ISOMETER® isoGEN423
6Pages

{{requestButtons}}

Catalog excerpts

ISOMETER® isoGEN423 - 1

ISOMETER® isoGEN423 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) up to 3(N)AC, AC 400 V, DC 400 V Suitable for the application of generators acc. to standard DIN VDE 0100-551

Open the catalog to page 1
ISOMETER® isoGEN423 - 2

Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) up to 3(N)AC, AC 400 V, DC 400 V Suitable for the application of generators acc. to standard DIN VDE 0100-551 Product description The ISOMETER® monitors the insulation resistance of unearthed AC, AC/DC and DC systems (IT systems) with nominal system voltages of 3(N)AC, AC/DC 0…400 V or DC 0…400 V. The maximum permissible system leakage capacitance Ce is 5 μF. DC components existing in AC systems do not influence the operating characteristics, when a minimum load current of DC 10 mA flows. A separate supply...

Open the catalog to page 2
ISOMETER® isoGEN423 - 3

If the values RF or Un do not violate their release value (response value plus hysteresis) for the period toff without interruption, the alarm relays will switch back to their initial position and the alarm LEDs AL1/AL2 stop lighting. If the fault memory is activated, the alarm relays remain in alarm condition and the LEDs light until the reset button “R” is pressed or the supply voltage is interrupted. The device function can be tested using the test button “T”. Parameters are assigned to the device via the LCD and the control buttons on the front panel; this function can be...

Open the catalog to page 3
ISOMETER® isoGEN423 - 4

Test / Reset If supplied from an IT system, both lines have to be protected by a fuse.* Connect each terminal separately to PE: The same wire cross section as for A1, A2 is to be used. L1/+, L2/– Connection to the IT system to be monitored T/R Connection for the external combined test and reset button. 11, 14 Connection to alarm relay K1 11, 24 Connection to alarm relay K2 A, B RS-485 communication interface with connectable terminating resistance. * For UL applications: Only use 60/75°C copper lines! For UL and CSA applications, it is mandatory to use 5 A fuses for the protection of the...

Open the catalog to page 4
ISOMETER® isoGEN423 - 5

Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Definitions: Measuring circuit (IC1) Supply circuit (IC2) Output circuit (IC3) Control circuit (IC4) Rated voltage Overvoltage category Rated impulse voltage: IC1/(IC2-4) IC2/(IC3-4) IC3/IC4 Rated insulation voltage: IC1/(IC2-4) IC2/(IC3-4 ) IC3/IC4 Polution degree Protective separation (reinforced insulation) between: IC1/(IC2-4) IC2/(IC3-4) IC 3/IC4 Voltage test (routine test) according to IEC 61010-1: IC2/(IC3-4 ) IC 3/IC4 Overvoltage category III, 600 V Overvoltage category III, 300 V Overvoltage category III, 300 V...

Open the catalog to page 5
ISOMETER® isoGEN423 - 6

Push-wire terminals: Nominal current Conductor sizes Stripping length Rigid Flexible without ferrules Flexible with ferrules with/without plastic sleeve Multi-conductor flexible with TWIN ferrules with plastic sleeve Opening force Test opening, diameter Other Operating mode continuous operation Mounting cooling slots must be ventilated vertically Degree of protection, built-in components (DIN EN 60529) IP30 Degree of protection, terminals (DIN EN 60529) IP20 Enclosure material polycarbonate DIN rail mounting acc. to IEC 60715 Screw fixing 2 x M4 with mounting clip Documentation number...

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages