ISOMETER® isoCHA425 - 1

ISOMETER® isoCHA425 Insulation monitoring device for unearthed DC systems (IT systems) DC 50 V up to 400 V Suitable for the charging of electric vehicles acc. to Japanese charging standard CHAdeMO

Open the catalog to page 1
ISOMETER® isoCHA425 - 2

Insulation monitoring device for unearthed DC systems (IT systems) DC 50 V up to 400 V Suitable for the charging of electric vehicles acc. to Japanese charging standard CHAdeMO Product description The ISOMETER® monitors the insulation resistance of DC charging stations according to the Japanese charging standard CHAdeMO for voltages between DC 50 V and 400 V. Asymmetric insulation faults are reported with a response time ≤ 1 second. Symmetrical insulation faults within 10 seconds. The maximum permissible system leakage capacitance Ce is 2 μF. In order to meet the requirements of applicable...

Open the catalog to page 2
ISOMETER® isoCHA425 - 3

The ISOMETER® uses the serial hardware interface RS-485 with the following protocols: • BMS The BMS protocol is an essential component of the Bender measuring device interface (BMS bus protocol). Data transmission takes place with ASCII characters. • Modbus RTU Modbus RTU is an application layer messaging protocol and it provides Master/Slave communication between devices that are connected altogether via bus systems and networks. Modbus RTU messages have a 16-bit CRC (Cyclic Redundant Checksum), which guarantees reliability. • IsoData The ISOMETER® continuously sends an ASCII data string...

Open the catalog to page 3
ISOMETER® isoCHA425 - 4

Operating elements 1 - ED “ON” (operation LED) flashes in case of interruption of the L connecting wires E/KE or L1/+/L2/- or system fault. 2 - larm LED “AL1”, lights when the values fall below the set A response value Alarm 1 and flashes in case of interruption of the connecting wires E/KE or L1/+/L2/-, or system faults as well as in the case of overvoltage (can be activated). 3 - larm LED “AL2” lights when the values fall below the set A response value Alarm 2 and flashes in case of interruption of the connecting wires E/KE or L1/+/L2/- or system faults as well as in the case of...

Open the catalog to page 4
ISOMETER® isoCHA425 - 5

Technical data Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Definitions: Measuring circuit (IC1) L+, L Supply circuit (IC2) A1, A2 Output circuit (IC3) 11, 14, 24 Control circuit (IC4) E, KE, T/R, A, B Rated voltage 400 V Overvoltage category III Rated impulse voltage: IC1/(IC2-4) 6 kV IC2/(IC3-4) 4 kV IC3/IC4 4 kV Rated insulation voltage: IC1/(IC2-4) 400 V IC2/(IC3-4) 250 V IC3/IC4 250 V Polution degree 3 Protective separation (reinforced insulation) between: IC1/(IC2-4) Overvoltage category III, 600 V IC2/(IC3-4) Overvoltage category III, 300 V IC 3/IC4 Overvoltage category...

Open the catalog to page 5
ISOMETER® isoCHA425 - 6

BENDER Group isoCHA425_D00352_02_D_XXEN / 07.2021 / © Bender GmbH & Co. KG, Germany – Subject to change! The specified standards take into account the edition valid until 07.2021 unless otherwise indicated. Bender GmbH & Co. KG Londorfer Straße 65 • 35305 Grünberg • Germany Tel.: +49 6401 807-0 • info@bender.de • www

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages