video corpo

ISOMETER® isoPV1685...
6Pages

{{requestButtons}}

Catalog excerpts

ISOMETER® isoPV1685... - 1

ISOMETER® isoPV1685… Insulation monitoring device for unearthed photovoltaic systems up to AC 1000V* and DC 1500 V From serial number: 2108…

Open the catalog to page 1
ISOMETER® isoPV1685... - 2

Insulation monitoring device for unearthed photovoltaic systems up to AC 1000V* and DC 1500 V Product description The device is used for insulation of large photovoltaic systems up to AC 1000 V*/DC 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against earth exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs...

Open the catalog to page 2
ISOMETER® isoPV1685... - 3

Ordering details Response value range 200 Ω…1 MΩ Nominal system voltage Un Absolute values Not for UL applications Wiring diagram 3 AC system Digital input 1: isoPV1685RTU: Test/Standby isoPV1685P: Starting the insulation fault location in the manual mode 1 - I2+, I2– Digital input 2: isoPV1685RTU: Reset/(Memory) isoPV1685P: No function 2 - CAN2, CAN1 Connection to CAN bus, 2 x RJ-45, can be terminated with CAN 120-Ω termination plug. 3 - RS-485 Term. DIP switch for the termination of the RS-485 interface Connection to Modbus or BMS bus, RS-485, S= shield (connect one end to PE), can be...

Open the catalog to page 3
ISOMETER® isoPV1685... - 4

Response time for insulation measurement isoPV1685... Response times insulation resistance measurement 1000 In the case of a leakage capacitance of 2000 µF, the measuring range for the insulation resistance is limited to 50 kΩ. The measurable leakage capacitance depends on the insulation resistance Minimum limiting condition for determining the value of the capacitance The determination of the leakage capacitance depends on the size of the insulation resistance. Example: In the case of an insulation resistance of 50 kΩ , the minimum measurable leakage capacitance is 35 μF. In the case of an...

Open the catalog to page 4
ISOMETER® isoPV1685... - 5

Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Insulation coordination acc. to IEC 60664-1 Rated voltage Rated impulse voltage/pollution degree Voltage ranges Nominal system voltage Un isoPV1685RTU AC 0…1000 V*/DC 0…1500 V (* not for UL applicatons) isoPV1685P DC 0…1500 V Nominal frequency 50/60 HZ ±1 Hz Tolerance of Un AC +10%/DC +6 % Supply voltage Us (refer also to device name plate) DC 18…30 V Power consumption ≤7W Measuring circuit for insulation monitoring Measuring voltage Um (peak value) Measuring current Im (at RF = 0 Ω) Internal DC resistance Ri Impedance...

Open the catalog to page 5
ISOMETER® isoPV1685... - 6

Technical data (continued) Other Classification of climatic conditions acc. to IEC 60721: Without solar radiation, precipitation, water, icing. Condensation possible temporarily: Stationary use (IEC 60721-3-3) 3K23 Transport (IEC 60721-3-2) 2K11 Long-term storage (IEC 60721-3-1) 1K22 Classification of mechanical conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) Transport (IEC 60721-3-2) Long-term storage (IEC 60721-3-1) Operating mode Position of normal use PCB fixation Tightening torque Degree of protection, internal components Degree of protection, terminals Documentation...

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages