ISOMETER® iso685-…-P Insulation monitoring device with integrated locating current injector for IT AC systems with galvanically connected rectifiers or converters and for IT DC systems

Open the catalog to page 1
ISOMETER® iso685-...-P - 2

Insulation monitoring device with integrated locating current injector for IT AC systems with galvanically connected rectifiers or converters and for IT DC systems Device features iso685-…-P • ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and for IT DC systems (IT = unearthed systems) • Automatic adaptation to the existing system leakage capacitance • Combination of AMPPLUS and other profile-specific measurement methods • Two separately adjustable response value ranges of 1 kΩ…10 MΩ for Alarm 1 and Alarm 2 • High-resolution graphical LC display • Connection...

Open the catalog to page 2
ISOMETER® iso685-...-P - 3

Insulation monitoring function Insulation fault location The insulation monitoring device continuously monitors the entire insulation resistance of an IT system during operation and triggers an alarm when the value falls below a preset response value. To obtain a measurement the device has to be connected between the IT system (unearthed system) and the protective earth conductor (PE). A measuring current in the μA range is superimposed onto the system which is recorded and evaluated by a microprocessor-controlled measuring circuit. The measuring time is dependent on the selected...

Open the catalog to page 3
ISOMETER® iso685-...-P - 4

ISOloop Ring systems are a special type of coupled systems in which all systems can be coupled to form a ring interconnection. The ISOloop function ensures that, in a system with several insulation monitoring devices, one device is always actively measuring. The devices that work in an ISOloop configuration are combined into a group. Within the group, digital inputs are used to control which devices are currently working together in a team. Within the team, the device with the lowest BCOM address takes over the measuring task. The basis of the ISOloop function is the combination of several...

Open the catalog to page 4
ISOMETER® iso685-...-P - 5

7 1 - Connection to an AC system Un 2 - Connection to a DC system Un 3 - inked with two IT systems which can be interconnected via a L coupling switch. Information regarding the state of the coupling switch is not necessary. 4 - Connection to a 3(N)AC system 5 - onnection to the IT system to be monitored (L1/+, L2, L3/-) C 6 - Separate connection of KE, E to PE 7 - K1) Alarm relay 1, available changeover contacts ( 8 - K2) Alarm relay 2, available changeover contacts ( 9 - Switchable resistor R for RS-485 bus termination 10 - Ethernet interface 11 - Digital interface * - systems > 690 V and...

Open the catalog to page 5
ISOMETER® iso685-...-P - 6

Dimension diagram Panel cut-out FP200 Digital interface X1 Digital interface Input 1 Input 2 Input 3 RS-485 A RS-485 B +24 V Output 1 Output 2 Analogue output Ground Deactivate Device high active TEST RESET +24 V + Q1 Q2 M+ active adjustable

Open the catalog to page 6
ISOMETER® iso685-...-P - 7

Connection example ISOMETER® with insulation fault locators Un ISOSCAN® ISOSCAN® System setup CTAC… CTAC…

Open the catalog to page 7
ISOMETER® iso685-...-P - 8

Technical data Insulation coordination according to IEC 60664-1/IEC 60664-3 Measuring circuit Definitions: Measuring circuit (IC1) (L1/+, L2, L3/-) Supply circuit (IC2) A1, A2 Output circuit 1 (IC3) 11, 12, 14 Output circuit 2 (IC4) 21, 22, 24 Control circuit (IC5) (E, KE), (X1, ETH, X3, X4) Rated voltage 1000 V Overvoltage category III Rated impulse voltage: IC1/(IC2-5) 8 kV IC2/(IC3-5) 4 kV IC3/(IC4-5) 4 kV IC4/IC5 4 kV Rated insulation voltage: IC1/(IC2-5) 1000 V IC2/(IC3-5) 250 V IC3/(IC4-5) 250 V IC4/IC5 250 V 3 Pollution degree for accessible parts on the outside of the device housing...

Open the catalog to page 8
ISOMETER® iso685-...-P - 9

Interfaces Field bus: Interface/protocol Data rate Max. amount Modbus requests Cable length Connection IP address Network mask BCOM address Function ISOnet: Number ISOnet devices Max. nominal system voltage range ISOnet Connection Connection type web server/Modbus TCP/BCOM 10/100 Mbit/s, autodetect < 100/s ≤ 100 m RJ45 DHCP/manual* 192.168.0.5* 255.255.255.0* system-1-0 communication interface 0…20 devices AC 690 V/DC 1000 V EDSsync: Number EDSsync devices ISOloop Number ISOloop devices Sensor bus: Interface/protocol Data rate Cable length Cable: twisted pair, one end of shield connected to...

Open the catalog to page 9
ISOMETER® iso685-...-P - 10

Ordering information Insulation fault locators Supply voltage Us Response value Insulation fault locators Absolute values Suitable system components Description A set of screw-type terminals A set of push-wire terminals Enclosure accessories (terminal cover, 2 mounting clips) 1) Transparent cover 144x72 (IP65) for FP200 2) BB bus 6TE connector 3) 1) Description Device version without display Display for front panel mounting Suitable measuring instruments on request! included in the scope of delivery If the “transparent front cover 144x72 (IP65)” is used, the cutout in the control cabinet...

Open the catalog to page 10

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages