220 V Bem.betriebsstrom 5 A/3 A/1 A/1 A/0.2 A/0.1 A Max. switching capacity 300 W/2770 VA Max. switching voltage DC 30 V/AC 277 V Minimum contact rating 1 mA at AC/DC ≥ 10 V Environment/EMC EMC IEC 61326-2-4 Ambient temperatures Operating temperature -25 °C… +55 °C Transport -40 °C… +85 °C Storage -25 °C…+70 °C Classification of climatic conditions acc....

Open the catalog to page 9
ISOSCAN® EDS440/441 - 10

Insulation fault locators ISOSCAN® EDS440/441 Ordering information Response value Absolute values Suitable system components DI-2USB (interface converter RS-485/USB) with USB cable Plug kit, screw terminals1) Plug kit, push-wire terminals Mechanical accessories (terminal cover, 2 mounting clips) 1) BB bus 4TE Connector 2) included in the scope of delivery included in the scope of delivery of EDS44x-S-4 Measuring current transformer for EDS440 Design type Alternative measuring current transformer from the Bender program Internal diameter/mm Design type Internal diameter/mm For further...

Open the catalog to page 10
ISOSCAN® EDS440/441 - 11

Insulation fault locators ISOSCAN® EDS440/441 Measuring current transformer for EDS441 Measuring current transformer for EDS441-LAB Design type Internal diameter/mm Design type Internal diameter/mm Alternative measuring current transformer from the Bender program Design type circular circular, 6-fold split-core Internal diameter/mm Measuring current transformer for EDS440-LAF Design type For further information regarding the measuring current transformers, refer to the respective data sheets. Characteristic curve for response sensitivity Network configuration, mains voltage, mains...

Open the catalog to page 11
ISOSCAN® EDS440/441 - 12

Fault curve EDS440…/EDS441… An insulation fault location beyond the grey area causes an error message. The EDS44…-L indicates error messages via flashing LEDs. Use an EDS44…-S, then the fault messages are indicated via the ISOMETER®. EDS440 Insulation fault location not possible Permissible range Insulation fault location not possible Permissible range Insulation fault location possible Insulation fault location 1,5 Bender GmbH & Co. KG Londorfer Straße 65 • 35305 Grünberg • Germany Tel.: +49 6401 807-0 • info@bender.de • www.bender.de BENDER Group EDS44xx_D00201_10_D_XXEN / 10.2021 / ©...

Open the catalog to page 12

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages