ISOMETER® isoRW685W-D - 1

ISOMETER® isoRW685W-D Insulation monitoring device for IT AC systems with galvanically connected rectifiers and converters and for IT systems especially for railway applications Preliminary data sheet

Open the catalog to page 1
ISOMETER® isoRW685W-D - 2

Insulation monitoring device for IT AC systems with galvanically connected rectifiers and converters and for IT systems especially for railway applications Product description The ISOMETER® isoRW685W-D is an insulation monitoring device for IT systems in accordance with IEC 61557-8 for railway applications and has been specifically tested according to DIN EN 50155. It is universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variable-speed drives). Application • C, DC or AC/DC main circuits A • C/DC main...

Open the catalog to page 2
ISOMETER® isoRW685W-D - 3

• Communication protocol Modbus TCP • Communication protocol Modbus RTU The ISOMETER® has been developed in compliance with the following standards: • BCOM for Bender device communication via Ethernet • BS bus for communication of Bender devices (RS-485) • Integrated web server for reading out measured values and for parameter setting Measurement method The series isoRW685W-D operates using the patented AMPPlus measurement method. This measurement method allows concise monitoring of modern power supply ystems, also in case of extensive, directly connected DC compos nents and high system...

Open the catalog to page 3
ISOMETER® isoRW685W-D - 4

Example AGHxxx Connection to an AC system Un Connection to a DC system Un Connection to an IT system with coupling device Connection to a 3(N)AC system C onnection to the IT system to be monitored (L1/+, L2, L3/-) Separate connection of KE, E to PE ( K1) Alarm relay 1, available changeover contacts ( K2) Alarm relay 2, available changeover contacts 9 - Switchable resistor R for RS-485 bus termination 10 - Ethernet interface 11 - Digital interface * - systems > 690 V and with overvoltage category III a fuse For for the connection to the system to be monitored must be provided....

Open the catalog to page 4
ISOMETER® isoRW685W-D - 5

Digital interface X1 Digital interface Configurable digital inputs (e.g. test, reset, …) Serial interface RS-485, termination by means of a DIP switch R. Supply voltage of the inputs and outputs I, Q and M. Electrical overload protection. Automatic shutdown in the event of short circuits and transients (resettable). When supplied via an external 24 V source, A1/+, A2/- must not be connected. Configurable digital output Deactivate Device high active TEST RESET +24 V + Q1 Q2 M+ active adjustable Configurable analogue output (e.g. measuring instrument) Reference potential ground Dimension...

Open the catalog to page 5
ISOMETER® isoRW685W-D - 6

Technical data Insulation coordination according to IEC 60664-1/IEC 60664-3 Definitions: Measuring circuit (IC1) Supply circuit (IC2) Output circuit 1 (IC3) Output circuit 2 (IC4) Control circuit (IC5) Rated voltage Overvoltage category Rated impulse voltage: IC1/(IC2-5) IC2/(IC3-5) IC3/(IC4-5) IC4/IC5 Rated insulation voltage: IC1/(IC2-5) IC2/(IC3-5) IC3/(IC4-5) IC4/IC5 Pollution degree outside (Un < 690 V) Pollution degree outside (Un >690 < 1000 V) Safe isolation (reinforced insulation) between: IC1/(IC2-5) IC2/(IC3-5) IC3/(IC4-5) IC4/IC5 Voltage test (routine test) according to IEC...

Open the catalog to page 6
ISOMETER® isoRW685W-D - 7

Technical data (continued) Interfaces Field bus Interface/protocol Data rate Max. amount Modbus requests Cable length Connection IP address Network mask BCOM address Function Connection Connection type web server/Modbus TCP/BCOM 10/100 Mbit/s, autodetect < 100/s ≤ 100 m RJ45 DHCP/manual 192.168.0.5 255.255.255.0 system-1-0 communication interface Sensor bus Interface/protocol RS-485/isoData/BS bus/Modbus RTU Data rate 9.6 kBaud/s Cable length ≤ 1200 m Cable: twisted pair, one end of shield connected to PE recommended: J-Y(St)Y min. 2x0.8 Connection terminals X1.A, X1.B Terminating resistor...

Open the catalog to page 7
ISOMETER® isoRW685W-D - 8

Ordering information Nominal system voltage range Un AC 0…690 V; 1…460 Hz Suitable system components Description A set of screw terminals A set of push-wire terminals Enclosure accessories (terminal cover, 2 mounting clips) 1) 1) included in the scope of delivery Coupling devices Suitable measuring instruments on request! Bender GmbH & Co. KG Londorfer Straße 65 • 35305 Grünberg • Germany Tel.: +49 6401 807-0 • info@bender.de • www.bender.de BENDER Group isoRW685W-D_D00178_11_D_XXDE / 01.2022 / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account...

Open the catalog to page 8

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages