ISOMETER® IR1575 - 1

ISOMETER® IR1575 Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

Open the catalog to page 1
ISOMETER® IR1575 - 2

Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Product description The ISOMETER® of the IR1575 series monitor the insulation resistance of unearthed main circuits (IT systems) AC, 3(N)AC 0…480 V resp. DC 0… 480 V. The AMP measurement method allows the Isometers to be used in systems with directly connected DC components. Taking the system leakage capacitances into account, the IR1575 automatically adapts itself to the existing system conditions in order to optimise the measuring time. An external supply voltage allows de-energised systems...

Open the catalog to page 2
ISOMETER® IR1575 - 3

Wiring diagram – Operating elements Wiring diagram – Mains connection 1 - TEST” button: to call up the self test “ Arrow up button: Parameter changes, scroll 2 - RESET” button: to delete alarm and fault messages “ Arrow down button: Parameter changes, scroll 3 - MENU” button: to call up the menu system “ Enter button: to confirm parameter changes 4 - LC display 2 x 16 characters 5 - Alarm LED “1” lights: insulation fault, first warning level reached 6 - Alarm LED “2” lights: insulation fault, second warning level reached 7 - xternal test button “T1/T2” (N/O contact) E 8 - xternal reset...

Open the catalog to page 3
ISOMETER® IR1575 - 4

Technical data Insulation coordination acc. to IEC 60664-1 Rated insulation voltage AC 500 V Rated impulse withstand voltage/pollution degree 4 kV/3 Voltage ranges Nominal system voltage Un Nominal frequency fn Supply voltage Us Power consumption AC, 3(N)AC 0...480 V, DC 0.480 V DC, 30.420 Hz see ordering information < 5 VA Switching elements Number of switching elements Operating principle Factory setting Contact class Rated contact voltage Making capacity Breaking capacity Response values Response value Rani (Alarm 1) Response value Ran2 (Alarm 2) Relative uncertainty Response time...

Open the catalog to page 4
ISOMETER® IR1575 - 5

Measuring time Dimension diagram Dimensions in mm Ordering information Design Increased shock and vibration resistance 1) Absolute values

Open the catalog to page 5
ISOMETER® IR1575 - 6

E& BENDER The Power in Electrical Safety6 Bender GmbH & Co. KG P.O. Box 1161 • 35301 Gruenberg • Germany Londorfer Strasse 65 • 35305 Gruenberg • Germany Tel.: +49 6401 807-0 • Fax: +49 6401 807-259 E-Mail: info@bender.de • www.bender.de BENDER Group

Open the catalog to page 6

All BENDER catalogs and technical brochures

  1. CTBC17

    2 Pages

  2. POWERSCOUT®

    8 Pages

  3. Energy meter

    6 Pages

  4. RDC121

    7 Pages

  5. RCMB123

    7 Pages

  6. RCMB 121-2

    7 Pages

  7. RCMB121-1

    7 Pages

  8. RDC104-4

    6 Pages

  9. 300ST

    4 Pages

  10. 400ST

    4 Pages

  11. USC710D4

    6 Pages

  12. DI-1DL

    4 Pages

  13. DI-2

    4 Pages